| 2018-09-14 11:05:00 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) THERE ARE INDICATIONS OF CONSTRUCTION TRAILERS ON |
| | THE PLAN, WITH NO SIZE DIMENSIONS OR SEPARATION |
| | DIMENSIONS BETWEEN THEM OF THE PROPOSED BUILDING. |
| | |
| | THE PROPOSED PROJECT SHALL COMPLY WITH THE FLORIDA FIRE |
| | PREVENTION CODE WHICH INCLUDES NFPA 241, STANDARD FOR |
| | SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION |
| | OPERATIONS, 2013 EDITION |
| | |
| | PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS; TABLE |
| | 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE |
| | REQUIRED IN EACH TRAILER. |
| | 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER |
| | CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH |
| | AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER |
| | FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS |
| | HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE |
| | IN ACCORDANCE WITH TABLE 4.2.1. |
| | |
| | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 30 FEET |
| | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 35 FEET |
| | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 40 FEET |
| | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 45 FEET |
| | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 50 FEET |
| | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE |
| | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET |
| | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL |
| | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC |
| | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. |
| | |
| | NOTES: |
| | (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY |
| | STRUCTURES IS LESS THAN THE MINIMUM SEPARATION |
| | DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE |
| | CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING |
| | WALL LENGTHS OF THE TEMPORARY STRUCTURES. |
| | (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES |
| | SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC |
| | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. |
| | (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL |
| | STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO |
| | MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE |
| | APPLYING THIS TABLE, IS 3600 MM (144 IN.). |
| | |
| | 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES, |
| | ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND |
| | PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE |
| | AUTHORITY HAVING JURISDICTION. |
| | |
| | |
| | PLEASE PROVIDE FOR THE INDICATED REQUIRMENTS OR |
| | SPRINKLER THEM FOR A 75% REDUCTION IN SEPARATION |
| | DISTANCES. |
| | |
| | |
| | |
| | 2) THERE ARE TWO ACCESS GATES INDICATED. THESE GATES |
| | SHALL PROVIDE THE REQUIRED OPENING DISTANCE FOR FIRE |
| | APPARATUS. |
| | |
| | THE ACCESS ROAD IS THE ONLY TRAVEL LANE THROUGH THE |
| | SITE AND IS REQUIRED TO BE A FIRE LANE. |
| | |
| | PER NFPA 1. CHAPTER 18, |
| | |
| | 18.2.3 FIRE DEPARTMENT ACCESS ROADS. |
| | 18.2.3.1 REQUIRED ACCESS. |
| | 18.2.3.4.1 DIMENSIONS. |
| | 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN |
| | UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FT (6.1 M). |
| | 18.2.3.4.1.2 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN |
| | UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13 FT |
| | 6 IN. (4.1 M). |
| | |
| | PLEASE PROVIDE INDICATIONS OF THE REQUIRED DIMENSION. |
| | |
| | |
| | |
| | 3) FOR SECURITY AND FD ACCESS A KNOX PADLOCK IS |
| | STRONGLY RECOMMENDED FOR 24 HR EMERGENCY ACCESS. |
| | |
| | A GENERAL CONSTRUCTION LOCK WILL BE CUT AND SITE LEFT |
| | UNSECURED IF A KNOX PADLOCK IS NOT PROVIDED. |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |