| 2018-10-10 13:22:16 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | HOWEVER, |
| | |
| | 1) THIS REVIEW MAY BE APPROVED FOR THE PROPOSED DEMO |
| | WORK ONLY. |
| | |
| | SHEET 001 - THERE ARE INDICATIONS UNDER THE SCOPE OF |
| | WORK AND HISTORICAL STATUS THAT SELECTIVE DEMOLITION |
| | SHALL TAKE PLACE PRIOR TO A TENANT REUSE SUBMITTAL AT A |
| | LATER DATE. |
| | |
| | THIS APPROVAL WOULD NOT INCLUDE THE PLANS SHEETS FOR |
| | THE PROPOSED TENANT SPACES. |
| | |
| | SHOULD THE INTENT BE FOR ONLY DEMO WORK PLEASE PROVIDE |
| | A WRITTEN NARRATIVE TO DO ONLY DEMO WORK AND TO ADDRESS |
| | THE COMMENTS BELOW IN REVISONS PRIOR TO RECONSTRUCTION. |
| | |
| | |
| | ******************************************************* |
| | ************************************************ |
| | |
| | |
| | |
| | |
| | THE FOLLOWING ARE COMMENTS RELATED TO THE PROPOSED |
| | TENANT SPACES IN REVIEW OF THE FLORIDA FIRE PREVENTION |
| | CODE, NFPA 1 AND 101, 2015 ED. |
| | |
| | |
| | 1) SHEET 001 & A SHEETS - THERE APPEARS TO BE MUTIPLE |
| | OCCUPANCIES PROPOSED FOR THE TENANT SPACES. WILL THESE |
| | OCCUPANCIES BE MIXED OR SEPARATED. |
| | |
| | PER NFPA 101, CHPATER 6, OCCUPANCY CLASSIFICATION. |
| | |
| | 6.1 CLASSIFICATION OF OCCUPANCY. |
| | 6.1.1 GENERAL. |
| | 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A |
| | BUILDING OR |
| | STRUCTURE, OR PORTION OF A BUILDING OR STRUCTURE, SHALL |
| | BE CLASSIFIED IN |
| | ACCORDANCE WITH 6.1.2 THROUGH 6.1.13. OCCUPANCY |
| | CLASSIFICATION SHALL BE |
| | SUBJECT TO THE RULING OF THE AUTHORITY HAVING |
| | JURISDICTION WHERE THERE IS A |
| | QUESTION OF PROPER CLASSIFICATION IN ANY INDIVIDUAL |
| | CASE. |
| | |
| | 6.1.14.2 DEFINITIONS. |
| | 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE |
| | IN WHICH TWO |
| | OR MORE CLASSES OF OCCUPANCY EXIST. |
| | 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE |
| | THE |
| | OCCUPANCIES ARE INTERMINGLED. |
| | 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY |
| | WHERE THE |
| | OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCE?RATED |
| | ASSEMBLIES. |
| | 6.1.14.3 MIXED OCCUPANCIES. |
| | 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE |
| | CLASSIFIED AS TO ITS USE IN |
| | ACCORDANCE WITH SECTION 6.1. |
| | 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST |
| | RESTRICTIVE |
| | REQUIREMENTS OF THE OCCUPANCIES INVOLVED, UNLESS |
| | SEPARATE SAFEGUARDS |
| | ARE APPROVED. |
| | 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.) |
| | 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED, |
| | EACH PART OF THE |
| | BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED |
| | IN THIS CHAPTER, |
| | SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY |
| | FIRE-RESISTIVE |
| | ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3, |
| | TABLE 6.1.14.4.1(A), |
| | AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED |
| | BY APPROVED |
| | EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY |
| | 6.1.14.4.6. |
| | |
| | 6.1.14.4.3 THE MINIMUM FIRE RESISTANCE RATING SPECIFIED |
| | IN TABLE |
| | 6.1.14.4.1(A) AND TABLE 6.1.14.4.1(B) SHALL BE |
| | PERMITTED TO BE |
| | REDUCED BY 1 HOUR, BUT IN NO CASE SHALL IT BE REDUCED |
| | TO LESS THAN 1 |
| | HOUR, WHERE THE BUILDING IS PROTECTED THROUGHOUT BY AN |
| | APPROVED |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| | 9.7.1.1(1) AND |
| | SUPERVISED IN ACCORDANCE WITH 9.7.2, UNLESS PROHIBITED |
| | BY THE |
| | DOUBLE-DAGGER FOOTNOTE ENTRIES IN THE TABLES. |
| | 6.1.14.4.4 OCCUPANCY SEPARATIONS SHALL BE VERTICAL, |
| | HORIZONTAL, OR |
| | BOTH OR, WHEN NECESSARY, OF SUCH OTHER FORM AS REQUIRED |
| | TO PROVIDE |
| | COMPLETE SEPARATION BETWEEN OCCUPANCY DIVISIONS IN THE |
| | BUILDING. |
| | 6.1.14.4.5* EACH SEPARATED PORTION OF THE BUILDING |
| | SHALL COMPLY |
| | WITH THE REQUIREMENTS FOR THE OCCUPANCY THEREIN. |
| | |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSITFY WITH SPECIFIC CODE |
| | REFERENCES. |
| | |
| | |
| | |
| | 2) SHEET A 0.02 - TWO EXITS ARE SHOWN ON FLOORS 2 AND 3 |
| | HOWEVER, THEY DO NOT MEET THE REQUIRED EXIT SEPARATION |
| | PER NFPA 101, CHAPTER 7 MEANS OF EGRESS. |
| | |
| | 38.2.4 NUMBER OF MEANS OF EGRESS. |
| | 38.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE |
| | FOLLOWING, EXCEPT |
| | AS OTHERWISE PERMITTED BY 38.2.4.2 THROUGH 38.2.4.6: |
| | (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 7.4. |
| | (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED |
| | ON EVERY STORY. |
| | (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE |
| | ACCESSIBLE FROM EVERY |
| | PART OF EVERY STORY. |
| | |
| | |
| | 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR |
| | EXIT DISCHARGE IS |
| | REQUIRED FROM A BUILDING OR PORTION THEREOF, SUCH |
| | EXITS, EXIT ACCESSES, |
| | OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED FROM EACH |
| | OTHER AND BE |
| | ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE |
| | HAS THE |
| | POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR OTHER |
| | EMERGENCY |
| | CONDITION. |
| | 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT |
| | DISCHARGES ARE |
| | REQUIRED, THEY SHALL BE LOCATED AT A DISTANCE FROM ONE |
| | ANOTHER NOT |
| | LESS THAN ONE-HALF THE LENGTH OF THE MAXIMUM OVERALL |
| | DIAGONAL |
| | DIMENSION OF THE BUILDING OR AREA TO BE SERVED, |
| | MEASURED IN A |
| | STRAIGHT LINE BETWEEN THE NEAREST EDGE OF THE EXITS, |
| | EXIT ACCESSES, OR |
| | EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED IN 7.5.1.3.3 |
| | THROUGH |
| | 7.5.1.3.5. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES. |
| | |
| | |
| | |
| | 3) SHEET 1.04 - THERE IS ONLY ONE EXIT INDICATED FROM |
| | THE ROOF PATIO, TWO ARE REQUIRED. |
| | |
| | PER NFPA 101, CHAPTER 38, NEW BUSINESS OCCUPANCIES |
| | |
| | 38.2.4 NUMBER OF MEANS OF EGRESS. |
| | 38.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE |
| | FOLLOWING, EXCEPT |
| | AS OTHERWISE PERMITTED BY 38.2.4.2 THROUGH 38.2.4.6: |
| | (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 7.4. |
| | (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED |
| | ON EVERY STORY. |
| | (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE |
| | ACCESSIBLE FROM EVERY |
| | PART OF EVERY STORY. |
| | |
| | |
| | 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR |
| | EXIT DISCHARGE IS |
| | REQUIRED FROM A BUILDING OR PORTION THEREOF, SUCH |
| | EXITS, EXIT ACCESSES, |
| | OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED FROM EACH |
| | OTHER AND BE |
| | ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE |
| | HAS THE |
| | POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR OTHER |
| | EMERGENCY |
| | CONDITION. |
| | 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT |
| | DISCHARGES ARE |
| | REQUIRED, THEY SHALL BE LOCATED AT A DISTANCE FROM ONE |
| | ANOTHER NOT |
| | LESS THAN ONE-HALF THE LENGTH OF THE MAXIMUM OVERALL |
| | DIAGONAL |
| | DIMENSION OF THE BUILDING OR AREA TO BE SERVED, |
| | MEASURED IN A |
| | STRAIGHT LINE BETWEEN THE NEAREST EDGE OF THE EXITS, |
| | EXIT ACCESSES, OR |
| | EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED IN 7.5.1.3.3 |
| | THROUGH |
| | 7.5.1.3.5. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES. |
| | |
| | |
| | |
| | 4) SHEET E 2 & E 3 - THERE NO INDICATIONS OF EMERGENCY |
| | LIGHTING. |
| | |
| | PER NFPA 101, CHAPTER 38, NEW BUSINESS OCCUPANCIES |
| | |
| | 38.2.9 EMERGENCY LIGHTING. |
| | 38.2.9.1 EMERGENCY LIGHTING SHALL BE PROVIDED IN |
| | ACCORDANCE |
| | WITH SECTION 7.9 IN ANY BUILDING WHERE ANY ONE OF THE |
| | FOLLOWING |
| | CONDITIONS EXISTS: |
| | (1) THE BUILDING IS THREE OR MORE STORIES IN HEIGHT. |
| | (2) THE OCCUPANCY IS SUBJECT TO 50 OR MORE OCCUPANTS |
| | ABOVE OR |
| | BELOW THE LEVEL OF EXIT DISCHARGE. |
| | (3) THE OCCUPANCY IS SUBJECT TO 300 OR MORE TOTAL |
| | OCCUPANTS. |
| | |
| | 7.9 EMERGENCY LIGHTING. |
| | 7.9.1 GENERAL. |
| | 7.9.1.1* EMERGENCY LIGHTING FACILITIES FOR MEANS OF |
| | EGRESS SHALL BE |
| | PROVIDED IN ACCORDANCE WITH SECTION 7.9 FOR THE |
| | FOLLOWING: |
| | (1) BUILDINGS OR STRUCTURES WHERE REQUIRED IN CHAPTERS |
| | 11 THROUGH 43 |
| | (2) UNDERGROUND AND LIMITED ACCESS STRUCTURES AS |
| | ADDRESSED IN SECTION |
| | 11.7 |
| | (3) HIGH-RISE BUILDINGS AS REQUIRED BY OTHER SECTIONS |
| | OF THIS CODE |
| | (4) DOORS EQUIPPED WITH DELAYED-EGRESS LOCKS |
| | (5) STAIR SHAFTS AND VESTIBULES OF SMOKEPROOF |
| | ENCLOSURES, FOR WHICH THE |
| | FOLLOWING ALSO APPLY: |
| | (A) THE STAIR SHAFT AND VESTIBULE SHALL BE PERMITTED TO |
| | INCLUDE A |
| | STANDBY GENERATOR THAT IS INSTALLED FOR THE SMOKEPROOF |
| | ENCLOSURE MECHANICAL VENTILATION EQUIPMENT. |
| | (B) THE STANDBY GENERATOR SHALL BE PERMITTED TO BE USED |
| | FOR THE |
| | STAIR SHAFT AND VESTIBULE EMERGENCY LIGHTING POWER |
| | SUPPLY. |
| | (6) NEW ACCESS-CONTROLLED EGRESS DOORS IN ACCORDANCE |
| | WITH 7.2.1.6.2 |
| | 7.9.1.2 FOR THE PURPOSES OF 7.9.1.1, EXIT ACCESS SHALL |
| | INCLUDE ONLY |
| | DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS, |
| | ESCALATORS, AND PASSAGEWAYS |
| | LEADING TO AN EXIT. FOR THE PURPOSES OF 7.9.1.1, EXIT |
| | DISCHARGE SHALL |
| | INCLUDE ONLY DESIGNATED STAIRS, RAMPS, AISLES, |
| | WALKWAYS, AND ESCALATORS |
| | LEADING TO A PUBLIC WAY. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES. |
| | |
| | |
| | |
| | 5) SHEET E2 & E3 - THE ARE NO INDICATIONS OF LIGHTING |
| | THE MEANS OF EGRESS |
| | |
| | 38.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS |
| | SHALL |
| | BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8. |
| | |
| | 7.8 ILLUMINATION OF MEANS OF EGRESS. |
| | 7.8.1 GENERAL. |
| | 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| | PROVIDED IN |
| | ACCORDANCE WITH SECTION 7.8 FOR EVERY BUILDING AND |
| | STRUCTURE WHERE |
| | REQUIRED IN CHAPTERS 11 THROUGH 43. FOR THE PURPOSES OF |
| | THIS |
| | REQUIREMENT, EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED |
| | STAIRS, AISLES, |
| | CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING |
| | TO AN EXIT. FOR THE |
| | PURPOSES OF THIS REQUIREMENT, EXIT DISCHARGE SHALL |
| | INCLUDE ONLY |
| | DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS, |
| | ESCALATORS, WALKWAYS, AND EXIT |
| | PASSAGEWAYS LEADING TO A PUBLIC WAY. |
| | 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| | CONTINUOUS DURING THE |
| | TIME THAT THE CONDITIONS OF OCCUPANCY REQUIRE THAT THE |
| | MEANS OF EGRESS |
| | BE AVAILABLE FOR USE, UNLESS OTHERWISE PROVIDED IN |
| | 7.8.1.2.2. |
| | |
| | |
| | |
| | |
| | 6) IS IT THE INTENT TO PROVIDE FIRE ALARM AND FIRE |
| | SPRINKLER SYSTEMS TO THE PROPOSED TENANT SPACES? |
| | |
| | ANY INTENT OF THESE SYSTEMS SHALL COMPLY WITH THE |
| | REQUIREMENTS OF F.A.C 61G AND BE SUBMITTED WITH THIS |
| | MASTER PERMIT. SHOP DRAWINGS WILL BE REQUIRED ON A |
| | FUTURE SUBMITTAL BY QUALFIED CONTRACTORS. |
| | |
| | 61G15-32.008 DESIGN OF FIRE ALARMS, SIGNALING SYSTEMS |
| | AND CONTROL SYSTEMS. |
| | (1) FIRE ALARMS, SIGNALING, AND CONTROL SYSTEMS |
| | INCLUDE, BUT ARE NOT LIMITED TO, FIRE PROTECTION |
| | SUPERVISION AND ALARM CIRCUITS, ACTIVATION CONTROLS, |
| | AND REMOTE SIGNALING. |
| | (2) THE FIRE PROTECTION SYSTEM DESIGN SPECIFICATIONS |
| | SHALL BE BASED ON APPLICABLE NFPA STANDARDS, WHEN |
| | AVAILABLE, OR ALTERNATIVE ENGINEERING SOURCES AND GOOD |
| | ENGINEERING PRACTICE WHEN REQUIRED, AND SHALL COMPLY |
| | WITH THE PROVISIONS OF RULE 61G15-33.006, F.A.C. |
| | SPECIFIC AUTHORITY 471.008, 471.033(2) FS. |
| | LAW IMPLEMENTED 471.033 FS. |
| | HISTORY--NEW 5-19-93, FORMERLY 21H-32.008. |
| | |
| | |
| | 61G15-32.003 COMMON REQUIREMENTS TO ALL FIRE PROTECTION |
| | ENGINEERING |
| | DOCUMENTS. |
| | (1) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS |
| | SHALL PROVIDE THE ENGINEERING REQUIREMENTS TO BE USED |
| | IN THE PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT |
| | DOCUMENTS AND TO INDICATE THE NATURE AND SCOPE OF THE |
| | WORK, AND TO DESCRIBE, DETAIL, DIMENSION, LABEL AND |
| | DEFINE THE FIRE PROTECTION COMPONENTS, SYSTEM(S), |
| | MATERIALS, ASSEMBLIES, EQUIPMENT AND ITS STRUCTURAL AND |
| | UTILITY SUPPORT SYSTEM(S), INSOFAR AS THEY INVOLVE THE |
| | SAFEGUARDING OF LIFE, HEALTH OR PROPERTY. |
| | (2) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS |
| | SHALL SPECIFY THE APPLICABLE REQUIREMENTS FOR THE |
| | ACCEPTANCE TESTING OF THE FIRE PROTECTION SYSTEM AND |
| | COMPONENTS, WHICH SHALL BE BASED UPON APPLICABLE CODES |
| | AND STANDARDS, WHERE AVAILABLE. |
| | (3) THE OCCUPANCY OF THE AREA OR DESCRIPTION OF A |
| | SPECIFIC HAZARD BEING PROTECTED BY THE FIRE PROTECTION |
| | SYSTEM(S) SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. |
| | (4) THE APPLICABLE CODE AND STANDARD TO BE USED IN THE |
| | PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT |
| | DOCUMENTS SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. WHEN CODES AND STANDARDS ARE NOT |
| | AVAILABLE OR APPLICABLE, AND SAID LAYOUT DOCUMENTS ARE |
| | TO BE BASED ON ENGINEERING JUDGMENT, ANY REASONS AND |
| | ASSUMPTIONS MADE TO DEVELOP THE FIRE PROTECTION CONCEPT |
| | SHALL BE IDENTIFIED ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. |
| | (5) STRUCTURAL SUPPORT AND STRUCTURAL OPENINGS REQUIRED |
| | BY THE FIRE PROTECTION SYSTEM SHALL BE SHOWN ON THE |
| | FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS AND SHALL |
| | BE REFERENCED ON STRUCTURAL ENGINEERING DOCUMENTS. |
| | (6) WHEN LAYOUT DOCUMENTS CONTAIN MATERIAL DEVIATION |
| | FROM THE ENGINEER OF RECORD'S FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENT, SUCH LAYOUT DOCUMENTS ARE NOT |
| | COMPLIANT UNLESS THEY ARE ACCOMPANIED BY REVISED |
| | ENGINEERING DOCUMENTS MADE AND SEALED BY THE ENGINEER |
| | OF RECORD FOR THE FIRE PROTECTION SYSTEM. |
| | (7) REQUIREMENTS FOR ACTIVATION CONTROL SYSTEMS, |
| | SEQUENCE, OPERATING PARAMETERS, INTERLOCKS, SAFETY |
| | RELATED DEVICES, INDICATORS AND ALARMS, SHALL BE SHOWN |
| | ON THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS, |
| | UNLESS SHOWN ON OTHER RELATED DOCUMENTS. |
| | (8) ANY INFORMATION DEEMED APPROPRIATE BY THE ENGINEER |
| | OF RECORD TO ASSIST THE AUTHORITY HAVING JURISDICTION |
| | IN UNDERSTANDING THE OWNER?S INTENDED USE AND PROPOSED |
| | PROTECTION OF THE BUILDING OR FACILITY AND TO PROVIDE |
| | SUFFICIENT DIRECTION TO THE INSTALLATION CONTRACTOR OR |
| | OTHER INTERESTED PARTIES REGARDING THE LAYOUT OF THE |
| | SYSTEM(S), SHALL BE INCLUDED IN THE FIRE PROTECTION |
| | SYSTEM ENGINEERING DOCUMENTS. |
| | SPECIFIC AUTHORITY 471.008, 471.033(2), FS |
| | LAW IMPLEMENTED 471.005(7), 471.033(2), FS |
| | HISTORY?NEW 5-19-93, FORMERLY 21H-32.003, AMENDED |
| | 4-2-2000, 6-26-01 |
| | |
| | 61G15-32.004 DESIGN OF WATER BASED FIRE PROTECTION |
| | SYSTEMS. |
| | (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT |
| | ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET, |
| | DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE |
| | CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE |
| | WATER MAINS AND DEDICATED FIRE PROTECTION WATER |
| | SOURCES. |
| | (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION |
| | SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL |
| | INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN |
| | APPLICABLE: |
| | (A) THE POINT OF SERVICE FOR THE FIRE PROTECTION WATER |
| | SUPPLY AS DEFINED BY 633.021(18) F.S. |
| | (B) APPLICABLE NFPA STANDARD TO BE APPLIED, OR IN THE |
| | CASE WHERE NO SUCH STANDARD EXISTS, THE ENGINEERING |
| | STUDY, JUDGMENTS, AND/OR PERFORMANCE BASED ANALYSIS AND |
| | CONCLUSIONS. |
| | (C) CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA. |
| | (D) DESIGN APPROACH, WHICH INCLUDES SYSTEM TYPE, |
| | DENSITIES, DEVICE TEMPERATURE RATING, AND SPACING FOR |
| | EACH SEPARATE 42 HAZARD OCCUPANCY. |
| | (E) CHARACTERISTICS OF WATER SUPPLY TO BE USED, SUCH AS |
| | MAIN SIZE AND LOCATION, WHETHER IT IS DEAD-END OR |
| | CIRCULATING; AND IF DEAD-END, THE DISTANCE TO THE |
| | NEAREST CIRCULATING MAIN, AS WELL AS ITS MINIMUM |
| | DURATION AND RELIABILITY FOR THE MOST HYDRAULICALLY |
| | DEMANDING DESIGN AREA. |
| | (F) WHEN PRIVATE OR PUBLIC WATER SUPPLIES ARE USED, THE |
| | FLOW TEST DATA, INCLUDING DATE AND TIME OF TEST, WHO |
| | CONDUCTED TEST OR SUPPLIED INFORMATION, TEST ELEVATION, |
| | STATIC GAUGE PRESSURE AT NO FLOW, FLOW RATE WITH |
| | RESIDUAL GAUGE PRESSURE, HYDRANT BUTT COEFFICIENT, AND |
| | LOCATION OF TEST IN RELATION TO THE HYDRAULIC POINT OF |
| | SERVICE. |
| | (G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE |
| | POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF |
| | WATER. |
| | (H) MICROBIAL INDUCED CORROSION (MIC). THE ENGINEER OF |
| | RECORD SHALL MAKE REASONABLE EFFORTS TO IDENTIFY WATER |
| | SUPPLIES THAT COULD LEAD TO MICROBIAL INDUCED CORROSION |
| | (MIC). SUCH EFFORTS MAY CONSIST OF DISCUSSIONS WITH THE |
| | LOCAL WATER PURVEYOR AND/OR FIRE OFFICIAL, FAMILIARITY |
| | WITH CONDITIONS IN THE LOCAL AREA, OR LABORATORY |
| | TESTING OF WATER SUPPLIES. WHEN CONDITIONS ARE FOUND |
| | THAT MAY RESULT IN MIC CONTAMINATION OF THE FIRE |
| | PROTECTION PIPING, THE ENGINEER SHALL DESIGN CORRECTIVE |
| | MEASURES. |
| | (I) BACKFLOW PREVENTION AND METERING SPECIFICATIONS AND |
| | DETAILS TO MEET LOCAL WATER PURVEYOR REQUIREMENTS |
| | INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP. |
| | (J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD |
| | AND INTERIOR FIRE PROTECTION COMPONENTS. |
| | (3) CONTRACTOR SUBMITTALS WHICH DEVIATE FROM THE ABOVE |
| | MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED MATERIAL |
| | DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING |
| | APPROVAL AND DOCUMENTATION. |
| | (4) IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE |
| | INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE |
| | OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL |
| | ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE |
| | CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES. |
| | SPECIFIC AUTHORITY 471.008, 471.033(2), FS |
| | LAW IMPLEMENTED 471.005(7), 471.033(2), FS |
| | HISTORY?NEW 5-19-93, FORMERLY 21H-32.004, AMENDED |
| | 4-2-2000, 6-26-01, 7-12-05 |
| | |
| | |
| | |
| | |
| | 7) THERE IS AN ELEVATOR INDICATED AS EXISTING. |
| | |
| | PER NFPA 101 CHAPTER 38 |
| | |
| | 38.5.3 ELEVATORS, ESCALATORS, AND CONVEYORS. ELEVATORS, |
| | ESCALATORS, AND CONVEYORS SHALL COMPLY WITH THE |
| | PROVISIONS OF |
| | SECTION 9.4. |
| | |
| | 9.4.2.2 EXCEPT AS MODIFIED HEREIN, EXISTING ELEVATORS, |
| | ESCALATORS, |
| | DUMBWAITERS, AND MOVING WALKS SHALL BE IN ACCORDANCE |
| | WITH THE |
| | REQUIREMENTS OF ASME A17.3, SAFETY CODE FOR EXISTING |
| | ELEVATORS |
| | AND ESCALATORS. |
| | |
| | 9.4.3 FIRE FIGHTERS? EMERGENCY OPERATIONS. |
| | |
| | 9.4.3.2 ALL EXISTING ELEVATORS HAVING A TRAVEL DISTANCE |
| | OF 25 FT |
| | (7620 MM) OR MORE ABOVE OR BELOW THE LEVEL THAT BEST |
| | SERVES THE |
| | NEEDS OF EMERGENCY PERSONNEL FOR FIRE-FIGHTING OR |
| | RESCUE PURPOSES |
| | SHALL CONFORM TO THE FIRE FIGHTERS? EMERGENCY |
| | OPERATIONS |
| | REQUIREMENTS OF ASME A17.3, SAFETY CODE FOR EXISTING |
| | ELEVATORS |
| | AND ESCALATORS. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES. |
| | |
| | |
| | |
| | |
| | 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |
| | |