| 2018-10-25 08:20:22 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18090601 |
| | REVIEWED: OCTOBER 24, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC ENERGY = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. [FBC 107.3.5] THIS IS AN ADDITION, NOT A LEVEL 1 |
| | ALTERATION. |
| | |
| | 2. [FBC 107.2.5]PROVIDE A SURVEY TO SHOW THE LOCATION |
| | ON SITE WITH SET BACKS AND SEPARATION FROM OTHER |
| | STRUCTURE. |
| | |
| | 3. [FBC 107.3.5] |
| | PROVIDE PROJECT DATA: |
| | AREA OF EXISTING |
| | AREA OF NEW ROOM |
| | TYPE OF CONSTRUCTION FOR EXISTING HOUSE |
| | |
| | 4. [FBC 107.3.5] THIS ADDITION DOESN?T MEET DEFINITION |
| | OF A BEDROOM. |
| | -70 SQ. FT MIN. OF AIR CONDITIONED WITH CLOSET AND |
| | MEANS OF ESCAPE. |
| | IT HAS THE 70 SQ. FT., BUT NO CLOSET AND NO MEANS OF |
| | ESCAPE. |
| | ADD CLOSET OR CHANGE ROOM DESIGNATION. |
| | ALSO, PLEASE SHOW DETAILS OF WINDOW-SIZE AND CONNECTION |
| | DETAILS. WHAT IS THE EXISTING WALL SHOWN MADE FROM? HOW |
| | DOES THIS WALL MEET WIND RESISTANCE? |
| | PROVIDE PRODUCT APPROVAL FOR WINDOW, OR INDICATE THAT |
| | YOU WOULD LIKE TO DEFER THE SUBMITTAL. |
| | ALSO, HOW IT MEETS OPENING PROTECTION (IMPACT OR |
| | SHUTTERS). IF SHUTTER SUPPLY THE PRODUCT APPROVAL, OR |
| | INDICATE THAT YOU WANT TO DEFER THE SUBMITTAL. |
| | |
| | 5. [FBC R602.2]DETAIL 1 SAYS EXISTING 2X8 @ 16? O.C. |
| | IT APPEARS THAT ONE WALL IS IN PLACE AND IT IS STATED |
| | THAT 2 WALLS ARE TO BE CONSTRUCTED. |
| | PLEASE PROVIDE A WAY FOR ME TO TELL WHAT IS NEW AND |
| | WHAT IS EXISTING. A DEMO PLAN MAY HELP TO CLARIFY THIS |
| | BY SHOWING EXISTING ROOF AND POST SUPPORTS. |
| | [FBC R602.2]PROVIDE DETAIL OF LEDGER CONNECTION TO |
| | EXISTING STRUCTURE. IF THIS IS EXISTING THEN STATE HOW |
| | IT IS CONNECTED NOW AND HOW THAT WILL MEET WIND UPLIFT. |
| | |
| | 6. [FBC R403.1.4]MINIMUM DEPTH. |
| | EXTERIOR FOOTINGS SHALL BE PLACED NOT LESS THAN 12 |
| | INCHES (305 MM) BELOW THE UNDISTURBED GROUND SURFACE. |
| | WHERE APPLICABLE, THE DEPTH OF FOOTINGS SHALL ALSO |
| | CONFORM TO SECTIONS R403.1.4.1 THROUGH R403.1.4.2. |
| | ALL WALLS WILL NEED FOOTER TO SUPPORT THE DEAD LOADS |
| | AND THE FOOTER WILL NEET TO RESIST UPLIFT FOR A WOOD |
| | FRAMED STRUCTURE. |
| | PROVIDE FLOOR AND ROOF LIVE/DEAD LOADS AND SHOW HOW |
| | UPLIFT RESISTANCE IS PROVIDED BY THE FOOTER AND AT |
| | CONNECTORS OF NEW TO EXISTING. |
| | |
| | 7. [FBC R506.2.3]VAPOR RETARDER. |
| | A 6-MIL (0.006 INCH; 152 ?M) POLYETHYLENE OR APPROVED |
| | VAPOR RETARDER WITH JOINTS LAPPED NOT LESS THAN 6 |
| | INCHES (152 MM) SHALL BE PLACED BETWEEN THE CONCRETE |
| | FLOOR SLAB AND THE BASE COURSE OR THE PREPARED SUBGRADE |
| | WHERE NO BASE COURSE EXISTS. |
| | |
| | 8. [FBC R403.1.6]FOUNDATION ANCHORAGE FOR WOOD SILL |
| | PLATE |
| | |
| | 9. [FBC R318]INDICATE THE MEANS OF TERMITE PROTECTION |
| | PROPOSED AND REFERENCE SECTION R308 FOR STANDARDS. |
| | HOW WILL THE NEW INTERIOR SPACE GET TERMITE PROTECTION |
| | WITH EXISTING SLAB. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |