Plan Review Details - Permit 18090360
Plan Review Stops For Permit 18090360
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-10-29 Cont ID  
Sent By jwitmer Date 2018-10-29 Time 10:17 Rev Time 0.00
Received By jwitmer Date 2018-10-29 Time 07:56 Sent To  
Notes
2018-10-29 09:47:552017 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 18090360
 W. P. B. PERMIT: 18010368
 ADD: 2481 OKEECHOBEE BLVD.
 CONT: IBIS BUILDING CORP.
 TEL: 561-568-2570
 E-MAIL: [email protected]
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW REVISION
 DATE: MON. OCT. 29/ 2018
 ACTION: BUILDING PROVISO
 1) SHEET A-214. DETAIL C1 ACCESSIBILITY SIGNAGE
 INDICATES THAT IT IS TO BE INSTALLED AT A HEIGHT OF 60
 INCHES VERTICALLY CENTERLINE OF THE SIGN FROM THE
 FINISH FLOOR.
 PLEASE REFER BACK TO THE 2017 FLORIDA ACCESSIBILITY
 CODE FOR SIGNAGE TACTILE CHARACTERS ABOVE FINISH FLOOR
 OR GROUND
 2014 ACCESSIBILITY CODE. 703.4.1 HEIGHT ABOVE FINISH
 FLOOR OR GROUND. TACTILE CHARACTERS ON SIGNS SHALL BE
 LOCATED 48 INCHES MINIMUM ABOVE THE FINISH FLOOR OR
 GROUND SURFACE, MEASURED FROM THE BASELINE OF THE
 LOWEST TACTILE CHARACTER AND 60 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE
 BASELINE OF THE HIGHEST TACTILE CHARACTER.
  
 SIGNAGE. 703.4.1 HEIGHT ABOVE FINISH FLOOR OR GROUND.
 TACTILE CHARACTERS ON SIGNS SHALL BE LOCATED 48 INCHES
 MINIMUM ABOVE THE FINISH FLOOR OR GROUND SURFACE,
 MEASURED FROM THE BASELINE OF THE LOWEST TACTILE
 CHARACTER AND 60 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 OR GROUND SURFACE, MEASURED FROM THE BASELINE OF THE
 HIGHEST TACTILE CHARACTER.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-10-01 Cont ID  
Sent By jpearson Date 2018-10-01 Time 08:25 Rev Time 0.00
Received By fgiaquin Date 2018-10-01 Time 06:23 Sent To  
Notes
2018-10-01 08:25:42WORK HAS BEEN ADDED TO REVISION WITH ZERO INCREASE IN
 VALUE. VALUE WILL BE INCREASED BY $10000 FOR ELECTRICAL
 ONLY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-09-14 Cont ID  
Sent By scaldero Date 2018-09-14 Time 11:17 Rev Time 0.00
Received By scaldero Date 2018-09-14 Time 10:51 Sent To  
Notes
2018-09-14 11:17:51PERMIT # 18090360
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED PROVISO: THE FOLLOWING ITEMS WILL BE REVIEWED
 AT TIME OF FIELD INSPECTION. FAILURE TO COMPLY WITH ALL
 FIRE CODE REQUIREMENTS WILL RESULT IN A FAILED
 INSPECTION UNTIL COMPLIANCE IS MET.
  
 1) SHEET G.002: NORTH EXIT STATES - 3.6" WIDTH REQUIRED
 / 36" WIDTH PROVIDED ---- REMOVE DECIMAL TO CORRECT
 NUMBER
  
 2) SHEET G.002: WEST EXIT STATES - 87.60" WIDTH
 REQUIRED / 52" WIDTH PROVIDED -----PLEASE CORRECT OR
 EXPLAIN DISCREPANCY IN REQUIREMENT.
  
 3) PER NFPA 1: 13.3.2.6* EXTERIOR ROOFS, CANOPIES,
 PORTE-COCHERES, BALCONIES, DECKS, OR SIMILAR
 PROJECTIONS. IN BUILDINGS PROTECTED THROUGHOUT BY
 AUTOMATIC SPRINKLERS IN ACCORDANCE WITH
 NFPA 13, AUTOMATIC SPRINKLER PROTECTION SHALL BE
 PROVIDED FOR THE EXTERIOR SPACES IN ACCORDANCE WITH
 13.3.2.6.
 13.3.2.6.1: UNLESS THE REQUIREMENTS OF 13.3.2.6.2,
 13.3.2.6.3, OR 13.3.2.6.4 ARE MET, SPRINKLERS SHALL BE
 INSTALLED UNDER EXTERIOR PROJECTIONS EXCEEDING 4 FT
 (1.2 M) IN WIDTH. [13:8.15.7.1]
 13.3.2.6.2* SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 WHERE THE EXTERIOR PROJECTIONS ARE CONSTRUCTED WITH
 MATERIALS THAT ARE NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE,
 OR FIRE RETARDANT?
 TREATED WOOD AS DEFINED IN NFPA 703, STANDARD FOR FIRE
 RETARDANT?TREATED WOOD AND FIRE-RETARDANT COATINGS FOR
 BUILDING MATERIALS. [13:8.15.7.2]
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-11-07 Time   Rev Time 0.00
Received By lmarchan Date 2018-11-02 Time 12:54 Sent To  
Notes
2018-11-06 12:54:34RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-29 Cont ID  
Sent By cpuell Date 2018-10-29 Time 14:10 Rev Time 0.00
Received By cpuell Date 2018-09-11 Time 11:19 Sent To  
Notes
2018-09-13 11:19:42C27

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-11-07 Cont ID  
Sent By ccole Date 2018-11-07 Time 13:08 Rev Time 0.00
Received By ccole Date 2018-11-07 Time 13:08 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-10-10 Cont ID  
Sent By ccole Date 2018-10-10 Time 09:06 Rev Time 0.00
Received By ccole Date 2018-10-05 Time 16:42 Sent To  
Notes
2018-10-10 09:13:141ST REVIEW FBC-2017 MECHANICAL
 REVISION #18090360
 MASTER # 18010368.
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET H1-101: ADDITIONAL UINFORMATION SHALL BE
 PROVIDED FOR THE NEW AIR-ROW/F18 FANS. THE NOTES ON THE
 PLAN INDICATE THE FANS ARE TO PAINTED HOWEVER THE
 APPLICATION OF PAINT MAY NOT BE APPROVED BY EITHER THE
 MANUFACTURER OR THE AGENCY THAT PROVIDED THE TESTING,
 LISTING AND LABELING OF THE PRODUCT. PLEASE SUBMIT
 PRODUCT DATA SHEETS FOR THE FANS AND FOR THE PAINT THAT
 WILL BE APPLIED TO THE FANS. THE ENGINEER OF RECORD
 SHALL PROVIDE SHOP DRAWING APPROVAL STAMPS ALL
 SUBMITTALS VERIFYING COMPLIANCE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-10-12 Cont ID  
Sent By gjohnson Date 2018-10-12 Time 07:32 Rev Time 0.00
Received By gjohnson Date 2018-10-12 Time 07:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-10-01 Cont ID  
Sent By llouie Date 2018-10-01 Time   Rev Time  
Received By llouie Date 2018-10-01 Time   Sent To  
Notes
2018-10-01 16:53:56SEPARATE PERMITS REQUIRED FOR:
 1.) SIGNAGE
 2.) BICYCLE RACK
  