| 2018-10-02 09:46:41 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PLEASE SHOW COMPLIANCE WITH FBC ACC 608.3.1 TRANSFER |
| | TYPE SHOWER COMPARTMENTS. |
| | IN TRANSFER TYPE COMPARTMENTS, GRAB BARS SHALL BE |
| | PROVIDED ACROSS THE CONTROL WALL AND BACK WALL TO A |
| | POINT 18 INCHES FROM THE CONTROL WALL. |
| | |
| | 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 608.4 SEATS. A |
| | FOLDING OR NON-FOLDING SEAT SHALL BE PROVIDED IN |
| | TRANSFER TYPE SHOWER COMPARTMENTS. |
| | 610.3 IN TRANSFER-TYPE SHOWERS, THE SEAT SHALL EXTEND |
| | FROM THE BACK WALL TO A POINT WITHIN 3 INCHES OF THE |
| | COMPARTMENT ENTRY. THE TOP OF THE SEAT SHALL BE 17 |
| | INCHES MINIMUM AND 19 INCHES MAXIMUM ABOVE THE BATHROOM |
| | FINISH FLOOR. SEATS SHALL COMPLY WITH 610.3.1 OR |
| | 610.3.2. |
| | |
| | 3. PLEASE SHOW COMPLIANCE WITH FBC ACC 608.5.1 TRANSFER |
| | TYPE SHOWER COMPARTMENTS. |
| | IN TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS, |
| | FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON |
| | THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM) |
| | MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE |
| | SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL |
| | 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE |
| | SEAT TOWARD THE SHOWER OPENING. |
| | |
| | 4. TEMPERED WATER SHALL BE REQUIRED TO BE DELIVERED |
| | FROM THE LAVATORY. TEMPERED WATER SHALL BE DELIVERED |
| | THROUGH AN APPROVED WATER-TEMPERATURE LIMITING DEVICE |
| | THAT CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL |
| | 416.5 |
| | |
| | 5. THE REFRIGERATOR ICE MACHINE IS NOT SHOWN ON THE |
| | WATER ISOMETRIC. PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 6. A BACKFLOW IS REQUIRED ON THE SUPPLY TO THE ICE |
| | MACHINE. PER FBC PL 608.3 |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |