Plan Review Details - Permit 18081549
Plan Review Stops For Permit 18081549
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-09-20 Cont ID  
Sent By jleahy Date 2018-09-20 Time 17:01 Rev Time 0.00
Received By jleahy Date 2018-09-20 Time 17:01 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-09-05 Cont ID  
Sent By pleduc Date 2018-09-05 Time   Rev Time 0.00
Received By pleduc Date 2018-09-05 Time 12:00 Sent To E
Notes
2018-09-05 12:10:06THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) THERE ARE INDICATIONS THAT A DUCT DETECTOR WILL
 CAUSE A FULL FIRE ALARM ACTIVATION. NFPA PROVIDES CODE
 REFERENCES FOR SUPERVISORY SIGNAL ACTIVATION.
  
 PER NFPA 90A, 2015 ED.
  
 6.4.3* FUNCTION.
 6.4.3.1 SMOKE DETECTORS PROVIDED AS REQUIRED BY 6.4.2
 SHALL AUTOMATICALLY STOP THEIR RESPECTIVE FAN(S) ON
 DETECTING THE PRESENCE OF SMOKE.
  
 6.4.4.2 IN ADDITION TO THE REQUIREMENTS OF 6.4.3, WHERE
 AN APPROVED FIRE ALARM SYSTEM IS INSTALLED IN A
 BUILDING, THE SMOKE DETECTORS REQUIRED BY THE
 PROVISIONS OF SECTION 6.4 SHALL BE CONNECTED TO THE
 FIRE ALARM SYSTEM IN ACCORDANCE WITH THE REQUIREMENTS
 OF NFPA 72, NATIONAL FIRE ALARM AND SIGNALING
 CODE.
  
 6.4.4.2.1 SMOKE DETECTORS USED SOLELY FOR CLOSING
 DAMPERS OR FOR HEATING, VENTILATING, AND
 AIR-CONDITIONING SYSTEM SHUTDOWN SHALL NOT BE REQUIRED
 TO ACTIVATE THE BUILDING EVACUATION ALARM.
  
 6.4.4.3 WHERE SMOKE DETECTORS REQUIRED BY SECTION 6.4
 ARE INSTALLED IN A BUILDING NOT EQUIPPED WITH AN
 APPROVED FIRE ALARM SYSTEM AS SPECIFIED BY 6.4.4.2, THE
 FOLLOWING SHALL OCCUR:
 (1) SMOKE DETECTOR ACTIVATION REQUIRED BY SECTION 6.4
 SHALL CAUSE A VISUAL SIGNAL AND AN AUDIBLE SIGNAL IN A
 NORMALLY OCCUPIED AREA.
 (2) SMOKE DETECTOR TROUBLE CONDITIONS SHALL BE
 INDICATED VISUALLY OR AUDIBLY IN A NORMALLY OCCUPIED
 AREA AND SHALL BE IDENTIFIED AS AIR DUCT DETECTOR
 TROUBLE.
  
 PER NFPA 72, 2013 ED
 23.8.5.4.6 SIGNAL INITIATION ? DUCT SMOKE DETECTORS.
 23.8.5.4.6.1 WHERE DUCT SMOKE DETECTORS ARE REQUIRED TO
 BE MONITORED AND A BUILDING FIRE ALARM SYSTEM IS
 INSTALLED, A DUCT DETECTOR ACTIVATION SIGNAL SHALL MEET
 THE REQUIREMENTS OF 21.7.4.
 21.7.4 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF HVAC
 SYSTEMS SHALL INITIATE A SUPERVISORY SIGNAL.
 21.7.4.1 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF
 HVAC SYSTEMS IN A FIRE ALARM SYSTEM WITHOUT A
 CONSTANTLY ATTENDED LOCATION OR SUPERVISING STATION
 SHALL BE PERMITTED TO INITIATE AN ALARM SIGNAL.
 21.7.4.2 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF
 HVAC SYSTEMS SHALL BE PERMITTED TO INITIATE AN ALARM
 SIGNAL WHERE REQUIRED BY OTHER GOVERNING LAWS, CODES,
 OR STANDARDS.
  
 PLEASE PROGRAM ACCORDINGLY FOR SUPERVISORY ACTIVATION.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-09-21 Time   Rev Time 0.00
Received By lmarchan Date 2018-08-31 Time 13:45 Sent To  
Notes
2018-09-04 13:45:23ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-09-21 Cont ID  
Sent By ccole Date 2018-09-21 Time 14:20 Rev Time 0.00
Received By ccole Date 2018-09-21 Time 14:20 Sent To I
Notes
***NONE***