Plan Review Details - Permit 18090049
Plan Review Stops For Permit 18090049
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-11-16 Cont ID  
Sent By dbattles Date 2018-11-16 Time 13:05 Rev Time 0.00
Received By dbattles Date 2018-11-16 Time 13:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-04 Cont ID  
Sent By rmcdouga Date 2018-10-04 Time 08:43 Rev Time 0.00
Received By rmcdouga Date 2018-10-03 Time 18:28 Sent To I
Notes
2018-10-03 19:01:38PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE WIND SPEED AND EXPOSURE CATEGORY AND
 PROVIDE THE DESIGN PRESSURES FOR THE WINDOWS AND
 SLIDING GLASS DOOR. FBC 1603.1.4
  
 2) INDICATE THE WINDOW SIZE AND PRESSURES BY CIRCLING
 THE APPROPRIATE ONES IN THE CHARTS ON SHEET 2 OF THE
 PRODUCT APPROVAL (NOA NO. 17-1018.08). FBC 107.2.1
  
 3) THE PHOTO THAT WAS SUBMITTED SHOWS TWO SINGLE HUNG
 WINDOWS JOINED TOGETHER WITH A MULLION. SUBMIT TWO SETS
 OF PRODUCT APPROVALS FOR THE STRUCTURAL MULLION. FAC
 RULE 612G20
  
 4) INDICATE THE DESIGN PRESSURES FOR THE SLIDING GLASS
 DOOR PANELS BY CIRCLING THE APPROPRIATE ITEMS ON THE
 CHART ON SHEET 13 AND THE DESIGN LOAD CAPACITY OF THE
 ANCHORS THAT WILL BE USED FROM THE CHART ON SHEET 15 OF
 THE PRODUCT APPROVAL (NOA NO. 17-1011.18).
  
 5) ALL FRAMING IS REQUIRED TO BE OF NONCOMBUSTIBLE
 MATERIALS. SPECIFY THE FRAMING MATERIAL TO BE USED ON
 THE PLANS. FBC 602.2
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-10-15 Cont ID  
Sent By jpearson Date 2018-10-15 Time 11:57 Rev Time 0.00
Received By jpearson Date 2018-10-15 Time 11:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-21 Cont ID  
Sent By jpearson Date 2018-09-21 Time 10:34 Rev Time 0.00
Received By jpearson Date 2018-09-21 Time 09:01 Sent To  
Notes
2018-09-21 10:33:54CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. THIS PERSON MUST BE A LICENSED DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER.
 PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
 2. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12
 3. RECEPTACLES INSTALLED TO SERVE THE COUNTER TOP IN
 KITCHEN REQUIRE GFCI PROTECTION. PROVIDE CORRECTION.
 NEC 210.8
 4. THE RECEPTACLE OUTLET SHOWN FOR THE PENINSULA IS NOT
 CODE COMPLIANT. THE COUNTER TOP IS NOT PERMITTED TO
 EXTEND MORE THAN 6 INCHES FROM ITS BASE FOR A
 RECEPTACLE OUTLET TO BE APPROVED IN THAT LOCATION.
 PROVIDE CORRECTION. NEC 210.52(C)(5)
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D)
 6. PROVIDE PANEL SCHEDULE FOR PANEL TO BE CHANGED
 INDICATING ANY NEW OR ALTERED CIRCUITS, THE WIRE AND
 BREAKER SIZE FOR THESE CIRCUITS, AND AFCI OR GFCI
 PROTECTION WHERE APPLICABLE TO COMPLY WITH CODE. NEC
 210.8, 210.12, 210.19, 210.20, 215.5, 408.4
 7. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12
 8. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D)
 9. IT APEARS THAT A HEAT LAMP IS BEING ADDED. IF THIS
 IS THE CASE, PROVIDE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30
 10. RENOVATED PLAN SHOWS RECEPTACLE OUTLETS THAT ARE
 EXISTING BEING REMOVED. RECEPTACLES SHALL BE INSTALLED
 SO THAT NO POINT MEASURED HORIZONTALLY ALONG THE FLOOR
 LINE OF ANY WALL SPACE IS MORE THAN 6 FEET FROM A
 RECEPTACLE OUTLET. THE WALL SPACING REQUIREMENTS FOR
 KITCHEN COUNTER SPACE STATE THAT RECEPTACLE OUTLETS
 SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE
 IS MORE THAN 24 INCHES MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE. THE PLAN PROVIDED DOES
 NOT MEET THIS CODE IN SOME AREAS. PROVIDE CORRECTION.
 NEC 210.52(C)(1)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-09-11 Cont ID  
Sent By pleduc Date 2018-09-11 Time   Rev Time 0.00
Received By pleduc Date 2018-09-11 Time 15:34 Sent To  
Notes
2018-09-11 15:36:19THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS, IF EXISTING, SHALL BE DONE UNDER
 SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE SAFETY
 CONTRACTORS.
  
 3) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-16 Cont ID  
Sent By dbattles Date 2018-11-16 Time 13:05 Rev Time 0.00
Received By dbattles Date 2018-10-05 Time 14:26 Sent To  
Notes
2018-10-09 14:26:49B06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-04 Cont ID  
Sent By rmcdouga Date 2018-10-04 Time 08:44 Rev Time 0.00
Received By rmcdouga Date 2018-09-04 Time 15:38 Sent To  
Notes
2018-09-05 15:38:46B01

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-10-03 Cont ID  
Sent By rmcdouga Date 2018-10-03 Time 18:47 Rev Time 0.00
Received By rmcdouga Date 2018-10-03 Time 18:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-10-24 Cont ID  
Sent By ccole Date 2018-10-23 Time 07:09 Rev Time 0.00
Received By ccole Date 2018-10-23 Time 12:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-09-20 Cont ID  
Sent By ccole Date 2018-09-20 Time 16:56 Rev Time 0.00
Received By ccole Date 2018-09-20 Time 16:54 Sent To  
Notes
2018-09-20 17:03:321ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18090049
 9/20/2018
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT AN AC CHANGE OUT FORM FOR THE REPLACED AC
 SYSTEM. THE FORM CAN BE ACCESSED ON THE CITY OF WEST
 PALM BEACH WEBSITE, OR AT THE FRONT COUNTER OF THE
 BUILDING DEPARTMENT.
  
 2) PLEASE INDICATE THE SIZE OF THE DUCT IN THE SOFFIT
 AND SHOW ALL OTHER DUCT ALTERATIONS IN THE CONDO.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-10-02 Cont ID  
Sent By gjohnson Date 2018-10-02 Time 09:59 Rev Time 0.00
Received By gjohnson Date 2018-10-01 Time 15:20 Sent To  
Notes
***NONE***