Plan Review Details - Permit 18090180
Plan Review Stops For Permit 18090180
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-09-26 Cont ID  
Sent By rmcdouga Date 2018-09-26 Time 18:00 Rev Time 0.00
Received By rmcdouga Date 2018-09-26 Time 17:12 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-10-16 Cont ID  
Sent By fgiaquin Date 2018-10-16 Time 05:54 Rev Time 0.00
Received By fgiaquin Date 2018-10-16 Time 05:34 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-18 Cont ID  
Sent By fgiaquin Date 2018-09-18 Time 06:38 Rev Time 0.00
Received By fgiaquin Date 2018-09-18 Time 06:34 Sent To  
Notes
2018-09-18 06:38:51ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO WIRE SIZES PROVIDED ON PLAN, NO CONDUIT OR WIRING
 SHOWN BEING RAN TO GENERATOR ON PLAN. NO CONDUIT SIZE
 OR WIRE SHOW BEING RAN TO SUB-PANEL ON PLAN. PROVIDE A
 COMPLETE AND ACCURATE ELECTRICAL PLAN FOR REVIEW. FS
 471.003(2)(H); 471.025; WPB FBC 107.2.1, 107.3.5
  
 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220; FBC RE E3602.2
 AS DISCUSSED PREVIOUSLY WITH ONE STOP GENERATOR SHOP
 VIA EMAIL THE "GENERATOR SIZING REPORT" IS NOT A PROPER
 AND FINISHED LOAD CALCULATION. PROVIDE LOAD
 CALCULATION.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2018-09-14 Cont ID  
Sent By lcrespo Date 2018-09-14 Time 21:03 Rev Time 0.00
Received By lcrespo Date 2018-09-14 Time 21:03 Sent To  
Notes
2018-09-14 21:03:5509/14/18 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-16 Cont ID  
Sent By fgiaquin Date 2018-10-16 Time 05:55 Rev Time 0.00
Received By fgiaquin Date 2018-10-03 Time 09:24 Sent To  
Notes
2018-10-05 09:24:38RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-26 Cont ID  
Sent By rmcdouga Date 2018-09-26 Time 18:00 Rev Time 0.00
Received By rmcdouga Date 2018-09-06 Time 13:22 Sent To  
Notes
2018-09-07 13:22:57ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2018-09-11 Cont ID  
Sent By mcruz Date 2018-09-11 Time 15:04 Rev Time 0.00
Received By mcruz Date 2018-09-11 Time 15:03 Sent To B
Notes
***NONE***