Plan Review Details - Permit 18081585
Plan Review Stops For Permit 18081585
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2019-04-03 Cont ID  
Sent By cthroop Date 2019-04-03 Time 16:36 Rev Time 0.00
Received By cthroop Date 2019-04-03 Time 16:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-02-26 Cont ID  
Sent By shill Date 2019-02-26 Time 07:23 Rev Time 0.00
Received By shill Date 2019-02-26 Time 07:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-11-08 Cont ID  
Sent By cthroop Date 2018-11-08 Time 08:29 Rev Time 0.00
Received By cthroop Date 2018-11-08 Time 08:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-11-02 Cont ID  
Sent By shill Date 2018-11-02 Time 21:41 Rev Time 0.00
Received By shill Date 2018-11-02 Time 21:41 Sent To  
Notes
2018-11-02 21:43:05****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B 1609, ON THE PRODUCT APPROVALS, INDICATE WHICH
 OPTION IS PROPOSED TO SHOW COMPLIANCE WITH DESIGN
 PRESSURES SPECIFIED.
  
 2ND REVIEW, RESPONSE LETTER STATES THAT THIS WILL BE
 PROVIDED BY CONTRACTOR, NOT PROVIDED.
  
 2. OK
  
 3. FOR THE FLOORING UNDERLAYMENT, PROVIDE THE FOLLOWING
 TEST REPORTS. IT IS RECOMMENDED THAT THIS BE RESOLVED
 VIA EMAIL PRIOR TO RESUBMITTAL. EMAIL THE NAME OF THE
 UNDERLAYMENT PROPOSED TO [email protected] WITH THE PERMIT
 NUMBER IN THE SUBJECT LINE. IF THE MANUFACTURER HAS
 ALREADY PROVIDED THE REQUIRED TEST REPORTS DIRECTLY TO
 US, TEST REPORTS DO NOT NEED TO BE SUBMITTED WHEN
 RESUBMITTING.
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 2ND REVIEW, A LINK TO NAC SUPERSAM 125 WAS PROVIDED VIA
 EMAIL. NO TEST REPORTS WERE PROVIDED. DO NOT SEND
 LINKS; ONLY SEND PDFS IF YOU WOULD LIKE A COURTESY
 REVIEW VIA EMAIL. OUR IT DEPARTMENT DISCOURAGES OPENING
 OF LINKS; THIS WILL NOT BE DONE IN THE FUTURE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-25 Cont ID  
Sent By shill Date 2018-09-25 Time 17:48 Rev Time 0.00
Received By shill Date 2018-09-25 Time 17:48 Sent To  
Notes
2018-09-25 17:52:25****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B 1609, ON THE PRODUCT APPROVALS, INDICATE WHICH
 OPTION IS PROPOSED TO SHOW COMPLIANCE WITH DESIGN
 PRESSURES SPECIFIED.
  
 2. FBC 107, PRODUCT APPROVALS ARE TO BE REVIEWED BY
 DESIGNER OF RECORD (SHOP DRAWING REVIEW OR LETTER OR
 INCORPORATE INTO PLAN).
  
 2. PLEASE ADVISE, WHAT TYPE OF FLOORING IS PROPOSED?
 SEE ITEM 4.
  
 3. FOR THE FLOORING UNDERLAYMENT, PROVIDE THE FOLLOWING
 TEST REPORTS. IT IS RECOMMENDED THAT THIS BE RESOLVED
 VIA EMAIL PRIOR TO RESUBMITTAL. EMAIL THE NAME OF THE
 UNDERLAYMENT PROPOSED TO [email protected] WITH THE PERMIT
 NUMBER IN THE SUBJECT LINE. IF THE MANUFACTURER HAS
 ALREADY PROVIDED THE REQUIRED TEST REPORTS DIRECTLY TO
 US, TEST REPORTS DO NOT NEED TO BE SUBMITTED WHEN
 RESUBMITTING.
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-10-19 Cont ID  
Sent By jpearson Date 2018-10-19 Time 07:29 Rev Time 0.00
Received By jpearson Date 2018-10-19 Time 06:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-17 Cont ID  
Sent By jpearson Date 2018-09-17 Time 16:03 Rev Time 0.00
Received By jpearson Date 2018-09-17 Time 12:05 Sent To  
Notes
2018-09-17 16:03:22CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NOTE 9 AND PANEL SCHEDULES SHOWN ARE NOT CODE
 COMPLIANT IN REFERENCE TO AFCI PROTECTION. ALL BRANCH
 CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12
 2. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D)
 3. POWER PLAN SHOWS 3 PANELS, PANEL A, PANEL B, AND
 PANEL L. RISER DIAGRAM ONLY SHOWS 2 PANELS, AND ONLY 2
 PANEL SCHEDULES ARE PROVIDED. PROVIDE CLARIFICAITON
 AND/OR CORRECTION. NEC 215.5; WPB FBC 107.2.1
 4. LIGHTING IN SHOWER/TUB AREAS IS SHOWN AS STANDARD
 RECESS LIGHTS. LIGHTING IN BATHTUB OR SHOWER AREAS
 SHALL BE SUITABLE FOR DAMP LOCATIONS. NO PARTS OF
 CORD-CONNECTED LUMINAIRES, CHAIN-, CABLE-, OR
 CORD-SUSPENDED LUMINAIRES, LIGHTING TRACK, PENDANTS, OR
 CEILING-SUSPENDED (PADDLE) FANS SHALL BE LOCATED WITHIN
 A ZONE MEASURED 3 FEET HORIZONTALLY AND 8 FEET
 VERTICALLY FROM THE TOP OF THE BATHTUB RIM OR SHOWER
 STALL THRESHOLD. PROVIDE CORRECTION. NEC 410.10(D)
 5. LIGHTING IN CLOSETS IS SHOWN AS STANDARD RECESS
 LIGHTS. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS
 AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE
 PERMITTED IN CLOTHES CLOSETS. PROVIDE CORRECTION. NEC
 410.16
 6. IT APPEARS THAT A GFCI RECEPTACLE IS SHOWN WITHIN
 THE TUB/SHOWER AREA OF THE MASTER BATH. RECEPTACLES
 SHALL NOT BE INSTALLED WITHIN A TUB OR SHOWER SPACE.
 PROVIDE CLARIFICATION AND/OR CORRECTION. NEC 406.9(C)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-10-17 Cont ID  
Sent By scaldero Date 2018-10-17 Time 10:16 Rev Time 0.00
Received By scaldero Date 2018-10-17 Time 10:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-09-05 Cont ID  
Sent By scaldero Date 2018-09-05 Time 11:51 Rev Time 0.00
Received By scaldero Date 2018-09-05 Time 11:46 Sent To  
Notes
2018-09-05 11:51:15PERMIT # 18081585
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 1) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 2) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-04-03 Cont ID  
Sent By cthroop Date 2019-04-03 Time 16:36 Rev Time 0.00
Received By cthroop Date 2019-03-25 Time 15:51 Sent To  
Notes
2019-03-26 15:51:45RESUB ROUTED TO GJOHNSON

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-02-26 Cont ID  
Sent By shill Date 2019-02-26 Time 07:23 Rev Time 0.00
Received By shill Date 2019-02-12 Time 15:48 Sent To  
Notes
2019-02-13 15:48:21B26

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-06 Cont ID  
Sent By shill Date 2018-11-06 Time 12:18 Rev Time 0.00
Received By shill Date 2018-10-11 Time 15:53 Sent To  
Notes
2018-10-12 15:54:01B26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-25 Cont ID  
Sent By shill Date 2018-09-25 Time 17:52 Rev Time 0.00
Received By shill Date 2018-08-31 Time 15:51 Sent To  
Notes
2018-09-04 15:52:02B34

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-02-15 Cont ID  
Sent By ccole Date 2019-02-15 Time 14:35 Rev Time 0.00
Received By ccole Date 2019-02-15 Time 12:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-10-24 Cont ID  
Sent By ccole Date 2018-10-24 Time 11:59 Rev Time 0.00
Received By ccole Date 2018-10-24 Time 10:51 Sent To  
Notes
2018-10-24 12:42:042ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18081585
 10/24/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AC CALCULATIONS: THE CALCULATIONS DO NOT SHOW ANY
 INTERNAL HEAT GAIN LOADS- SEE PAGE 1 AND REFER TO
 SECTION C403.2.1 FBC M.
  
 2) SHEET M201: A DUCT SMOKE DETECTOR IS REQUIRED IN THE
 SUPPLY SYSTEM OF WSHP 1-01 PER SECTION 606.2.1 FBC M.
 PLEASE NOTE THAT THE AIR DISTRIBUTION PLAN INDICATES
 SUPPLY AIR OVER 2000 CFMS, AND IT IS THE POLICY OF THE
 BUILDING DEPARTMENT TO REQUIRE DUCT SMOKE DETECTORS ON
 5-TON SYSTEMS UNLESS MANUFACTURER'S DATA VERIFIES THE
 SYSTEMS CANNOT PRODUCE OVER 2000 CFMS.
  
 3) M201: IT APPEARS THAT AN ADDITIONAL EXHAUST FAN WILL
 BE REQUIRED IN THE BATHUB/SHOWER ROOM OF BATHROOM #3
 (BEDROOM #3 ON THE PLAN) IF THE WALLS OF THE ROOM ARE
 NOT OPEN AT THE TOP.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-09-18 Cont ID  
Sent By ccole Date 2018-09-18 Time 08:43 Rev Time 0.00
Received By ccole Date 2018-09-18 Time 08:33 Sent To  
Notes
2018-09-18 08:53:301ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18081585
 9/18/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE CORRECT THE ADDRESS ON THE PERMIT
 APPLICATION, THE PLANS AND THE CALCULATIONS. THE
 CORRECT ADDRESS IS 529 S. FLAGLER DRIVE.
  
 2) REFER TO SECTION R101.5.1.2 FBC EC. THE PROJECT
 SHALL BE IN COMPLIANCE WITH THE COMMERCIAL PROVISIONS
 OF THE FBC EC. REFER TO SECTIONS C101.5 AND C403.2.1
 AND SUBMIT REVISED ENERGY AND AC CALCULATIONS.
  
 3) SHEET M201: UNDERSIZED BEDROOM RETURN SYSTEMS: A)
 MASTER BEDROOM & BERDOOM #1- RETURN DUCTS SHALL BE
 SIZED 1.5 TIMES THE CROSS SECTIONAL AREA OF THE SUPPLY
 DUCT ENTERING THE ROOM. B) BEDROOMS 2 & 3: THE TRANSFER
 GRILLS SHALL BE SIZED AT 50 SQUARE INCHES PER 100 CFMS
 OF SUPPLY AIR- SECTION 601.6 FBC M.
  
 4) M201: THE PLAN SHOWS DRYER EXHAUST AND TOILET
 EXHAUST DUCTS CONNECTING INTO THE SAME SHAFT, HOWEVER A
 COMMON MULTI-STORY DRYER EXHAUST SYSTEM SHALL SERVE
 ONLY CLOTHES DRYERS. REFER TO SECTION 504.10 ITEMS 1-12
 AND PROVIDE ADDITIONAL DETAILS AND NOTES TO CLARIFY.
  
 5) M201: THE PLAN SHOWS KITCHEN HOOD EXHAUST AND TOILET
 EXHAUST DUCTS CONNECTING INTO THE SAME SHAFT, HOWEVER A
 COMMON MULTI-STORY HOOD EXHAUST SYSTEM SHALL SERVE ONLY
 KITCHEN HOOD EXHAUST. REFER TO SECTION 505.3 ITEMS 1-12
 AND PROVIDE ADDITIONAL DETAILS AND NOTES TO CLARIFY.
  
 6) M201: VERIFY THAT ALL MATERIALS IN AC CLOSETS USED
 AS PLENUM RETURNS ARE NON-COMBUSTIBLE OR ARE LISTED AND
 LABELED AS HAVING A FLAME SPREAD OF NOT MORE THAN 25
 AND A SMOKE-DEVELOPED INDEX OF NOT MORE THN 50- SECTION
 602.2.1 FBC M.
  
 7) PLEASE SUBMIT PRODUCT DATA SHEETS FOR ALL COOKING
 APPLIANCES, KITCHEN HOOD, AND DRYER. ALL SUBMITTALS
 SHALL BE APPROVED BY THE EOR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
 HTTPS://WWW.SURVEYMONKEY.COM/R/WESTPALMBEACHCONSTRUCTIO
 NSERVICES
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-04-02 Cont ID  
Sent By gjohnson Date 2019-04-02 Time 08:47 Rev Time 0.00
Received By gjohnson Date 2019-04-02 Time 08:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-02-20 Cont ID  
Sent By gjohnson Date 2019-02-20 Time 09:30 Rev Time 0.00
Received By gjohnson Date 2019-02-20 Time 09:30 Sent To  
Notes
2019-02-20 09:30:313RD REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED 2ND
 REQUEST
  
 3. DETAILS ON SHT. P101 THAT ARE NOT UNDER THE SCOPE OF
 THIS PERMIT PLEASE REMOVE IF NOT BEING USED. IF WORK IS
 BEING DONE ON THE ROOF DRAINS OR CONDENSATE PLEASE
 PROVIDE PIPING DETAILS AND FLOOR PLANS SHOWING NEW WORK
 . PER WPB AMEND TO FBC 107..2.1
  
 4. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION
 GUIDE FOR THE TUB DRAINS INSTALLED IN THE SHOWER STALLS
 SHOW DETAIL OF HOW THE SHOWER PAN WILL BE SEALED AROUND
 TUB DRAIN, THE MANUFACTURE SPECIFICATIONS SHALL ALSO
 SHOW APPROVAL OF USE IN THIS APPLICATION. PER WPB AMEND
 TO FBC 107..2.1
  
 NEW COMMENTS:
  
 1. SHT A-3 DETAIL #10 THE WATER PROOF MEMBRANE SHALL
 PITCH TO DRAIN. PER FBC PL 417.5.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-11-05 Cont ID  
Sent By gjohnson Date 2018-11-05 Time 16:55 Rev Time 0.00
Received By gjohnson Date 2018-11-05 Time 16:55 Sent To  
Notes
2018-11-05 17:18:193RD REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED 2ND
 REQUEST
  
 3. DETAILS ON SHT. P101 THAT ARE NOT UNDER THE SCOPE OF
 THIS PERMIT PLEASE REMOVE IF NOT BEING USED. IF WORK IS
 BEING DONE ON THE ROOF DRAINS OR CONDENSATE PLEASE
 PROVIDE PIPING DETAILS AND FLOOR PLANS SHOWING NEW WORK
 . PER WPB AMEND TO FBC 107..2.1
  
 4. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION
 GUIDE FOR THE TUB DRAINS INSTALLED IN THE SHOWER STALLS
 SHOW DETAIL OF HOW THE SHOWER PAN WILL BE SEALED AROUND
 TUB DRAIN, THE MANUFACTURE SPECIFICATIONS SHALL ALSO
 SHOW APPROVAL OF USE IN THIS APPLICATION. PER WPB AMEND
 TO FBC 107..2.1
  
 NEW COMMENTS:
  
 1. SHT A-3 DETAIL #10 THE WATER PROOF MEMBRANE SHALL
 PITCH TO DRAIN. PER FBC PL 417.5.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-09-25 Cont ID  
Sent By shill Date 2018-09-25 Time 17:22 Rev Time 0.00
Received By jesmith Date 2018-09-25 Time 17:22 Sent To  
Notes
2018-09-25 17:44:29FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW:
 PERMIT 18081585
 PLUMBING COMMENTS: DENIED
  
 1. PROVIDE PIPING MATERIALS TYPE & FIRE RATED
 ASSEMBLIES FOR RELOCATED DRAIN FLOORPENETRATIONS WPB
 FBC 107.2.1.
  
 2. PROVIDE DETAIL FOR MASTER BATH & SHOWER MEMBRANE AS
 APPLIED TO TEMPERED GLASS WALL, SEAT & THRESHOLD, FBC
 107.2.1.
  
 3. SHOW CURB DETAIL ON TYPICAL SHOWER PAN DETAIL 11
 PLAN A3, FBC 107.2.1.
  
 4. LAUNDRY - ADD NOTE AT STACKED WASHER/DRYER
 "ACCESSIBLE SHUTOFF VALVES REQUIRED" FBC P 606.3.
  
 5. SHEET P101 GENERAL PIPING NOTES MAKE REFERENCE TO
 GAS PIPING BUT NONE IS SHOWN. IF NO GAS PIPING IS
 PROPOSED, REMOVE THE NOTE. IF THERE IS GAS PIPING, THEN
 A SEPARATE WILL BE REQUIRED, FBC 107.2.1.
  
 6. KITCHEN SINK IS RLEOCATED REQUIRING LOCATION OF
 STACK. PROVIDE A RISER DIAGRAM, FBC 107.3.5.1.3(13)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL: [email protected]
 561-805-6715
  