Plan Review Details - Permit 18090631
Plan Review Stops For Permit 18090631
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-01-02 Cont ID  
Sent By jwitmer Date 2019-01-02 Time 09:34 Rev Time 0.00
Received By jwitmer Date 2019-01-02 Time 06:45 Sent To  
Notes
2019-01-02 09:34:542017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18090631
 ADD: 871 VILLAGE BLVD. SUITE: 603
 CONT: EVERKLEEN CONSTRUCTION SE
 TEL: 561-818-7082
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. JAN. 02/2019
 ACTION: BUILDING PROVISO
  
 1) SHEET 1.0A:
 1A) NOTE # 3 INDICATES THE WALL DISPLAY UNIT IS OWNER
 SUPPLIED. 2017 FBC-ACCESSIBILITY CODE SECTION 904.4
 SALES AND SERVICE COUNTERS. SALES COUNTERS AND SERVICE
 COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2. THE
 ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND THE
 SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP.
 EXCEPTION: IN ALTERATIONS, WHEN THE PROVISION OF A
 COUNTER COMPLYING WITH 904.4 WOULD RESULT IN A
 REDUCTION OF THE NUMBER OF EXISTING COUNTERS AT WORK
 THE COUNTER SHALL BE PERMITTED TO HAVE A PORTION WHICH
 IS 24 INCHES (610 MM) LONG MINIMUM COMPLYING WITH
 904.4.1 PROVIDED THAT THE REQUIRED CLEAR FLOOR OR
 GROUND SPACE IS CENTERED ON THE ACCESSIBLE LENGTH OF
 THE COUNTER.
  
 1B) NOTE # 5 INDICATES THE RECEPTION DESK IS ALSO OWNER
 SUPPLIED. MUST COMPLY WITH 2017 ACCESS. CODE 904.3.3
 CHECK WRITING SURFACES. WHERE PROVIDED, CHECK WRITING
 SURFACES SHALL COMPLY WITH 902.3 HEIGHT.
 THE TOPS OF WORK SURFACES SHALL BE 28 INCHES MINIMUM
 AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.902.3.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-24 Cont ID  
Sent By jwitmer Date 2018-10-24 Time 13:08 Rev Time 0.00
Received By jwitmer Date 2018-10-24 Time 11:06 Sent To  
Notes
2018-10-24 13:08:442017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18090631
 ADD: 871 VILLAGE BLVD. SUITE: 603
 CONT: EVERKLEEN CONSTRUCTION SE
 TEL: 561-818-7082
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. OCT. 24/2018
 ACTION: DENIED
  
 1) SHEET C-1:
  
 1A) GENERAL NOTES NOTE (1) INDICATES THE PLANS WERE
 DEVELOPED UNDER THE 5TH EDITION OF THE FLORIDA BUILDING
 CODE. PLEASE NOTE THE 6TH EDITION OF THE FLORIDA
 BUILDING CODE, (2017) WAS ADOPTED STATEWIDE
 DEC. 31/ 2017. PLEASE UPDATE PLANS.
  
 1B) UNDER THE HEADING CONSTRUCTION TYPE THE PLANS
 INDICATE III-B AND LEVEL OF ALTERATION AS A LEVEL III.
 PLEASE UNDER THE 2017 FBC-EXISTING BUILDING CODE
 SECTION 505.1 SCOPE. LEVEL 3 ALTERATIONS APPLY WHERE
 THE WORK AREA EXCEEDS 50 PERCENT OF THE BUILDING AREA.
 NOT THE TENANT AREA. PLEASE UPDATE THE PLANS, SHEET
 C-1.
  
 2) SHEET 1.0A:
  
 2A) THE FLOOR PLAN DOES NOT SHOW THE FIXTURES IN THE
 RESTROOM. THE RESTROOM IS INDICATED TO BE ONLY 5 FEET
 WIDE, PLEASE PROVIDE THE LAYOUT OF THE FIXTURES, IT
 APPEARS THAT IT MAY NOT MEET THE REQUIREMENTS FOR AN
 ACCESSIBLE RESTROOM. IF NOT PLEASE SHOW WHERE 20% OF
 THE $125,000.00 DOLLARS ARE BEING USED IN ACCESSIBLE
 UPGRADES AND IN THE ORDER AS DIRECTED UNDER :
 2017 FBC-ACCESSIBILITY CODE SECTION 202.4.1
 DISPROPORTIONATE COST.
 (1) COST ASSOCIATED WITH PROVIDING AN ACCESSIBLE
 ENTRANCE AND AN ROUTE TO THE ALTERED AREAS,
 (2) COST ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE,
 SUCH AS INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS.
 (3) THE DETAIL SHOWN FOR THE ACCESSIBLE RESTROOM SHOWS
 THE ENTRANCE DOOR ON THE SIDE OF THE ROOM NOT THE END
 AS SHOWN IN THE FLOOR PLANS. PLEASE ALSO NOTE THE SIDE
 WALL DOES NOT PROVIDE THE DISTANCE IN FEET AND INCHES
 FOR THIS ROOM.
  
