Plan Review Details - Permit 18090148
Plan Review Stops For Permit 18090148
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-10-18 Cont ID  
Sent By shill Date 2018-10-18 Time 15:43 Rev Time 0.00
Received By shill Date 2018-10-18 Time 15:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-10-25 Cont ID  
Sent By jpearson Date 2018-10-25 Time 11:14 Rev Time 0.00
Received By jpearson Date 2018-10-25 Time 11:14 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-24 Cont ID  
Sent By jpearson Date 2018-09-24 Time 07:12 Rev Time 0.00
Received By jpearson Date 2018-09-24 Time 07:12 Sent To  
Notes
2018-09-24 07:12:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE SHOW WINDOW OUTLETS PER NEC 210.62.
 2. PROVIDE AIC RATING OF PANAL A. NEC 110.3, 110.9
 3. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-09-14 Cont ID  
Sent By pleduc Date 2018-09-14 Time   Rev Time 0.00
Received By pleduc Date 2018-09-14 Time 11:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-10-25 Time   Rev Time 0.00
Received By lmarchan Date 2018-10-22 Time 15:43 Sent To  
Notes
2018-10-23 15:43:12RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-18 Cont ID  
Sent By shill Date 2018-10-18 Time 15:43 Rev Time 0.00
Received By shill Date 2018-09-06 Time 15:20 Sent To  
Notes
2018-09-07 15:20:23B16

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-10-25 Cont ID  
Sent By ccole Date 2018-10-25 Time 14:49 Rev Time 0.00
Received By ccole Date 2018-10-25 Time 14:41 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-09-25 Cont ID  
Sent By ccole Date 2018-09-25 Time 09:07 Rev Time 0.00
Received By ccole Date 2018-09-25 Time 09:07 Sent To  
Notes
2018-09-25 09:09:471ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18090148
 9/25/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2: PROVIDE THE WIND LOAD DESIGN CRITERIA USED
 TO DETERMINE THE RTU ANCHORAGE TO THE EXISTING CURB-
 SECTION 301.15 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-10-25 Cont ID  
Sent By jesmith Date 2018-10-25 Time 13:42 Rev Time 0.00
Received By jesmith Date 2018-10-25 Time 13:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-10-02 Cont ID  
Sent By jesmith Date 2018-10-02 Time 12:33 Rev Time 0.00
Received By jesmith Date 2018-10-02 Time 12:33 Sent To  
Notes
2018-10-02 12:33:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. RE: SUBMITTED LETTER FROM CLUB PILATES REQUESTING
 APPROVAL FOR ONE (1) SINGLE UNISEX BATHROOM; MEN'S AND
 WOMEN'S SEPERATE FACILITIES ARE REQUIRED BASED UPON FBC
 PLUMBING 403.1 AND SHALL COMPLY WITH FBC ACC 604 AND
 606
 A. THE TENANT'S LETTER STATING THE OCCUPANCY WOULD BE
 LESS THAN 15 DOES NOT CHANGE THE FACT THAT THE NUMBER
 OF OCCUPANTS (DEEMED 18) SHALL BE DETERMINED BY THE
 FLORIDA BUILDING CODE, BUILDING PER FBC PLUMBING 403.1,
 TABLE 403.1
 B. THE ONLY EXCEPTION FOR APPROVAL FOR A REDUCED
 OCCUPANCY LOAD IS NOTED IN FBC BUILDING 1004.1.2 AND
 NEEDS TO BE ADDRESSED TO THE BUILDING OFFICIAL FOR
 APPROVAL.
 2. A SERVICE SINK IS REQUIRED PER PER FBC PLUMBING
 403.1, TABLE 403.1
 A. THE TENANT'S LETTER STATING THE OCCUPANCY WOULD BE
 LESS THAN 15 DOES NOT CHANGE THE FACT THAT THE NUMBER
 OF OCCUPANTS (DEEMED 18) SHALL BE DETERMINED BY THE
 FLORIDA BUILDING CODE, BUILDING PER FBC PLUMBING 403.1,
 TABLE 403.1
 B. THE ONLY EXCEPTION FOR APPROVAL FOR A REDUCED
 OCCUPANCY LOAD IS NOTED IN FBC BUILDING 1004.1.2 AND
 NEEDS TO BE ADDRESSED TO THE BUILDING OFFICIAL FOR
 APPROVAL.
 3. RE: PLAN SHEET P-2; WATER ISOMETRIC. SHOW BRANCH TO
 TRAP PRIMER NOTED ON "FLOOR DRAIN & TRAP PRIMER"
 DETAIL. WPB FBC 107.2.1
 4. RE: PLAN SHEET P-2; WATER ISOMETRIC. PROVIDE
 INFORMATION FOR BACKFLOW PREVENTOR SHOWN ON SUPPLY TO
 WATER FILTER. INCLUDE TYPE, MODEL NUMBER AND ASSE
 STANDARD FOR COMPLIANCE. IF THERE IS A RELIEF OPENING
 ON THE DEVICE THEN PROVIDE DETAILS FOR DISCHARGE
 PIPING. WPB FBC 107.2.1
 5. RE: PLAN SHEET P-2; "HOT WATER LIMITING DEVICE"
 DETAIL. WHERE DOES HOT WATER CONTINUE TO AFTER
 SERVICING THE LAVATORY. PLEASE CLARIFY. WPB FBC 107.2.1
 6. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE DETAILED, QUANTITY ESTIMATES, AND/OR BONA
 FIDE SIGNED CONTRACTS WITH SCOPE AND VALUE OF WORK, TO
 INCLUDE ALL MATERIALS AND LABOR. THIS IS FOR TOTAL
 PROJECT, NOT JUST PLUMBING. WPB FBC 109.3
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop Z ZONING
Rev No 1 Status P Date 2018-10-15 Cont ID  
Sent By LL Date 2018-10-15 Time   Rev Time 0.00
Received By llouie Date 2018-10-15 Time   Sent To  
Notes
2018-10-15 13:53:16ZONED GC; EXCERCISE STUDIOS AND HEALTH CLUBS PERMITTED
 IN GC.