| Plan Review Stops For Permit 18090564 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-12-03 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-12-03 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-12-03 |
Time |
11:03 |
Sent To |
|
|
| Notes |
| 2018-12-03 11:05:31 | PROVISO: | | | PROVIDE SUBMITTAL FOR FLOORING AND UNDERLAYMENT. | | | | | | PLEASE ADVISE, WHAT FLOORING AND UNDERLAYMENT ARE | | | PROPOSED? PLEASE ADVISE VIA EMAIL. IF THE UNDERLAYMENT | | | PRODUCT PROPOSED IS NOT ONE FOR WHICH WE HAVE TEST | | | REPORTS ON FILE, THE FOLLOWING REPORTS ARE REQUIRED: | | | [email protected] | | | DYLAN BATTLES | | | 561-805-6718 | | | | | | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO | | | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST | | | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE | | | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) | | | | | | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM | | | CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | | | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED | | | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | | | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-10-31 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-10-31 |
Time |
09:10 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-10-31 |
Time |
09:10 |
Sent To |
|
|
| Notes |
| 2018-10-31 09:12:23 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 18090564 | | | REVIEWED: OCTOBER 30, 2018 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER I | | | [email protected] | | | 561-805-6718 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC ENERGY = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. [FBC AMENDED 109]PROVIDE A SEPARATE PERMIT | | | APPLICATION FOR ONE OF THE UNITS AND SEPARATE THE PLANS | | | FOR EACH PERMIT. THE 4 TH FLOOR UNIT SHOULD INCLUDE THE | | | WORK ON THE SOFFIT AND PROVIDE WHAT IS BEING USED FOR | | | CEILING INSULATION IN THE ATTIC OR INDICATE WHAT IS | | | EXISTING. | | | | | | 2. [FBC AMENDED 109]PROVIDE PROJECT VALUE FOR EACH UNIT | | | AND PROVIDE CONTRACT FOR EACH AS THE VALUE APPEARS LOW | | | AT 30,000 FOR THE TWO UNITS. | | | | | | 3. [FBC EXISTING 501]THE LEVEL OF ALTERATION SHOULD BE | | | LEVEL 1 ALTERATION AS STRUCTURAL ELEMENTS AND SYSTEMS | | | ARE BEING REMOVED AND REPLACED WITH NEW. | | | | | | 4. [FBC 107.3.5]PROVIDE EXISTING FLOOR PLAN WITH DEMO | | | NOTES TO HELP CLARIFY THE SCOPE OF WORK BEING | | | PERFORMED. | | | | | | 5. [FBC A233]PROVIDE ONE BATHROOM DOOR WITH 29 INCH | | | CLEARANCE. | | | | | | 6. PLEASE ADVISE, WHAT FLOORING AND UNDERLAYMENT ARE | | | PROPOSED? PLEASE ADVISE VIA EMAIL. IF THE UNDERLAYMENT | | | PRODUCT PROPOSED IS NOT ONE FOR WHICH WE HAVE TEST | | | REPORTS ON FILE, THE FOLLOWING REPORTS ARE REQUIRED: | | | | | | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO | | | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST | | | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE | | | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) | | | | | | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM | | | CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | | | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED | | | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | | | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. | | | | | | NOTE: | | | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW | | | OF MATERIALS REQUESTED. | | | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS | | | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | | NEED "VOID", RENDERING THEM NOT USABLE. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2018-12-04 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-12-04 |
Time |
07:49 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-12-04 |
Time |
07:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2018-11-19 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-11-19 |
Time |
08:21 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-11-14 |
Time |
13:20 |
Sent To |
|
|
| Notes |
| 2018-11-19 08:21:21 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | 1. CORRECTED. | | | | | | NEW COMMENT: | | | | | | 2. PLANS ARE NOW SHOWN WITH TWO ADDRESSES AND SHOULD BE | | | SEPARATED INTO SEPARATE PERMIT PACKAGES PER BUILDING | | | COMMENTS. A NEW PERMIT WILL BE REQUIRED FOR ONE OF THE | | | UNITS. WPB FBC 105.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-10-01 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-10-01 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-10-01 |
Time |
10:50 |
Sent To |
|
|
| Notes |
| 2018-10-01 14:17:32 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | (S) | | | | | | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-11-20 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-11-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-11-20 |
Time |
13:31 |
Sent To |
|
|
| Notes |
| 2018-11-20 13:31:41 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | | | | 1) THE LOCATION AND FUNCTION OF THE SMOKE DETECTORS | | | SHALL BE CONFIMRED ON FIRE INSPECTION PER NFPA 101. | | | | | | | | | | | | 2) ANY WORK ON FIRE ALARM EQUIPMENT SHALL BE DONE UNDER | | | SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY | | | CONTRACTORS. | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-09-19 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-09-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-09-18 |
Time |
15:10 |
Sent To |
I |
|
| Notes |
| 2018-09-19 09:54:57 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | | | | 1) THE LOCATION AND FUNCTION OF THE SMOKE DETECTORS | | | SHALL BE CONFIMRED ON FIRE INSPECTION PER NFPA 101. | | | | | | | | | | | | 2) ANY WORK ON FIRE ALARM EQUIPMENT SHALL BE DONE UNDER | | | SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY | | | CONTRACTORS. | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-12-04 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-12-04 |
Time |
08:57 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-11-08 |
Time |
15:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-10-31 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-10-31 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-09-13 |
Time |
15:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2018-10-31 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-10-31 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-10-31 |
Time |
09:12 |
Sent To |
|
|
| Notes |
| 2018-10-31 09:13:27 | LEVEL 1 ALTERATION DUE TO FIRE DAMAGE. | | | NO CHANGE IN AREA OR OCCUPANCY. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2018-12-04 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-12-04 |
Time |
08:58 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-12-04 |
Time |
08:58 |
Sent To |
|
|
| Notes |
| 2018-12-04 09:00:42 | 3RD REVIEW FBC-2017 MECHANICAL | | | PERMIT #18090564 | | | 11/26/2018 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: APPROVED WITH PROVISO: | | | | | | 1) PROVIDE THE CORRECTED M101 PLAN SHEETS FOR UNIT 306. | | | | | | STEVEN KENNEDY, CBO | | | ASSISTANT BUILDING OFFICIAL | | | (561) 805-6710 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2018-11-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-11-26 |
Time |
17:18 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-11-26 |
Time |
17:18 |
Sent To |
|
|
| Notes |
| 2018-11-26 17:24:28 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT #18090564 | | | 11/26/2018 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE CORRECTED M101 PLAN SHEETS FOR UNIT 306. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-10-05 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-10-05 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-10-05 |
Time |
16:16 |
Sent To |
|
|
| Notes |
| 2018-10-05 16:30:55 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #18090564 | | | 10/5/2018 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE ADDRESSES AND UNIT NUMBERS ON THE SUBMITTED AC | | | AND ENERGY CALCULATIONS DO NOT MATCH THE ADDRESSES AND | | | UNIT NUMBERS ON THE PLANS AND PERMIT APPLICATION. | | | | | | 2) M101: THE RETURN TRANSFER GRILLS ARE UNDERSIZED IN | | | THE MASTER BEDROOMS- 50 SQ, INCHES PER 100 CFMS | | | REQUIRED AND ALL AIR FROM THE MASTER SUITE SHALL BE | | | RETURNED PER SECTION 601.6 (2 & 3) FBC M. | | | | | | 3) M101: PROVIDE A CONDENSATE DISPOSAL PLAN- | | | SECTION307.2.1 FBC M. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2018-12-04 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-12-04 |
Time |
08:57 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-12-04 |
Time |
08:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-10-25 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2018-10-25 |
Time |
12:27 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2018-10-09 |
Time |
10:23 |
Sent To |
|
|
| Notes |
| 2018-10-25 12:27:07 | DENIED: AS DISCUSSED WITH THOMAS HICKLING, PM, | | | CONTRACTOR TO PROVIDE CLEAR SCOPE OF WORK ON REVISED | | | PLANS; SCOPE WHICH IS TO BE LIMITED TO PROVIDING NEW | | | INWALL SHOWER AND TUB/SHOWER VALVES AND A NEW SHOWER | | | PAN. | | 2018-10-11 16:34:27 | HOLD : CONTRACTOR TO PROVIDE CLEAR SCOPE ON REVISED | | | PLANS PER THAMAS HICKLING SUPER RESTORATION SERVICES |
|
|