Plan Review Details - Permit 18090371
Plan Review Stops For Permit 18090371
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2018-12-17 Cont ID  
Sent By cthroop Date 2018-12-17 Time 09:35 Rev Time 0.00
Received By cthroop Date 2018-12-17 Time 09:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2018-12-13 Cont ID  
Sent By cthroop Date 2018-12-13 Time 08:15 Rev Time 0.00
Received By cthroop Date 2018-12-12 Time 16:23 Sent To  
Notes
2018-12-13 08:17:13BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 4TH REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DEMO PLAN SHEET MISSING FROM 2ND SET OF PLANS.
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-12-05 Cont ID  
Sent By cthroop Date 2018-12-05 Time 14:03 Rev Time 0.00
Received By cthroop Date 2018-12-05 Time 14:03 Sent To  
Notes
2018-12-05 14:04:51THIS RE-SUBMITTAL NEEDS TO GO THROUGH THE LIBRARIANS.
 PLEASE ASSIGN BLDG. REVIEW TO SHILL. CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-12-05 Cont ID  
Sent By cthroop Date 2018-12-05 Time 12:04 Rev Time 0.00
Received By cthroop Date 2018-12-05 Time 12:04 Sent To  
Notes
2018-12-05 12:06:18BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. VALUE CHANGED. OK
 2. NEW PLAN SHEETS TO BE SUBMITTED.
2018-11-01 10:30:28ELECTRICAL PLAN REVIEW COMMENTS FROM 9/21/18 EXPLAINED
 THAT ALL SHEETS ARE REQUIRED TO BE SIGNED/SEALED BY THE
 PERSON RESPONSIBLE FOR DESIGN. ON RE-SUBMISSION, ONLY
 THE ELECTRICAL SHEETS HAVE BEEN CORRECTED. JP

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-06 Cont ID  
Sent By shill Date 2018-10-06 Time 14:47 Rev Time 0.00
Received By shill Date 2018-10-06 Time 14:47 Sent To  
Notes
2018-10-06 14:48:03****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. ADDRESS PLUMBING COMMENTS, APPLICABLE FOR BUILDING
 REVIEW (FBC ACCESSIBILITY).
  
 2. FBC 109, VALUE IS TO INCLUDE ALL LABOR, MATERIALS,
 OVERHEAD, PROFIT, INCLUDING ITEMS PROVIDED BY OTHERS.
 PROVIDE A COST BREAKDOWN AND CONTRACT.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-11-01 Cont ID  
Sent By jpearson Date 2018-11-01 Time 10:30 Rev Time 0.00
Received By jpearson Date 2018-11-01 Time 10:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-21 Cont ID  
Sent By jpearson Date 2018-09-21 Time 12:59 Rev Time 0.00
Received By jpearson Date 2018-09-21 Time 09:01 Sent To  
Notes
2018-09-21 12:59:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. THIS PERSON MUST BE A LICENSED DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER.
 PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
 3. PROVIDE ACCURATE RISER DIAGRAM, SHOWING ALL DETAILS
 OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. RISER PROVIDED
 INDICATES THIS IS A 3 PHASE SERVICE, BUT PANEL
 SCHEDULES INDICATE THIS IS A SINGLE PHASE SERVICE.
 PROVIDE CLARIFICATION. NEC 215.5, 230, 250.50, 250.94,
 408.30; WPB FBC 107.2.1
 4. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. LOAD CALCULATION PROVIDED IS NOT
 CODE COMPLIANT. NEC 215.2, 220, 408.30
 5. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-10-30 Cont ID  
Sent By scaldero Date 2018-10-30 Time 10:38 Rev Time 0.00
Received By scaldero Date 2018-10-30 Time 10:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-09-14 Cont ID  
Sent By scaldero Date 2018-09-14 Time 10:41 Rev Time 0.00
Received By scaldero Date 2018-09-14 Time 10:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-12-14 Cont ID  
Sent By gjohnson Date 2018-12-14 Time 10:26 Rev Time 0.00
Received By gjohnson Date 2018-12-05 Time 15:31 Sent To  
Notes
2018-12-06 15:31:19B18

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-05 Cont ID  
Sent By cmontell Date 2018-12-05 Time 12:06 Rev Time 0.00
Received By cthroop Date 2018-11-08 Time 08:30 Sent To  
Notes
2018-10-26 12:58:07B01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-06 Cont ID  
Sent By shill Date 2018-10-06 Time 14:48 Rev Time 0.00
Received By shill Date 2018-09-11 Time 10:37 Sent To  
Notes
2018-09-13 10:37:42B28

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2018-12-14 Cont ID  
Sent By ccole Date 2018-12-14 Time 08:20 Rev Time 0.00
Received By ccole Date 2018-12-14 Time 08:20 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-12-12 Cont ID  
Sent By ccole Date 2018-12-12 Time 14:23 Rev Time 0.00
Received By ccole Date 2018-12-12 Time 14:23 Sent To  
Notes
2018-12-12 14:37:423RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18090371
 12/12/18
  
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1: SIGNATURE OF CONTRACTOR OR QUALIFIER ON
 PLANS REQUIRED: SEE FLORIDA STATUTE 633.021, AND
 SECTION 107.2.1 FBC. WPB AMENDMENTS TO THE FBC: ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 2) M1: IT IS ACKNOWLEDGED THAT THE PARTITIONS LEAVE A
 24" AIR SPACE FOR AIRFLOW, HOWEVER THE PLAN APPEARS TO
 SHOW FLEX DUCT RELOCATED OR EXTENDED TO AREA OF THE NEW
 ROOMS. PLEASE LABEL THE DUCTS ON THE PLAN AS NEW (N),
 EXISTING (E), OR RELOCATED (RE).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2018-11-08 Cont ID  
Sent By ccole Date 2018-11-08 Time 08:26 Rev Time 0.00
Received By ccole Date 2018-11-08 Time 08:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-10-03 Cont ID  
Sent By ccole Date 2018-10-03 Time 09:21 Rev Time 0.00
Received By ccole Date 2018-10-03 Time 09:21 Sent To  
Notes
2018-10-03 09:27:141ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18090371
 10/3/18
  
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE MECHANICAL ALTERATION PLANS SHOWING
 ALL NECESSARY CHANGES TO THE EXISTING SYSTEMS TO
 PROVIDE THE REQUIRED VENTILATION TO THE NEW OFFICES-
 SEE TABLE 403.3.1.1 AND SECTION 601.6 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-12-14 Cont ID  
Sent By gjohnson Date 2018-12-14 Time 10:24 Rev Time 0.00
Received By gjohnson Date 2018-12-14 Time 09:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-12-03 Cont ID  
Sent By tklarge Date 2018-12-03 Time 11:22 Rev Time 0.00
Received By tklarge Date 2018-12-03 Time 10:45 Sent To  
Notes
2018-12-03 11:21:461) A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED AND
 SHALL BE HANDICAPPED ACCESSIBLE PER 2017 FBC-PLUMBING
 TABLE 403.1 & SEC. 410.3, FL. ACCESS. CODE SEC.211.1.
 2) WHERE ARE YOU GETTING THE PLUMBING FIXTURE RATIO
 COUNT FROM ON SHT. P1? THE NUMBER OF PLUMBING FIXTURES
 IS CORRECT BUT THE RATIOS ARE INCORRECT. COMPLY WITH
 2017 FBC-PLUMBING TABLE 403.1 FOR "M" OCCUPANCY.
 3) THE FLOOR PLAN LAYOUT AND NUMBER OF FIXTURES ON SHT.
 A2 DOES NOT CORRELATE WITH SHT.A1 OR P1. SHT. A2 DOES
 NOT SHOW THE DRINKING FOUNTAIN OR SERVICE SINK AND A
 URINAL IS SHOWN IN THE MEN'S RESTROOM. SUBMIT A REVISED
 SHT. A2 THAT CCORRELATES WITH THE OTHER SHEETS.
 4) SUBMIT A WATER RISER DIAGRAM FOR THE ADDED DRINKING
 FOUNTAINS AND SERVICE SINK. WPB AMEND. TO FBC SEC.
 107.3.5.1.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
2018-11-01 10:30:01ELECTRICAL PLAN REVIEW COMMENTS FROM 9/21/18 EXPLAINED
 THAT ALL SHEETS ARE REQUIRED TO BE SIGNED/SEALED BY THE
 PERSON RESPONSIBLE FOR DESIGN. ON RE-SUBMISSION, ONLY
 THE ELECTRICAL SHEETS HAVE BEEN CORRECTED. JP

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-10-02 Cont ID  
Sent By gjohnson Date 2018-10-02 Time 10:34 Rev Time 0.00
Received By gjohnson Date 2018-10-01 Time 15:20 Sent To  
Notes
2018-10-02 10:35:201ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. INDICATE ON THE TYPE OF OCCUPANCY, THE OCCUPANT LOAD
 AND PROVIDE A PLUMBING FIXTURE COUNT BREAKDOWN IT SHALL
 COMPLY WITH FBC PL SEC 403.1 AND TABLE 403.1 IT MAY BE
 REQUIRED TO PROVIDE A WATER FOUNTAIN AND SERVICE SINK
 DEPENDING ON OCCUPANT LOAD.
  
 2. THE RECONFIGURED BATHROOMS SHALL COMPLY WITH FBC ACC
 2017 6TH EDITION SEC 213
 PLEASE SHOW COMPLIANCE WITH THE FOLLOWING
 604.2 LOCATION. THE WATER CLOSET SHALL BE POSITIONED
 WITH A WALL OR PARTITION TO THE REAR AND TO ONE SIDE.
 THE CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES
 MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR
 PARTITION
 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM
 THE REAR WALL.
 604.4 SEATS. THE SEAT HEIGHT OF A WATER CLOSET ABOVE
 THE FINISH FLOOR SHALL BE 17 INCHES MINIMUM AND 19
 INCHES MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
 604.5.1 SIDE WALL. THE SIDE WALL GRAB BAR SHALL BE 42
 INCHES LONG MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL.
 604.5.2 REAR WALL. THE REAR WALL GRAB BAR SHALL BE 36
 INCHES LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF
 THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24
 INCHES MINIMUM ON THE OTHER SIDE.
 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE
 606.2 THE LAVATORY SHALL HAVE A CLEAR FLOOR SPACE. A
 CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR A
 FORWARD APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING
 WITH 306 SHALL BE PROVIDED.
 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  