| 2018-09-17 17:37:35 | 09/17/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE PLANS INDICATE AN EXISTING GAS METER. NOTE: IF |
| | THE EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES, |
| | 2017 FBC FUEL GAS RES. SECS.G2412.4, G2412.8, G2413.1, |
| | G2413.2, G2413.3 |
| | |
| | 2. TYPE OF GAS NEEDS TO BE PUT ON ISOMETRIC AND LABEL. |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 3. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER 2017 FBC FUEL GAS RES. SEC. G2413.2. |
| | |
| | 4. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| | AHEAD OF EACH MP REGULATOR, 2017 FBC FUEL GAS RES. SEC. |
| | G2420.4. |
| | |
| | 5. SUBMIT MANUFACTURER?S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS RES. SEC. |
| | G2408.1. |
| | |
| | 6. A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| | IMMEDIATELY AHEAD OF EACH MP REGULATOR. 2017 FBC FG |
| | RES. SEC. G2420.4. |
| | |
| | 7. REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING |
| | SHALL BE APPROVED FOR OUTDOOR INSTALLATION. 2017 FBC |
| | FUEL GAS RES. SEC. G2421.1. |
| | |
| | 8. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC FUEL |
| | GAS RES. SEC. G2412.4, G2412.8, G2413.1, G2413.2, & |
| | G2413.3. |
| | |
| | 9. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| | DRAWN. WPB AMENDMENTS TO THE FBC SEC. 107.2.1. |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 10. A SUB ELECTRICAL PERMIT MAY BE REQUIRED FOR THE |
| | SOURCE OF IGNITION, WPB AMENDMENTS TO THE FBC SEC 105.1 |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |