| 2018-10-10 16:57:20 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE DISCHARGE FROM THE STEAM UNIT SHALL DISCHARGE |
| | THRU AN AIR GAP INTO A WASTE RECEPTOR NOT A FLOOR DRAIN |
| | . FBC PL 802.2 AND THE WASTE RECEPTOR CANNOT BE |
| | INSTALLED IN CONCEALED SPACES. WASTE RECEPTORS SHALL |
| | NOT BE INSTALLED IN PLENUMS, CRAWL SPACES, ATTICS, |
| | INTERSTITIAL SPACES ABOVE CEILINGS AND BELOW FLOORS. |
| | READY ACCESS SHALL BE PROVIDED TO WASTE RECEPTORS. THE |
| | WASTE RECEPTOR SHALL BE INSTALLED IN A CLOSET OR OPEN |
| | AREA PER FBC PL 802.3 |
| | |
| | 2. ON SHT P2-90-14A IT NOTES THAT THE STEAM UNIT IS BY |
| | OTHERS IF THIS IS CORRECT A SEPARATE PERMIT WILL BE |
| | REQUIRED. PLACE NOTE ON PLAN. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |