Plan Review Details - Permit 18090047
Plan Review Stops For Permit 18090047
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-11-07 Cont ID  
Sent By dbattles Date 2018-11-07 Time 14:58 Rev Time 0.00
Received By dbattles Date 2018-11-07 Time 14:21 Sent To  
Notes
2018-11-07 14:59:00****CORRECTIONS****
 W.P.B. PERMIT: 18090047
 REVIEWED: NOVEMBER 7, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVALS FOR
 WINDOW AND DOORS, OR INDICATE THAT YOU WOULD LIKE THEM
 DEFERED.
  
 2. [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVALS FOR
 FLAT ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM
 DEFERED.
  
 3. [FBC ENERGY R401.2]MEET REQUIREMENTS IN R401.2
 RESIDENTIAL ENERGY CODE. CHOOSE METHOD IN R401.2 AND
 SUPPLY DOCUMENTATION.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-10-11 Cont ID  
Sent By jpearson Date 2018-10-11 Time 13:51 Rev Time 0.00
Received By jpearson Date 2018-10-11 Time 13:51 Sent To  
Notes
2018-10-11 13:51:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.12; FBC RE E3902.16
 2. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 3. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR 50 AMP SUB-PANEL. NEC
 225.31, 225.32
 4. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A
 BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3
 5. CONDUIT/FEEDER FROM MAIN PANEL TO SUB-PANEL MUST
 INCLUDE AN EQUIPMENT GROUNDING CONDUCTOR. PROVIDE
 CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1
 6. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
 7. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER CODE. NEC
 210.63; FBC RE E3901.12
 8. RISER DAIGRAM STATES TO "INSTALL NEW DOUBLE LUG" IN
 THE 200 AMP MAIN PANEL. WHAT IS THE PURPOSE OF THIS?
 MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN
 A BUILDING OR OTHER STRUCTURE FROM THE SERVICE-ENTRANCE
 CONDUCTORS. PROVIDE CLARIFICATION AND/OR CORRECTION.
 NEC 230.70; FBC RE E3601.6
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-26 Cont ID  
Sent By fgiaquin Date 2018-09-26 Time 09:23 Rev Time 0.00
Received By fgiaquin Date 2018-09-26 Time 09:00 Sent To  
Notes
2018-09-26 09:23:34ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO ELECTRICAL PLAN SUBMITTED FOR REVIEW. PROVIDE
 ELECTRICAL PLAN FOR REVIEW, SIGNED AND SEALED BY A
 LICENSED DESIGN PROFESSIONAL OR THE ELECTRICAL
 CONTRACTOR QUALIFIER. FS 471.003(2)(H); 471.025; WPB
 FBC 107.2.1, 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2018-11-20 Cont ID  
Sent By fmittner Date 2018-11-20 Time 08:55 Rev Time 0.00
Received By fmittner Date 2018-11-20 Time 08:55 Sent To  
Notes
2018-11-20 08:57:20PROPERTY LOCATED WITHIN HISTORIC DISTRICT. DEMO/NEW
 CONSTRUCTION REQUIRES HPB APPROVAL. QUESTIONS, CONTACT
 FRIEDERIKE MITTNER, CITY HISTORIC PRESERVATION PLANNER
 AT (561) 822-1457 OR [email protected].

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-12-08 Cont ID  
Sent By shill Date 2018-12-08 Time 09:04 Rev Time 0.00
Received By shill Date 2018-09-26 Time 18:18 Sent To  
Notes
2018-09-27 13:35:54R08
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-27 Cont ID  
Sent By shill Date 2018-09-27 Time 13:35 Rev Time 0.00
Received By shill Date 2018-09-06 Time 13:00 Sent To  
Notes
2018-09-11 13:00:33R08

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2018-09-06 Cont ID  
Sent By shill Date 2018-09-06 Time 09:14 Rev Time 0.00
Received By shill Date 2018-09-06 Time 09:14 Sent To  
Notes
2018-09-06 09:14:30****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-11-07 Cont ID  
Sent By dbattles Date 2018-11-07 Time 14:59 Rev Time 0.00
Received By dbattles Date 2018-11-07 Time 14:59 Sent To  
Notes
2018-11-07 14:59:41[FBC AMENDED 109]PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF
  
 REVIEWED: NOVEMBER 7, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-10-26 Cont ID  
Sent By cmontell Date 2018-10-26 Time 09:17 Rev Time 0.00
Received By cmontell Date 2018-10-26 Time 09:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-10-23 Cont ID  
Sent By jesmith Date 2018-10-23 Time 15:21 Rev Time 0.00
Received By jesmith Date 2018-10-23 Time 15:20 Sent To  
Notes
2018-10-23 15:20:551ST REVIEW:
 PLUMBING COMMENTS: APPROVED
 PROVISO
 1. PROVIDE ANTI-SCALD VALVE AT SHOWER. FBC RES P2708.4
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop Z ZONING
Rev No 1 Status F Date 2018-11-20 Cont ID  
Sent By fmittner Date 2018-11-20 Time 08:57 Rev Time 0.00
Received By fmittner Date 2018-11-20 Time 08:57 Sent To  
Notes
2018-11-20 08:57:45NEED LOT COVERAGE/FAR NUMBERS