Plan Review Details - Permit 18081580
Plan Review Stops For Permit 18081580
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-10-31 Cont ID  
Sent By dbattles Date 2018-10-31 Time 15:33 Rev Time 0.00
Received By dbattles Date 2018-10-31 Time 15:33 Sent To  
Notes
2018-10-31 15:34:32PROVISO:
 PLEASE HAVE OWNER SIGN THE ENERGY CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-28 Cont ID  
Sent By dbattles Date 2018-09-28 Time 15:18 Rev Time 0.00
Received By dbattles Date 2018-09-28 Time 15:18 Sent To  
Notes
2018-09-28 15:20:09****CORRECTIONS****
 W.P.B. PERMIT: 18081580
 REVIEWED: SEPTEMBER 28, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC ENERGY R401.2]PROVIDE ENERGY CALCULATIONS TO
 MEET REQUIREMENTS IN RESIDENTIAL ENERGY CODE. CHOOSE
 METHOD IN R401.2 AND SUPPLY DOCUMENTATION.
 PLEASE INCLUDE ALL SKYLIGHTS AND SOLAR TUBES IN THE
 CALCULATIONS.
  
 2. [FBC R302.10]PROVIDE CUT SHEET FOR ICYNENE(ICC-ES
 REPORT OR EQUAL) WITH THE TYPE SELECTED TO ESTABLISH
 THICKNESS NEEDED TO MEET REQUIRED R-VALUE, FLAME SPREAD
 INDEX AND SMOKE DEVELOPED INDEX.
  
 3. [FBC R408.4]ACCESS TO UNDER FLOOR SPACE. ACCESS
 OPENINGS THROUGH THE FLOOR SHALL BE A MINIMUM OF 18
 INCHES BY 24 INCHES. OPENINGS THROUGH A PERIMETER WALL
 SHALL BE NOT LESS THAN 16 INCHES BY 24 INCHES.
  
 4. [FBC R408.4]IS THERE CURRENTLY ACCESS TO UNDER FLOOR
 SPACE? SHOW WHERE IT IS LOCATED.
 ALSO, PROVIDE EXISTING UNDER FLOOR VENTING AMOUNT AND
 ADDITIONAL VENTING FOR ENTRY RAISED FLOOR.
  
 5. [FBC R318]SHEET S1 SHOWS TERMITE TREATMENT AT NEW
 CONCRETE ONLY.
 PLEASE ADD NOTE TO TREAT AREA AT ENTRY WHERE NEW FLOOR
 IS GOING IN AND AT REAR WHERE COVERING SLAB. EVEN
 THOUGH EXISTING SLAB REMAINS THAT AREA SHOULD MEET
 CURRENT CODES.
  
 6. [FBC R506.2.3]AT EXISTING SLAB TO REMAIN. THIS SLAB
 SEEMS LIKE SOMETHING THAT WAS EXTERIOR AND WOULD NOT
 HAVE PROPER VAPOR BARRIER, OR IT WOULS BE TO OLD TO
 CONSIDER ADEQUATE. PLEASE ADDRESS HOW PROPER VAPOR
 BARRIER IS BEING PROVIDED FOR AREAS WHERE EXISTING SLAB
 IS TO REMAIN.
  
 7. [FBC R301.4]&[FBC R301.5]PROVIDE LIVE LOAD AND DEAD
 LOAD INFORMATION ON SHEET S-2 FOR ROOF LOADS.
  
 8. [FBC 107.2.5]SHEET A1 AT GARAGE DETAIL LEFT SIDE
 A/A1. IS THIS SUPPOSE TO LEAD TO A DETAIL?
 PROVIDE DETAIL, DETAIL NUMBER OR DELETE AS APPLICABLE.
  
 9. [FBC 107.2.5]SHEET S1 CALL OUTS A/S1 DON'T LEAD TO
 CORRECT DETAIL PAGE.
 PLEASE ADJUST PAGE NUMBER ON CALLOUTS.
  
 10. [FAC RULE 9N-3]PROVIDE PRODUCT APPROVAL FOR FRENCH
 DOOR, WINDOW MULL, SKYLIGHTS AND SOLAR TUBES.
  
 11. IS THE ENTRYWAY THE MAHOGANY DOOR FROM FL-15209.3?
 THIS PRODUCT APPROVAL FOR OXO ARRANGEMENT PROVIDES MAX
 +40/-40. SHEET A2A DESIGN DATA SHOW DESIGN PRESSURES AT
 +52.2/-56.8 FOR INTERIOR ZONES.
 PLEASE PROVIDE DATA TO SHOW THAT THE DOOR WILL MEET
 PRESSURES.
  
 12. [FBC AMENDED 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS
 TO THE BUILDING INSPECTOR PRIOR TO INSTALLATION.
  
 13. [FBC AMENDED 107.3.4.1]SEE COMMENTS IN ROOFING
 REVIEW, OR INDICATE THAT YOU WOULD LIKE THEM DEFERED.
 IF DEFERRED THE NOA'S WILL BE APPROVED, BUT THE
 ADDITIONAL ATTACHMENT MATERIALS WILL NEED TO BE
 SUBMITTED WITH THE ROOFING SUB PERMIT.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-11-06 Cont ID  
Sent By jpearson Date 2018-11-06 Time 10:50 Rev Time 0.00
Received By jpearson Date 2018-11-06 Time 07:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-25 Cont ID  
Sent By jpearson Date 2018-09-25 Time 15:19 Rev Time 0.00
Received By jpearson Date 2018-09-25 Time 10:37 Sent To  
Notes
2018-09-25 15:19:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. PLAN SHOWS A POOL, BUT THIS IS NOT INCLUDED IN
 LOAD CALCULATION. NEC 220; FBC RE E3602.2
 2. NOTE BY RISER DIAGRAM STATES THAT RECEPTACLES SHALL
 BE TAMPER RESISTANT PER NEC 406.11. THIS CODE SECTION
 DOES NOT APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE E4002.14
 3. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902
 4. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE
 OUTLETS IN GARAGE, INCLUDING GARAGE DOOR OPENER.
 PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 6. LIGHT FIXTURES IN CLOSET NOT SPECIFIED, BUT APPEAR
 TO BE RECESS LIGHTS. PER CODE, LIGHTING WITH OPEN OR
 PARTIALLY ENCLOSED LAMPS AND PENDANT LUMINAIRES OR
 LAMPHOLDERS SHALL NOT BE PERMITTED IN CLOTHES CLOSETS.
 PROVIDE CORRECTION. NEC 410.16; FBC RE E4003.12
 7. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1
 8. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION FOR MASTER BATH. NEC 210.11(C)(3),
 210.52(D); FBC RE E3703.4, E3901.6
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-12-10 Cont ID  
Sent By dbattles Date 2018-12-10 Time 12:42 Rev Time 0.00
Received By dbattles Date 2018-12-05 Time 09:31 Sent To  
Notes
2018-12-07 09:32:03IMPACT FEES ROUTED TO DBATTLES

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-28 Cont ID  
Sent By tklarge Date 2018-11-28 Time 11:44 Rev Time 0.00
Received By tklarge Date 2018-10-19 Time 16:18 Sent To  
Notes
2018-10-22 16:18:42R35

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-02 Cont ID  
Sent By hmoser Date 2018-10-02 Time 15:45 Rev Time 0.00
Received By hmoser Date 2018-08-31 Time 15:44 Sent To  
Notes
2018-09-04 15:44:34R13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-12-10 Cont ID  
Sent By dbattles Date 2018-12-10 Time 12:41 Rev Time 0.00
Received By dbattles Date 2018-12-10 Time 12:41 Sent To  
Notes
2018-12-10 12:42:24M.U.# 2018-039878-0000
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-09-28 Cont ID  
Sent By dbattles Date 2018-09-28 Time 15:22 Rev Time 0.00
Received By dbattles Date 2018-09-28 Time 15:22 Sent To  
Notes
2018-09-28 15:23:06[FBC AMENDED 109]PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-11-15 Cont ID  
Sent By cmontell Date 2018-11-15 Time 15:05 Rev Time 0.00
Received By cmontell Date 2018-11-15 Time 14:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-10-02 Cont ID  
Sent By hmoser Date 2018-10-02 Time 15:45 Rev Time 0.00
Received By hmoser Date 2018-10-02 Time 15:37 Sent To I
Notes
2018-10-02 15:45:16PLAN DENIED
 1) PROVIDE MANUFACTURES SPECS. FOR RANGE HOOD
 PER SECTION M1503.4 MAKE UP AIR REQUIRED 2017
 RESIDENTIAL CODE.
 2) REFER TO NOTE 19 ON PLAN FOR BALANCED RETURN AIR
 FOR MASTER BEDROOM.
 3) PROVIDE ENERGY CALCULATIONS FOR ADDITION. PER
 SECTION M1401.3 SIZING
 4) PROVIDE AHRI SHEETS FOR EQUIPMENT.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-11-28 Cont ID  
Sent By tklarge Date 2018-11-28 Time 11:40 Rev Time 0.00
Received By tklarge Date 2018-11-28 Time 10:42 Sent To I
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2018-10-31 Cont ID  
Sent By dbattles Date 2018-10-31 Time 15:28 Rev Time 0.00
Received By dbattles Date 2018-10-31 Time 15:28 Sent To  
Notes
2018-10-31 15:33:44CONCRETE ROOF TILE NOA 14-0102.04 IS OK.
 THE TWO UNDERLAYMENT PRODUCT APPROVALS BACK TO
 CONTRACTOR AND SUBMIT WITH ROOF SUB PERMIT THE ONE THAT
 WILL BE USED (SEE COMMENTS BELOW FOR ADDITIONAL INFO
 NEEDED).
  
 1. PROVIDE PRODUCT APPROVAL FOR TILE ATTACHMENT
 MATERIAL BASED ON THE MAXIMUM DESIGN PRESSURE FOR THE
 ROOF.
  
 2. WHY ARE THERE TWO PRODUCT APPROVALS FOR
 UNDERLAYMENTS.
 CHOOSE WHICH ONE WILL BE USED AND SELECT ON THE PRODUCT
 APPROVAL THE ONE THAT MEETS REQUIRMENTS FOR
 UNDERLAYMENT FOR CONCRETE TILE ROOF (SEE NOA 14-0102.04
 SECTION 4.1)
 PROVIDE UNDERLAYMENT ATTACHMENT ENGINEERING FOR
 SELECTED UNDERLAYMENT FOR APPLICABLE ROOF ZONES.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-09-28 Cont ID  
Sent By dbattles Date 2018-09-28 Time 15:23 Rev Time 0.00
Received By dbattles Date 2018-09-28 Time 15:23 Sent To  
Notes
2018-09-28 15:33:091. PROVIDE PRODUCT APPROVAL FOR TILE ATTACHMENT
 MATERIAL BASED ON THE MAXIMUM DESIGN PRESSURE FOR THE
 ROOF.
  
 2. WHY ARE THERE TWO PRODUCT APPROVALS FOR
 UNDERLAYMENTS.
 CHOOSE WHICH ONE WILL BE USED AND SELECT ON THE PRODUCT
 APPROVAL THE ONE THAT MEETS REQUIRMENTS FOR
 UNDERLAYMENT FOR CONCRETE TILE ROOF (SEE NOA 14-0102.04
 SECTION 4.1)
 PROVIDE UNDERLAYMENT ATTACHMENT ENGINEERING FOR
 SELECTED UNDERLAYMENT FOR APPLICABLE ROOF ZONES.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  

Review Stop Z ZONING
Rev No 3 Status P Date 2019-05-30 Cont ID  
Sent By awooten Date 2019-05-30 Time   Rev Time 0.00
Received By awooten Date 2019-05-30 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-10-30 Cont ID  
Sent By awooten Date 2018-10-30 Time 14:48 Rev Time 0.00
Received By awooten Date 2018-10-29 Time 13:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-09-21 Cont ID  
Sent By awooten Date 2018-09-21 Time   Rev Time  
Received By awooten Date 2018-09-21 Time   Sent To  
Notes
***NONE***