| Plan Review Stops For Permit 18090349 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2018-12-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-12-03 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
rgathrig |
Date |
2018-12-03 |
Time |
09:10 |
Sent To |
|
|
| Notes |
| 2018-12-03 09:13:12 | PAGE CORRECTED TO SHOW THE RAMP AS-BUILT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-11-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-11-15 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-11-15 |
Time |
09:01 |
Sent To |
|
|
| Notes |
| 2018-11-15 10:40:34 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. GA-2.8, FBC 107, FBC B CHAPTER 10, AS DISCUSSED, THE | | | 6" CURB IS NOT IN AN AREA WHICH IS TYPICAL AND PRESENTS | | | A TRIP HAZARD. PLEASE SEND A PROPOSED DETAIL VIA EMAIL | | | AS DISCUSSED PRIOR TO RESUBMITTAL. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-11-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-11-02 |
Time |
19:35 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-11-02 |
Time |
18:20 |
Sent To |
|
|
| Notes |
| 2018-11-02 19:35:55 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. SHEET A-2.7, A-2.7D, PARKING SPACES WERE REMOVED | | | FROM THE WEST SIDE AND EAST CENTRAL SECTION OF THE | | | GARAGE. CONFIRM THIS IS CORRECT AND REVISE THE PARKING | | | SUMMARY PAGE, FBC 107. IF THIS IS CORRECT, CLARIFY USE | | | OF THE SPACE. | | | | | | 2. GA-2.7, SOUTH SIDE PARKING SPACES REMOVED, CLARIFY | | | USE OF SPACE. | | | | | | 3. GA-2.8, FBC 107, FBC B CHAPTER 10, PLEASE CONTACT ME | | | TO EXPLAIN THE CURB AND RAMP IT IS NOT CLEAR HOW ACCESS | | | TO THE STAIR IS AFFECTED. IT APPEARS THAT THIS | | | CONDITION OCCURS AT OTHER LOCATIONS. | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2018-10-02 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-10-02 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-10-01 |
Time |
17:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-09-19 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2018-09-19 |
Time |
13:55 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2018-09-19 |
Time |
13:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-12-03 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2018-12-03 |
Time |
09:26 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-11-28 |
Time |
08:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-11-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-11-15 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-11-08 |
Time |
15:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-11-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-11-02 |
Time |
19:38 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-09-18 |
Time |
13:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2018-11-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-11-13 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-11-13 |
Time |
14:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-10-12 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-10-12 |
Time |
08:46 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-10-12 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2018-10-12 09:02:49 | 1ST REVIEW FBC-2014 MECHANICAL | | | REVISON #18090349 | | | MASTER #16020294 | | | 10/1218 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE FIFTH EDITION 2014 | | | FBC M- FLORIDA MECHANICAL CODE FIFTH EDITION 2014 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M3.1A: IT APPEARS THAT AIR IS BEING RETURNED | | | FROM THE TOILET ROOM ON THE 1ST FLOOR BY THE CONFERENCE | | | ROOM WHICH IS PROHIBITED PER SECTION 918.6 FBC M. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2018-12-03 |
|
|
Cont ID |
|
| Sent By |
rgathrig |
Date |
2018-12-03 |
Time |
09:14 |
Rev Time |
0.00 |
| Received By |
rgathrig |
Date |
2018-12-03 |
Time |
09:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2018-11-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-11-15 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-11-15 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2018-11-15 10:40:54 | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | ALL PLAN PAGES ARE OK - NEW SHEETS SUBMITTED NEXT | | | REVIEW NEED VERIFICATION | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2018-11-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-11-02 |
Time |
19:37 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-11-02 |
Time |
19:37 |
Sent To |
|
|
| Notes |
| 2018-11-02 19:38:22 | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | ALL PLAN PAGES ARE OK - NEW SHEETS SUBMITTED NEXT | | | REVIEW NEED VERIFICATION | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-10-10 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2018-10-10 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2018-10-10 |
Time |
16:37 |
Sent To |
|
|
| Notes |
|
|