Plan Review Details - Permit 18090098
Plan Review Stops For Permit 18090098
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-10-09 Cont ID  
Sent By jleahy Date 2018-10-09 Time 08:02 Rev Time 0.00
Received By jleahy Date 2018-10-09 Time 08:02 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-09-26 Cont ID  
Sent By jleahy Date 2018-09-24 Time 09:27 Rev Time 0.00
Received By jleahy Date 2018-09-24 Time 09:27 Sent To  
Notes
2018-09-24 09:29:46FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED A LOAD CALCULATION FOR THE SERVICE.
  
 NEED TO SHOW BRANCH CIRCUIT SIZE AND OCP SIZE FOR
 CIRCUITS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-10-11 Time   Rev Time 0.00
Received By lmarchan Date 2018-10-03 Time 09:51 Sent To  
Notes
2018-10-05 09:51:37RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-24 Cont ID  
Sent By jleahy Date 2018-09-24 Time 09:30 Rev Time 0.00
Received By jleahy Date 2018-09-05 Time 13:11 Sent To  
Notes
2018-09-06 13:11:58ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-10-11 Cont ID  
Sent By ccole Date 2018-10-11 Time 10:12 Rev Time 0.00
Received By ccole Date 2018-10-11 Time 10:12 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-09-21 Cont ID  
Sent By ccole Date 2018-09-21 Time 14:52 Rev Time 0.00
Received By ccole Date 2018-09-21 Time 14:52 Sent To E
Notes
2018-09-21 15:08:141ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18090098
 9/21/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW MINI-SPLIT SYSTEM IN ACCORDANCE WITH SECTION
 C403.2.1 FBC EC. THE CALCULATIONS SHALL INDICATE THE
 HEAT LOAD OF THE SPACE HAS INCREASED BEYOND THE
 CAPACITY OF THE EXISTING SYSTEM.
  
 2) REMOVE THE AC CHANGEOUT FORMS FROM THE PERMIT FILE.
 THE PROPOSED PROJECT IS A NEW AC SYSTEM INSTALLATATION,
 NOT A CHANGEOUT- SECTION 107.2.1 WPB
  
 3) PROVIDE A PLAN THAT SHOWS THE LOCATIONS OF THE AIR
 HANDLER AND CONDENSER, AND REFRIGERANT AND CONDENSATE
 PIPING RUNS- SECTION 107.2.1 WPB.
  
 4) THE CONDENSER MOUNTING DETAIL NOTES INDICATE 160 MPH
 WIND SPEED, HOWEVER THE WIND SPEED SHALL BE 170 MPH PER
 SECTION 1609 FBC B.
  
 5) THE ENGINEER WHO PLACED HIS SIGNATURE AND SEAL ON
 THE EXTERIOR CONDENSER MOUNTING DETAILS SHALL ALSO
 PROVIDE HIS TITLE BLOCK ON THE PLANS- SECTION
 61G15-23.002 FAC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved