Plan Review Details - Permit 18090564
Plan Review Stops For Permit 18090564
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-12-03 Cont ID  
Sent By dbattles Date 2018-12-03 Time 11:03 Rev Time 0.00
Received By dbattles Date 2018-12-03 Time 11:03 Sent To  
Notes
2018-12-03 11:05:31PROVISO:
 PROVIDE SUBMITTAL FOR FLOORING AND UNDERLAYMENT.
  
 PLEASE ADVISE, WHAT FLOORING AND UNDERLAYMENT ARE
 PROPOSED? PLEASE ADVISE VIA EMAIL. IF THE UNDERLAYMENT
 PRODUCT PROPOSED IS NOT ONE FOR WHICH WE HAVE TEST
 REPORTS ON FILE, THE FOLLOWING REPORTS ARE REQUIRED:
 [email protected]
 DYLAN BATTLES
 561-805-6718
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-31 Cont ID  
Sent By dbattles Date 2018-10-31 Time 09:10 Rev Time 0.00
Received By dbattles Date 2018-10-31 Time 09:10 Sent To  
Notes
2018-10-31 09:12:23****CORRECTIONS****
 W.P.B. PERMIT: 18090564
 REVIEWED: OCTOBER 30, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC AMENDED 109]PROVIDE A SEPARATE PERMIT
 APPLICATION FOR ONE OF THE UNITS AND SEPARATE THE PLANS
 FOR EACH PERMIT. THE 4 TH FLOOR UNIT SHOULD INCLUDE THE
 WORK ON THE SOFFIT AND PROVIDE WHAT IS BEING USED FOR
 CEILING INSULATION IN THE ATTIC OR INDICATE WHAT IS
 EXISTING.
  
 2. [FBC AMENDED 109]PROVIDE PROJECT VALUE FOR EACH UNIT
 AND PROVIDE CONTRACT FOR EACH AS THE VALUE APPEARS LOW
 AT 30,000 FOR THE TWO UNITS.
  
 3. [FBC EXISTING 501]THE LEVEL OF ALTERATION SHOULD BE
 LEVEL 1 ALTERATION AS STRUCTURAL ELEMENTS AND SYSTEMS
 ARE BEING REMOVED AND REPLACED WITH NEW.
  
 4. [FBC 107.3.5]PROVIDE EXISTING FLOOR PLAN WITH DEMO
 NOTES TO HELP CLARIFY THE SCOPE OF WORK BEING
 PERFORMED.
  
 5. [FBC A233]PROVIDE ONE BATHROOM DOOR WITH 29 INCH
 CLEARANCE.
  
 6. PLEASE ADVISE, WHAT FLOORING AND UNDERLAYMENT ARE
 PROPOSED? PLEASE ADVISE VIA EMAIL. IF THE UNDERLAYMENT
 PRODUCT PROPOSED IS NOT ONE FOR WHICH WE HAVE TEST
 REPORTS ON FILE, THE FOLLOWING REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-12-04 Cont ID  
Sent By jpearson Date 2018-12-04 Time 07:49 Rev Time 0.00
Received By jpearson Date 2018-12-04 Time 07:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-11-19 Cont ID  
Sent By jpearson Date 2018-11-19 Time 08:21 Rev Time 0.00
Received By jpearson Date 2018-11-14 Time 13:20 Sent To  
Notes
2018-11-19 08:21:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
  
 NEW COMMENT:
  
 2. PLANS ARE NOW SHOWN WITH TWO ADDRESSES AND SHOULD BE
 SEPARATED INTO SEPARATE PERMIT PACKAGES PER BUILDING
 COMMENTS. A NEW PERMIT WILL BE REQUIRED FOR ONE OF THE
 UNITS. WPB FBC 105.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-01 Cont ID  
Sent By jpearson Date 2018-10-01 Time 14:20 Rev Time 0.00
Received By jpearson Date 2018-10-01 Time 10:50 Sent To  
Notes
2018-10-01 14:17:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 (S)
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-11-20 Cont ID  
Sent By pleduc Date 2018-11-20 Time   Rev Time 0.00
Received By pleduc Date 2018-11-20 Time 13:31 Sent To  
Notes
2018-11-20 13:31:41THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) THE LOCATION AND FUNCTION OF THE SMOKE DETECTORS
 SHALL BE CONFIMRED ON FIRE INSPECTION PER NFPA 101.
  
  
  
 2) ANY WORK ON FIRE ALARM EQUIPMENT SHALL BE DONE UNDER
 SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY
 CONTRACTORS.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-09-19 Cont ID  
Sent By pleduc Date 2018-09-19 Time   Rev Time 0.00
Received By pleduc Date 2018-09-18 Time 15:10 Sent To I
Notes
2018-09-19 09:54:57THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) THE LOCATION AND FUNCTION OF THE SMOKE DETECTORS
 SHALL BE CONFIMRED ON FIRE INSPECTION PER NFPA 101.
  
  
  
 2) ANY WORK ON FIRE ALARM EQUIPMENT SHALL BE DONE UNDER
 SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY
 CONTRACTORS.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-04 Cont ID  
Sent By skennedy Date 2018-12-04 Time 08:57 Rev Time 0.00
Received By skennedy Date 2018-11-08 Time 15:04 Sent To  
Notes
2018-11-09 15:04:43B25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-31 Cont ID  
Sent By dbattles Date 2018-10-31 Time 09:13 Rev Time 0.00
Received By dbattles Date 2018-09-13 Time 15:44 Sent To  
Notes
2018-09-14 15:44:18B09

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-10-31 Cont ID  
Sent By dbattles Date 2018-10-31 Time 09:12 Rev Time 0.00
Received By dbattles Date 2018-10-31 Time 09:12 Sent To  
Notes
2018-10-31 09:13:27LEVEL 1 ALTERATION DUE TO FIRE DAMAGE.
 NO CHANGE IN AREA OR OCCUPANCY.
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-12-04 Cont ID  
Sent By skennedy Date 2018-12-04 Time 08:58 Rev Time 0.00
Received By skennedy Date 2018-12-04 Time 08:58 Sent To  
Notes
2018-12-04 09:00:423RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18090564
 11/26/2018
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: APPROVED WITH PROVISO:
  
 1) PROVIDE THE CORRECTED M101 PLAN SHEETS FOR UNIT 306.
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-11-26 Cont ID  
Sent By ccole Date 2018-11-26 Time 17:18 Rev Time 0.00
Received By ccole Date 2018-11-26 Time 17:18 Sent To  
Notes
2018-11-26 17:24:282ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18090564
 11/26/2018
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE CORRECTED M101 PLAN SHEETS FOR UNIT 306.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-10-05 Cont ID  
Sent By ccole Date 2018-10-05 Time 16:17 Rev Time 0.00
Received By ccole Date 2018-10-05 Time 16:16 Sent To  
Notes
2018-10-05 16:30:551ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18090564
 10/5/2018
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ADDRESSES AND UNIT NUMBERS ON THE SUBMITTED AC
 AND ENERGY CALCULATIONS DO NOT MATCH THE ADDRESSES AND
 UNIT NUMBERS ON THE PLANS AND PERMIT APPLICATION.
  
 2) M101: THE RETURN TRANSFER GRILLS ARE UNDERSIZED IN
 THE MASTER BEDROOMS- 50 SQ, INCHES PER 100 CFMS
 REQUIRED AND ALL AIR FROM THE MASTER SUITE SHALL BE
 RETURNED PER SECTION 601.6 (2 & 3) FBC M.
  
 3) M101: PROVIDE A CONDENSATE DISPOSAL PLAN-
 SECTION307.2.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-12-04 Cont ID  
Sent By skennedy Date 2018-12-04 Time 08:57 Rev Time 0.00
Received By skennedy Date 2018-12-04 Time 08:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-10-25 Cont ID  
Sent By jesmith Date 2018-10-25 Time 12:27 Rev Time 0.00
Received By jesmith Date 2018-10-09 Time 10:23 Sent To  
Notes
2018-10-25 12:27:07DENIED: AS DISCUSSED WITH THOMAS HICKLING, PM,
 CONTRACTOR TO PROVIDE CLEAR SCOPE OF WORK ON REVISED
 PLANS; SCOPE WHICH IS TO BE LIMITED TO PROVIDING NEW
 INWALL SHOWER AND TUB/SHOWER VALVES AND A NEW SHOWER
 PAN.
2018-10-11 16:34:27HOLD : CONTRACTOR TO PROVIDE CLEAR SCOPE ON REVISED
 PLANS PER THAMAS HICKLING SUPER RESTORATION SERVICES