Plan Review Details - Permit 18090601
Plan Review Stops For Permit 18090601
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-11-30 Cont ID  
Sent By dbattles Date 2018-11-30 Time 12:29 Rev Time 0.00
Received By dbattles Date 2018-11-30 Time 12:29 Sent To  
Notes
2018-11-30 12:36:23PROVISO: DEFERRED SUBMITTAL
 1. PROVIDE PRODUCT APPROVAL FOR IMPACT PROTECTION OF
 EXISTING WINDOW IN ADDITION, OR PROVIDE PRODUCT
 APPROVAL FOR WINDOW TO MEET
 2. MECHANICAL SUB-PERMIT FOR COOLING WILL BE STAND
 ALONE PERMIT WITH THE VALUE AND PLANS TO BE REVIEWED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-25 Cont ID  
Sent By dbattles Date 2018-10-25 Time 08:18 Rev Time 0.00
Received By dbattles Date 2018-10-24 Time 16:19 Sent To  
Notes
2018-10-25 08:20:22****CORRECTIONS****
 W.P.B. PERMIT: 18090601
 REVIEWED: OCTOBER 24, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC 107.3.5] THIS IS AN ADDITION, NOT A LEVEL 1
 ALTERATION.
  
 2. [FBC 107.2.5]PROVIDE A SURVEY TO SHOW THE LOCATION
 ON SITE WITH SET BACKS AND SEPARATION FROM OTHER
 STRUCTURE.
  
 3. [FBC 107.3.5]
 PROVIDE PROJECT DATA:
 AREA OF EXISTING
 AREA OF NEW ROOM
 TYPE OF CONSTRUCTION FOR EXISTING HOUSE
  
 4. [FBC 107.3.5] THIS ADDITION DOESN?T MEET DEFINITION
 OF A BEDROOM.
 -70 SQ. FT MIN. OF AIR CONDITIONED WITH CLOSET AND
 MEANS OF ESCAPE.
 IT HAS THE 70 SQ. FT., BUT NO CLOSET AND NO MEANS OF
 ESCAPE.
 ADD CLOSET OR CHANGE ROOM DESIGNATION.
 ALSO, PLEASE SHOW DETAILS OF WINDOW-SIZE AND CONNECTION
 DETAILS. WHAT IS THE EXISTING WALL SHOWN MADE FROM? HOW
 DOES THIS WALL MEET WIND RESISTANCE?
 PROVIDE PRODUCT APPROVAL FOR WINDOW, OR INDICATE THAT
 YOU WOULD LIKE TO DEFER THE SUBMITTAL.
 ALSO, HOW IT MEETS OPENING PROTECTION (IMPACT OR
 SHUTTERS). IF SHUTTER SUPPLY THE PRODUCT APPROVAL, OR
 INDICATE THAT YOU WANT TO DEFER THE SUBMITTAL.
  
 5. [FBC R602.2]DETAIL 1 SAYS EXISTING 2X8 @ 16? O.C.
 IT APPEARS THAT ONE WALL IS IN PLACE AND IT IS STATED
 THAT 2 WALLS ARE TO BE CONSTRUCTED.
 PLEASE PROVIDE A WAY FOR ME TO TELL WHAT IS NEW AND
 WHAT IS EXISTING. A DEMO PLAN MAY HELP TO CLARIFY THIS
 BY SHOWING EXISTING ROOF AND POST SUPPORTS.
 [FBC R602.2]PROVIDE DETAIL OF LEDGER CONNECTION TO
 EXISTING STRUCTURE. IF THIS IS EXISTING THEN STATE HOW
 IT IS CONNECTED NOW AND HOW THAT WILL MEET WIND UPLIFT.
  
 6. [FBC R403.1.4]MINIMUM DEPTH.
 EXTERIOR FOOTINGS SHALL BE PLACED NOT LESS THAN 12
 INCHES (305 MM) BELOW THE UNDISTURBED GROUND SURFACE.
 WHERE APPLICABLE, THE DEPTH OF FOOTINGS SHALL ALSO
 CONFORM TO SECTIONS R403.1.4.1 THROUGH R403.1.4.2.
 ALL WALLS WILL NEED FOOTER TO SUPPORT THE DEAD LOADS
 AND THE FOOTER WILL NEET TO RESIST UPLIFT FOR A WOOD
 FRAMED STRUCTURE.
 PROVIDE FLOOR AND ROOF LIVE/DEAD LOADS AND SHOW HOW
 UPLIFT RESISTANCE IS PROVIDED BY THE FOOTER AND AT
 CONNECTORS OF NEW TO EXISTING.
  
 7. [FBC R506.2.3]VAPOR RETARDER.
 A 6-MIL (0.006 INCH; 152 ?M) POLYETHYLENE OR APPROVED
 VAPOR RETARDER WITH JOINTS LAPPED NOT LESS THAN 6
 INCHES (152 MM) SHALL BE PLACED BETWEEN THE CONCRETE
 FLOOR SLAB AND THE BASE COURSE OR THE PREPARED SUBGRADE
 WHERE NO BASE COURSE EXISTS.
  
 8. [FBC R403.1.6]FOUNDATION ANCHORAGE FOR WOOD SILL
 PLATE
  
 9. [FBC R318]INDICATE THE MEANS OF TERMITE PROTECTION
 PROPOSED AND REFERENCE SECTION R308 FOR STANDARDS.
 HOW WILL THE NEW INTERIOR SPACE GET TERMITE PROTECTION
 WITH EXISTING SLAB.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-11-29 Cont ID  
Sent By jpearson Date 2018-11-29 Time 17:17 Rev Time 0.00
Received By jpearson Date 2018-11-29 Time 17:17 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-16 Cont ID  
Sent By jpearson Date 2018-09-16 Time 16:53 Rev Time 0.00
Received By jpearson Date 2018-09-16 Time 16:53 Sent To  
Notes
2018-09-16 16:53:19CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.12; FBC RE E3902.16
 2. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 4. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 5. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.16.
 6. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-30 Cont ID  
Sent By dbattles Date 2018-11-30 Time 12:29 Rev Time 0.00
Received By dbattles Date 2018-11-21 Time 14:57 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-25 Cont ID  
Sent By dbattles Date 2018-10-25 Time 08:22 Rev Time 0.00
Received By dbattles Date 2018-09-13 Time 15:19 Sent To  
Notes
2018-09-14 15:19:23R07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2018-12-06 Cont ID  
Sent By dbattles Date 2018-12-06 Time 11:23 Rev Time 0.00
Received By dbattles Date 2018-12-06 Time 11:23 Sent To  
Notes
2018-12-06 11:23:37MU-2018-040266-0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-11-30 Cont ID  
Sent By dbattles Date 2018-11-30 Time 12:30 Rev Time 0.00
Received By dbattles Date 2018-11-30 Time 12:30 Sent To  
Notes
2018-11-30 12:31:56PLEASE CHECK OUT 1 SET OF PLANS, TAKE TO PALM BEACH
 COUNTY FOR IMPACT REVIEW AND RETURN HERE WITH PBC STAMP
 ON ONE SET OF PLANS AND RECEIPT WITH MU NUMBER.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-10-25 Cont ID  
Sent By dbattles Date 2018-10-25 Time 08:21 Rev Time 0.00
Received By dbattles Date 2018-10-25 Time 08:21 Sent To  
Notes
2018-10-25 08:21:49[FBC AMENDED 109]PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-10-15 Cont ID  
Sent By cmontell Date 2018-10-13 Time 09:31 Rev Time 0.00
Received By cmontell Date 2018-10-15 Time 13:08 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2018-11-30 Cont ID  
Sent By dbattles Date 2018-11-30 Time 12:32 Rev Time 0.00
Received By dbattles Date 2018-11-30 Time 12:32 Sent To  
Notes
2018-11-30 12:32:56PROVISO:
 PRODUCT APPROVALS NEED TO BE SUBMITTED WITH ROOFING
 SUB-PERMIT.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-10-25 Cont ID  
Sent By dbattles Date 2018-10-25 Time 08:22 Rev Time 0.00
Received By dbattles Date 2018-10-25 Time 08:22 Sent To  
Notes
2018-10-25 08:25:53REVIEWED: OCTOBER 25, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVALS FOR
 ROOFING, OR INDICATE THAT THEY WILL BE DEFERRED.

Review Stop Z ZONING
Rev No 2 Status P Date 2018-11-28 Cont ID  
Sent By dbattles Date 2018-11-30 Time 12:29 Rev Time 0.00
Received By awooten Date 2018-11-28 Time   Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-09-19 Cont ID  
Sent By awooten Date 2018-09-19 Time   Rev Time  
Received By awooten Date 2018-09-19 Time   Sent To  
Notes
2018-09-19 12:40:34PROVIDE A COPY OF THE SURVEY OF PROPERTY SHOWING
 ADDITION HATCHED AND BUILDING SEPARATION/SETBACK ( 6
 FOOT MINIMUM).
  
 PROVIDE THE DIMENSIONS OF THE FLOOR PLANS.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]