 2B) AT THE REAR OF THE BUILDING THE PLANS INDICATE WHAT
 APPEARS TO BE A BREAK ROOM BUT IS LABELED A KITCHEN.
 PLEASE NOTE THE OVERALL TRAVEL DISTANCE IS OVER 110
 FEET. IN THE 2017 FBC-B TABLE 1006.2.1 IN A SPRINKLERED
 BUILDING THE ALLOWABLE TRAVEL DISTANCE IS 100 FEET,
 THEN REQUIRING A SECOND EXIT IF OVER THAT DISTANCE. THE
 2ND EXIT AT THE REAR OF THE BUILDING TRAVELS THROUGH
 WHAT IS LABELED A KITCHEN. SECTION 1016.2 OF THE FBC-B
 EGRESS THROUGH INTERVENING SPACES. (5) NOT ALLOWED
 THROUGH KITCHENS, YOU MAY WANT TO RELABEL THE USAGE AS
 A BREAK ROOM AS LONG AS THERE WILL BE NO APPLIANCES
 WITH FLAMES, STOVES.
 2C) THE FLOOR PLAN DOES NOT SHOW IF THE FRONT AND REAR
 EXITS ARE ACCESSIBLE MEANS OF EGRESS WITH A LANDING ON
 THE EXTERIOR SIDE OF THE DOOR LESS THAN ? INCH OF
 FINISH FLOOR. SEE ACCESS. CODE 303.2 VERTICAL CHANGES
 IN LEVEL.
  
 2D) THE FLOOR PLAN ALSO SHOWS A RECEPTION DESK WITH A
 HIGH AND LOW COUNTERS. THE PLANS DO NOT SHOW COMPLIANCE
 WITH 2017 ACCESS. CODE 904.3.3 CHECK WRITING SURFACES.
 NOR SERVICE COUNTERS 904.4.
  
 2E) THIS FLOOR PLAN IDENTIFIES A DIAMOND 3 A DISPLAY
 CASE AND DIAMOND 4 WHAT APPEARS TO BE EITHER CHAIRS AND
 OR STOOLS. ADDITIONAL INFORMATION REQUIRED 107.2.1.
 SHOW COMPLIANCE WITH ACCESS. CODE FOR ACCESSIBILITY,
 904.4.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-01-25 Cont ID  
Sent By jpearson Date 2019-01-25 Time 12:09 Rev Time 0.00
Received By jpearson Date 2019-01-25 Time 12:09 Sent To  
Notes
2019-01-25 12:10:56SPOKE WITH CONTRACTOR WHO EXPLAINED SCOPE OF PROJECT.
 VALUE IS GOOD.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-12-20 Cont ID  
Sent By jpearson Date 2018-12-20 Time 13:35 Rev Time 0.00
Received By jpearson Date 2018-12-20 Time 11:22 Sent To  
Notes
2018-12-20 13:35:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 (S)
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
 (NOT PROVIDED.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-02 Cont ID  
Sent By jpearson Date 2018-10-02 Time 09:49 Rev Time 0.00
Received By jpearson Date 2018-10-02 Time 09:49 Sent To  
Notes
2018-10-02 09:49:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 (S)
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-12-14 Cont ID  
Sent By pleduc Date 2018-12-14 Time   Rev Time 0.00
Received By pleduc Date 2018-12-14 Time 13:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-09-18 Cont ID  
Sent By pleduc Date 2018-09-18 Time   Rev Time 0.00
Received By pleduc Date 2018-09-18 Time 11:59 Sent To I
Notes
2018-09-18 13:17:54THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE REAR EXIT LIGHT IS INDICATED IN DIFFERENT
 LOCATIONS ON DIFFERENT SHEETS. THE LOCATION DIRECTLY
 OVER THE REAR OFFICE DOOR MAY BE CONFUSED WITH THE
 ACTUAL EXIT.
  
 THAT EXIT SIGN SHALL BE MORE AWAY FROM DIRECTLY OVER
 THAT DOOR TO AN AREA OUT AND AWAY.
  
 ENSURE REAR EXIT LIGHT IS LOCATED AS SHOWN ON SHEET
 1.2.A.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-08 Cont ID  
Sent By gjohnson Date 2019-01-08 Time 16:26 Rev Time 0.00
Received By gjohnson Date 2018-12-07 Time 10:25 Sent To  
Notes
2018-12-10 10:25:39B03

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-24 Cont ID  
Sent By cpuell Date 2018-10-24 Time 13:34 Rev Time 0.00
Received By cpuell Date 2018-09-14 Time 11:26 Sent To  
Notes
2018-09-17 11:26:54B02

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-10-24 Cont ID  
Sent By jwitmer Date 2018-10-24 Time 13:09 Rev Time 0.00
Received By jwitmer Date 2018-10-24 Time 11:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-12-21 Cont ID  
Sent By ccole Date 2018-12-21 Time 08:45 Rev Time 0.00
Received By ccole Date 2018-12-20 Time 16:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-10-10 Cont ID  
Sent By ccole Date 2018-10-10 Time 16:03 Rev Time 0.00
Received By ccole Date 2018-10-10 Time 15:09 Sent To  
Notes
2018-10-10 16:15:351ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18090631
 10/10/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE VANILLA SHELL PERMIT #18041305 WAS APPROVED WITH
 THE FOLLOWING LIST OF PROVISOS TO BE ADDRESSED UNDER
 THE BUILD-OUT PERMIT. PLEASE PROVIDE THE FOLLOWING
 ITEMS.
  
 A) AC COOLING AND HEATING CALCULATIONS- SECTION
 C403.2.1 FBC EC.
  
 B) DUCT SMOKE DETECTORS ARE REQUIRED IN THE SUPPLY AIR
 SYSTEMS OF EACH NEW 5-TON RTU PER SECTION 606.2.1 FBC
 M. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE
 MANUFACTURER'S SPECIFICATIONS INDICATE SYSTEMS ARE NOT
 CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR.
  
 C) OUTSIDE AIR DAMPERS THAT WILL AUTOMATICALLY CLOSE
 WHEN THE SPACE IS NOT OCCUPIED- C403.2.4.3 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-01-08 Cont ID  
Sent By gjohnson Date 2019-01-08 Time 16:26 Rev Time 0.00
Received By gjohnson Date 2019-01-08 Time 16:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-10-15 Cont ID  
Sent By gjohnson Date 2018-10-15 Time 16:55 Rev Time 0.00
Received By gjohnson Date 2018-10-15 Time 16:47 Sent To  
Notes
2018-10-15 17:21:071ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHOW ALL THE PLUMBING FIXTURES ON THE FLOOR PLAN.
 PER WPB AMEND TO FBC 107.2.1
  
 2. THE DISCHARGE PIPING FROM THE PRESSURE AND
 TEMPERATURE VALVE SHALL DISCHARGE THROUGH AN AIR GAP IN
 THE SAME ROOM. FBC PL 504.6(2)3
  
 3. THE LAVATORIES IN THE BATHROOMS SHALL HAVE
 TEMPERATURE LIMITING DEVISE ON HOT SIDE TO LIMIT
 TEMPERATURE OF THE WATER TO TEMPERED WATER THE VALVE
 SHALL COMPLY WITH ASSE 1070 OR CSA B125.3 . PER FBC PL
 416.4
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2019-02-12 Cont ID  
Sent By eschneid Date 2019-02-12 Time 09:01 Rev Time 0.25
Received By eschneid Date 2019-02-12 Time 08:58 Sent To PC
Notes
2019-02-12 09:02:24APPLICANT PROVIDED VERIFICATION THAT NO PARKING IS
 DIRECTLY BEHIND THE BAY.

Review Stop Z ZONING
Rev No 2 Status F Date 2018-12-31 Cont ID  
Sent By eschneid Date 2018-12-31 Time 16:45 Rev Time 0.25
Received By eschneid Date 2018-12-31 Time 15:19 Sent To  
Notes
2018-12-31 16:50:44FAILED
  
 1) THE RESUBMITTED PLANS SHOW A LANDING AND RAMP
 EXTENDING FROM THE BACK DOOR OF THE BAY. THIS AREA
 CONTAINS PARKING SPACES FOR THE PLAZA. YOU NEED TO
 INCLUDE A SURVEY/SITE PLAN OF THE PARKING AREA AND HOW
 THE PARKING IS AFFECTED. IF THIS LANDING AND RAMP
 ENCROACH INTO THE PARKING SPACES, THEN A MINOR PLANNED
 DEVELOPMENT AMENDMENT TO UPDATE THE SITE PLAN AND
 PARKING TABLES IS REQUIRED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2018-10-12 Cont ID  
Sent By eschneid Date 2018-10-12 Time 11:22 Rev Time 0.25
Received By eschneid Date 2018-10-12 Time 11:22 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved