Plan Review Details - Permit 18090633
Plan Review Stops For Permit 18090633
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-04-29 Cont ID  
Sent By dbattles Date 2019-04-29 Time 09:20 Rev Time 0.00
Received By dbattles Date 2019-04-29 Time 09:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-03-18 Cont ID  
Sent By dbattles Date 2019-03-18 Time 08:29 Rev Time 0.00
Received By dbattles Date 2019-03-14 Time 16:47 Sent To  
Notes
2019-03-18 08:30:27****CORRECTIONS****
 W.P.B. PERMIT: 18090633
 REVIEWED: MARCH 18, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 311.3 FBC[R] FLOORS AND LANDINGS AT EXTERIOR DOORS.
 THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH
 EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL BE NOT
 LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A
 DIMENSION OF NOT LESS THAN 36 INCHES (914 MM) MEASURED
 IN THE DIRECTION OF TRAVEL. THE SLOPE AT EXTERIOR
 LANDINGS SHALL NOT EXCEED 1/4 UNIT VERTICAL IN 12 UNITS
 HORIZONTAL (2 PERCENT).
 -PLEASE ADD LANDING OUTLINE AND LANDING DIMENSIONS TO
 FLOOR PLAN.
  
 2) 602 FBC[R] WOOD WALL CONSTRUCTION.
 -PROVIDE CONNECTOR TYPE AND SPACING FOR BASE PLATE TO
 FOUNDATION.
 -PROVIDE CONNECTOR AND SPACING OF LEDGER BOARD AND WALL
 STUDS TO EXISTING STRUCTURE.
  
 3) 107.3.4 FBC[AMENDED] PREVIOUS COMMENT WAS TO PROVIDE
 PRODUCT APPROVALS. THE RESPONSE WAS TO SEE NOTE 1A, 2
 AND 3.
 -NOTE 1A HAS NINE DOORS LISTED WITH THE PRODUCT
 APPROVAL NUMBER LISTED. PLEASE SELECT THE ONE TO BE
 USED AND PRINT OUT TWO COPIES OF THE PRODUCT APPROVAL.
 MAKE SURE IT IS APPROVED FOR FLORIDA BUILDING CODE 6 TH
 EDITION 2017.
 ALSO, WE NEED TWO COPIES OF THE PRODUCT APPROVAL FOR
 THE LAUNDRY ROOM DOOR.
  
 3) 602.3(3)TABLE FBC[R] REQUIREMENTS FOR WOOD
 STRUCTURAL PANEL WALL SHEATHING USED TO RESIST WIND
 PRESSURES.
 -PROVIDE SHEATHING NAIL SIZE AND SPACING FROM TABLE
 R602.3(3).
  
 4) THIS COMMENT IS NOT FROM THE BUILDING CODE. THIS IS
 A GENERAL OBSERVATION AND NO RESPONSE IS REQUIRED.
 -FROM THE LOOK OF LAUNDRY DOOR AND WATER HEATER
 PLACEMENT I DO NOT SEE HOW YOU WOULD GET TWO APPLIANCES
 IN THE SPACE. WHEN ONE APPLIANCE IS IN IT BLOCKS THE
 DOOR AND MAY HINDER THE NEXT APPLIANCE FROM GETTING
 INTO SPACE. MAYBE MOVE WATER HEATER DOWN OR CONSIDER
 DOUBLE DOORS.
  
 5) 905.2.2 FBC[R] & 905.1.1 FBC[R] FOR ROOF SLOPES FROM
 TWO UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) AND
 LESS THAN FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL
 (4:12), DOUBLE UNDERLAYMENT APPLICATION IS REQUIRED.
 -ADD ROOF PITCH TO PLANS AND ADD NOTE FOR DOUBLE
 UNDERLAYMENT IS PITCH IS LESS THAN FOUR UNITS VERTICAL
 IN 12 UNITS HORIZONTAL (4:12)
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS.
 FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE
 REQUIRED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-11-08 Cont ID  
Sent By dbattles Date 2018-11-08 Time 08:29 Rev Time 0.00
Received By dbattles Date 2018-11-07 Time 15:45 Sent To  
Notes
2018-11-08 08:29:41****CORRECTIONS****
 W.P.B. PERMIT: 18090633
 REVIEWED: NOVEMBER 7, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FL. STATUTE 471]DOCUMENTS PREPARED BY AN
 ARCHITECT/ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED, DATED ORIGINALS.
 PLEASE SIGN AND SEAL A-101 AND A-102(BOTH SETS)
  
 2. [FBC AMENDED 107.3.5] PROJECT DATA:
 OCCUPANCY = R-3 ?
 AREA TABULATIONS = STATE WHAT IS EXISTING UNDER AIR
 AND, PROPOSED NEW AMOUNT AND TOTAL THAT WILL NOW BE
 UNDER AIR.
 [FBC EXISTING 501]STATE THE LEVEL OF ALTERATION FOR
 WORK BEING PERFORMED.
 STATE CODE EDITION BEING USED FOR ALL TRADES.
 WE ARE CURRENTLY USING FLORIDA BUILDING CODE(FBC), 6TH
 EDITION (2017)
 BASIC WIND SPEED=170
 RISK CATEGORY = II ?
 EXPOSURE CATEGORY = B,C OR D ?
 BUILDING CLASSIFICATION = ENCLOSED ?
 MEAN BLDG. HGT. = 0 FT.-0 IN. ?
 WIND SPEED V ULT = 170 ?
 WIND SPEED V ASD = 132 ?
 INTERNAL PRESSURE COEFFICIENT GCPI = +/-0.18
  
 3. [FBC ENERGY R503.1.1]BUILDING ENVELOPE. BUILDING
 ENVELOPE ASSEMBLIES THAT ARE PART OF THE ALTERATION
 SHALL COMPLY WITH SECTION R402.1.2 OR R402.1.4,
 SECTIONS R402.2.1 THROUGH R402.2.13, R402.3.1,
 R402.3.2, R402.4.3 AND R402.4.5
  
 4. [FBC EXISTING 807.2]NEW STRUCTURAL ELEMENTS.
 NEW STRUCTURAL ELEMENTS IN ALTERATIONS, INCLUDING
 CONNECTIONS AND ANCHORAGE, SHALL COMPLY WITH THE
 FLORIDA BUILDING CODE, BUILDING.
 PROVIDE IN-FILL DETAIL, DOOR/WINDOW BUCK DETAILS AND
 NEW COVERED LAUNDRY AREA CONSTRUCTION DETAILS.
  
 5. [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVALS FOR
 WINDOWS AND DOORS, OR INDICATE THAT YOU WOULD LIKE THEM
 DEFERED.
 PROVIDE NEW DOOR/WINDOWS DESIGN PRESSURES AND SIZES.
  
 6. [FBC AMENDED 107.3.5]IF NEW ROOF OVER THE LAUNDRY
 AREA PROVIDE PRODUCT APPROVAL FOR ROOFING MATERIAL TO
 BE USED.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-03-18 Cont ID  
Sent By jpearson Date 2019-03-18 Time 09:33 Rev Time 0.00
Received By jpearson Date 2019-03-18 Time 09:33 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-05 Cont ID  
Sent By jpearson Date 2018-10-05 Time 14:34 Rev Time 0.00
Received By jpearson Date 2018-10-05 Time 14:34 Sent To  
Notes
2018-10-05 14:34:11CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS
 471, 481
 2. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB
 FBC 107.2.1, 107.3.5; FS 471 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-10-18 Cont ID  
Sent By jesmith Date 2018-10-18 Time 14:01 Rev Time 0.00
Received By jesmith Date 2018-10-18 Time 13:59 Sent To  
Notes
2019-03-07 16:21:41THE REQUIREMENT FOR GAS HAS BEEN ELIMINATED. THERE IS
 NO GAS ON THE SITE. JESMITH 3/7/2019
2018-10-18 14:01:26REQUIREMENT FOR GAS IS ON THE PLAN. A REVIEW HAS NOT
 BEEN MADE AT THIS TIME. APPLICATION FOR GAS PERMIT MUST
 BE SUBMITTED ALONG WITH PLANS COMPLYING WITH THE
 FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-04-29 Cont ID  
Sent By dbattles Date 2019-04-29 Time 09:20 Rev Time 0.00
Received By dbattles Date 2019-04-25 Time 15:41 Sent To  
Notes
2019-04-26 15:41:15RESUB ROUTED TO DBATTLES

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-03-18 Time   Rev Time 0.00
Received By lmarchan Date 2019-02-28 Time 13:21 Sent To  
Notes
2019-03-01 13:21:26R04

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-08 Cont ID  
Sent By dbattles Date 2018-11-08 Time 08:31 Rev Time 0.00
Received By dbattles Date 2018-09-14 Time 10:07 Sent To  
Notes
2018-09-17 10:07:55R32

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2019-04-29 Cont ID  
Sent By dbattles Date 2019-04-29 Time 09:21 Rev Time 0.00
Received By dbattles Date 2019-04-29 Time 09:21 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-11-08 Cont ID  
Sent By dbattles Date 2018-11-08 Time 08:30 Rev Time 0.00
Received By dbattles Date 2018-11-08 Time 08:30 Sent To  
Notes
2018-11-08 08:31:07DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 [FBC AMENDED 109]PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-03-16 Cont ID  
Sent By cmontell Date 2019-03-16 Time 06:15 Rev Time 0.00
Received By cmontell Date 2019-03-16 Time 05:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-10-23 Cont ID  
Sent By cmontell Date 2018-10-23 Time 09:17 Rev Time 0.00
Received By cmontell Date 2018-10-23 Time 09:17 Sent To  
Notes
2018-10-22 14:36:36MECHANICAL PLAN REVIEW FAIL
  
 1 - NEED MECHANICAL PLAN PER2017 FLORIDA BUILDING CODE
 - BUILDING SEC 107
  
 2 - NEED EQUIPMENT SIZING (MANUAL J) PER 2017 FLORIDA
 BUILDING CODE - ENERGY CONSERVATION SEC R403.7
  
 3 - NEED COMPLIANCE REPORT PER 2017 FLORIDA BUILDING
 CODE - ENERGY CONSERVATION SEC R405.4.2.1
  
  
 CHRIS MONTELLO
 561-805-6673

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-03-07 Cont ID  
Sent By jesmith Date 2019-03-07 Time 16:25 Rev Time 0.00
Received By jesmith Date 2019-03-07 Time 14:28 Sent To  
Notes
2019-03-07 16:24:58APPROVED
 ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-10-18 Cont ID  
Sent By jesmith Date 2018-10-18 Time 13:46 Rev Time 0.00
Received By jesmith Date 2018-10-18 Time 13:45 Sent To  
Notes
2018-10-18 13:45:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. WPB FBC 107.3.5.3(12): PROVIDE SANITARY RISER
 DIAGRAM SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR
 THE DESIGN IN ACCORDANCE WITH FS 471 & 481.; SHOW HOW
 THE NEW SANITARY PIPING WILL INTEGRATE WITH EXISTING
 SYSTEM SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR
 THE DESIGN IN ACCORDANCE WITH FS 471 & 481. CLOUD NEW
 WORK. SHOW ALL REQUIRED DRAINS,TRAPS AND VENTS AND SIZE
 IN ACCORDANCE WITH FBC RES INCLUDING BUT NOT LIMITED
 TO, CHAPTERS 30, 31 AND 32 .
 2. WPB FBC 107.2.1: PLAN A-102 SHOWS RELOCATED WASHER,
 DRYER AND WATER HEATER OUT SIDE OF MAIN STRUCTURE IN AN
 AREA THAT MAY PROVIDE AN OVERHANG AND NO EXTERIOR
 WALLS; PLEASE CLARIFY. PROVIDE MANUFACTURER'S
 DOCUMENTATION ALLOWING APPLIANCES TO BE INSTALLED IN A
 WET AREA.
 3. FBC RES P2708.4: TUB/SHOWER CONTROL VALVE(S) SHALL
 BE PRESSURE BALANCED PB, THERMOSTATIC MIXING (TM) OR
 COMBINATION PB/TM VALVE TYPES WITH HIGH TEMPERATURE
 LIMITING STOP.
 4. FBC RES P2903.5: PROVIDE WATER HAMMER ARRESTORS AT
 WATER SUPPLIES TO ICE LINE, DISHWASHER AND CLOTHES
 WASHER.
 5. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE DETAILED, QUANTITY ESTIMATES, AND/OR BONA
 FIDE SIGNED CONTRACTS WITH SCOPE AND VALUE OF WORK, TO
 INCLUDE ALL MATERIALS AND LABOR. THIS IS FOR TOTAL
 PROJECT, NOT JUST PLUMBING. WPB FBC 109.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471, 481 & FAC 61G15) INTO THE
 ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED
 SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS
 SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2019-03-18 Cont ID  
Sent By dbattles Date 2019-03-18 Time 08:30 Rev Time 0.00
Received By dbattles Date 2019-03-18 Time 08:30 Sent To  
Notes
2019-03-18 08:33:36APPROVED WITH PRODUCT APPROVAL FL5444-R14
 ASPHALT ROOF SHINGLES

Review Stop Z ZONING
Rev No 2 Status P Date 2019-03-11 Cont ID  
Sent By llouie Date 2019-03-11 Time   Rev Time 0.00
Received By llouie Date 2019-03-11 Time   Sent To  
Notes
2019-03-11 11:51:52* SCOPE OF WORK DOES NOT EXCEED 50% VALUE OF THE
 STRUCTURE.
  
 * STRUCTURES IDENTIFIED IN THE SURVEY THAT ENCROACH
 ONTO THE ADJACENT RIGHT-OF-WAY AND DOES NOT SEEM TO BE
 COMPLETED BY PERMIT (I.E. FENCE BLOCKING OFF
 RIGHT-OF-WAY, METAL CONTAINER ENCROACHING INTO ROW)
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-09-28 Cont ID  
Sent By llouie Date 2018-09-28 Time   Rev Time  
Received By llouie Date 2018-09-28 Time   Sent To  
Notes
2018-09-28 16:21:40** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SHOW IN A SITE PLAN THE SETBACK DISTANCE FROM THE
 PROPOSED LAUNDRY CLOSET, LOCATED AT THE SOUTHEAST SIDE
 OF THE RESIDENCE, TO THE PROPERTY LINE(S).
  
 NOTES:
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * SCOPE OF WORK DOES NOT EXCEED 50% VALUE OF THE
 STRUCTURE.
  
 * STRUCTURES IDENTIFIED IN THE SURVEY THAT ENCROACH
 ONTO THE ADJACENT RIGHT-OF-WAY AND DOES NOT SEEM TO BE
 COMPLETED BY PERMIT (I.E. FENCE BLOCKING OFF
 RIGHT-OF-WAY, METAL CONTAINER ENCROACHING INTO ROW)
  
 * ZONE: SF7
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  