| 2018-10-31 09:44:48 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 18090428 |
| | W. P. B. PERMIT: 17080883 |
| | ADD: 2037 SPRUCE AVE. |
| | CONT: WEST PALM BEACH HOUSING AUTHORITY / CBC1258445 |
| | TEL: 561-676-8442 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. OCT. 31/2018 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A2.3: |
| | |
| | 1A) THE MEN?S RESTROOM DETAIL INDICATES A URINAL THAT |
| | MAY OVERLAP THE CLEAR FLOOR SPACE REQUIRED FOR THE |
| | WATER CLOSET. PLEASE DIMENSION THE CLEAR FLOOR SPACES |
| | FOR ALL OF THE PLUMBING FIXTURES. SHOW CODE COMPLIANCE |
| | FOR: |
| | 2017 FBC-ACCESSIBILITY CODE SECTION 604.3.2 OVERLAP. |
| | THE REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL BE |
| | PERMITTED TO OVERLAP THE WATER CLOSET, ASSOCIATED GRAB |
| | BARS, DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT |
| | HOOKS, SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE |
| | AND CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE |
| | TURNING SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL |
| | BE LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE. |
| | |
| | 1B) DETAIL # 2 RESTROOM ELEVATION DETAILS DETAIL F, |
| | PLEASE DIMENSION THE BOTTOM ELEVATION OF THE MIRROR TO |
| | SHOW COMPLIANCE WITH SECTION 603.3 OF THE FBC-ACCESS. |
| | CODE. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS |
| | SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE |
| | REFLECTING SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE |
| | THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE |
| | LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE |
| | BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890 |
| | MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 1C) BREAK ROOM ELEVATION (6)(A) SHOWS A TOE KICK AND |
| | DOORS, THE PLAN DOES NOT INDICATE THESE ELEMENTS ARE |
| | REMOVABLE FOR A FRONT ENTRY. A SIDE ENTRY CANNOT BE |
| | USED SINCE THE CLEAR FLOOR SPACE FOR THE 48 INCHES |
| | CANNOT BE CENTERED ON THE SINK. PLEASE SHOW COMPLIANCE |
| | WITH 2017 ACCESS. CODE SECTION 606.2 CLEAR FLOOR SPACE. |
| | A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR |
| | A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 1D) BREAK ROOM ELEVATION (6)(B)SHOWS A MICROWAVE IN THE |
| | TOP CABINETS. PLEASE SHOW COMPLIANCE WITH THE 2017 |
| | FBC-ACCESS. CODE SECTIONS: |
| | 308.1 REACH RANGES SHALL COMPLY WITH 308. |
| | 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE |
| | OR MORE OF THE REACH RANGES SPECIFIED IN 308. |
| | 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH |
| | ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, |
| | PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED |
| | TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS (22.2 N) |
| | MAXIMUM. |
| | |
| | 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |