Plan Review Details - Permit 18090183
| Plan Review Stops For Permit 18090183 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2018-09-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-09-26 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-09-26 |
Time |
11:31 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2018-09-18 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-09-18 |
Time |
06:22 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-09-18 |
Time |
05:56 |
Sent To |
|
|
| Notes |
| 2018-09-18 06:22:46 | APPLICATION SAYS 150AMP ATS AND PANEL. PLAN SHOWS | | | 200AMP ATS AND PANEL. WIRE ON PLAN ONLY RATED FOR | | | 150AMP. APPROVED PROVISIONALLY WITH REDLINED DRAWINGS | | | BY MYSELF FOR 150AMP PANEL AND ATS ONLY. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2018-09-14 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-09-14 |
Time |
20:50 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-09-14 |
Time |
20:50 |
Sent To |
|
|
| Notes |
| 2018-09-14 20:51:00 | 09/14/18 REVIEWED FOR CODE COMPLIANCE (GAS) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM | | | THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND | | | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF | | | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY | | | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-09-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-09-26 |
Time |
13:07 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-09-06 |
Time |
13:27 |
Sent To |
|
|
| Notes |
| 2018-09-07 13:27:28 | ROUTED TO ZONING INBOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-09-11 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2018-09-11 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2018-09-11 |
Time |
10:09 |
Sent To |
B |
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |