Plan Review Details - Permit 18081520
Plan Review Stops For Permit 18081520
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-10-03 Cont ID  
Sent By dbattles Date 2018-10-03 Time 16:01 Rev Time 0.00
Received By dbattles Date 2018-10-03 Time 16:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-25 Cont ID  
Sent By cthroop Date 2018-09-25 Time 10:51 Rev Time 0.00
Received By cthroop Date 2018-09-25 Time 10:51 Sent To I
Notes
2018-09-25 10:55:51BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SITE FENCING SHALL COMPLY WITH FBC CHPT. 33
 SAFEGUARDS DURING CONSTRUCTION.
 2. MATERIAL CONTAINERS ON PLAN ARE NOT PART OF THIS
 PERMIT. REMOVE FROM PLAN.
 3. PROVIDE A DETAIL OF FENCE INSTALLATION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-10-10 Cont ID  
Sent By pleduc Date 2018-10-10 Time   Rev Time 0.00
Received By pleduc Date 2018-10-10 Time 13:22 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-09-14 Cont ID  
Sent By pleduc Date 2018-09-14 Time   Rev Time 0.00
Received By pleduc Date 2018-09-14 Time 10:50 Sent To B
Notes
2018-09-14 11:05:00THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE ARE INDICATIONS OF CONSTRUCTION TRAILERS ON
 THE PLAN, WITH NO SIZE DIMENSIONS OR SEPARATION
 DIMENSIONS BETWEEN THEM OF THE PROPOSED BUILDING.
  
 THE PROPOSED PROJECT SHALL COMPLY WITH THE FLORIDA FIRE
 PREVENTION CODE WHICH INCLUDES NFPA 241, STANDARD FOR
 SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION
 OPERATIONS, 2013 EDITION
  
 PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS; TABLE
 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE
 REQUIRED IN EACH TRAILER.
 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER
 CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH
 AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER
 FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS
 HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE
 IN ACCORDANCE WITH TABLE 4.2.1.
  
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 NOTES:
 (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY
 STRUCTURES IS LESS THAN THE MINIMUM SEPARATION
 DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE
 CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING
 WALL LENGTHS OF THE TEMPORARY STRUCTURES.
 (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES
 SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
 (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL
 STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO
 MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE
 APPLYING THIS TABLE, IS 3600 MM (144 IN.).
  
 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES,
 ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND
 PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
  
  
 PLEASE PROVIDE FOR THE INDICATED REQUIRMENTS OR
 SPRINKLER THEM FOR A 75% REDUCTION IN SEPARATION
 DISTANCES.
  
  
  
 2) THERE ARE TWO ACCESS GATES INDICATED. THESE GATES
 SHALL PROVIDE THE REQUIRED OPENING DISTANCE FOR FIRE
 APPARATUS.
  
 THE ACCESS ROAD IS THE ONLY TRAVEL LANE THROUGH THE
 SITE AND IS REQUIRED TO BE A FIRE LANE.
  
 PER NFPA 1. CHAPTER 18,
  
 18.2.3 FIRE DEPARTMENT ACCESS ROADS.
 18.2.3.1 REQUIRED ACCESS.
 18.2.3.4.1 DIMENSIONS.
 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FT (6.1 M).
 18.2.3.4.1.2 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13 FT
 6 IN. (4.1 M).
  
 PLEASE PROVIDE INDICATIONS OF THE REQUIRED DIMENSION.
  
  
  
 3) FOR SECURITY AND FD ACCESS A KNOX PADLOCK IS
 STRONGLY RECOMMENDED FOR 24 HR EMERGENCY ACCESS.
  
 A GENERAL CONSTRUCTION LOCK WILL BE CUT AND SITE LEFT
 UNSECURED IF A KNOX PADLOCK IS NOT PROVIDED.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-10 Cont ID  
Sent By cpuell Date 2018-10-10 Time 15:19 Rev Time 0.00
Received By cpuell Date 2018-10-03 Time 13:09 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-25 Cont ID  
Sent By cthroop Date 2018-09-25 Time 10:51 Rev Time 0.00
Received By cthroop Date 2018-08-30 Time 11:28 Sent To  
Notes
2018-08-31 11:28:35ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2018-10-10 Cont ID  
Sent By cpuell Date 2018-10-10 Time 15:19 Rev Time 0.00
Received By llouie Date 2018-10-10 Time   Sent To FIRE
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-09-13 Cont ID  
Sent By llouie Date 2018-09-13 Time   Rev Time 0.00
Received By llouie Date 2018-09-11 Time 12:03 Sent To FIRE
Notes
2018-09-13 11:32:42** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PROVIDE A DETAIL OF THE PROPOSED CONSTRUCTION FENCE
 (I.E. HOW TALL IS THE FENCE? CHAIN LINK OR OTHER
 MATERIAL? ETC.)
  
 2.) SCREENING DETAILS SHALL BE SUBMITTED WITH THE
 TEMPORARY CONSTRUCTION FENCE PERMIT APPLICATION. WIND
 SCREENING SHALL BE SUBSTANTIAL ENOUGH TO AVOID TEARS
 DUE TO WIND OR SUN AND SHALL HAVE NO LESS THAN 85%
 OPACITY.
  
 3.) THE SITE PLAN SHOWS MATERIAL CONTAINERS ON THE
 SITE. A SEPARATE PERMIT IS REQUIRED FOR THESE
 CONTAINERS AND SHALL BE REMOVED FROM THE SITE PLAN FOR
 THE CONSTRUCTION FENCE.
  
  
 NOTES:
  
 * CONSTRUCTION FENCE SHALL BE MAINTAINED IN A
 SATISFACTORY MANNER DURING THE ENTIRE CONSTRUCTION
 PERIOD.
  
 * GATES SHALL BE CHAINED AND LOCKED WITH A LOCK
 SUBSTANTIAL ENOUGH TO ENSURE CLOSURE AND SECURITY WHEN
 WORKERS ARE NOT ON THE JOB SITE.
  
 * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: RPD (GEORGIAN GARDENS APTS.)