Plan Review Details - Permit 18081512
Plan Review Stops For Permit 18081512
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-02-27 Cont ID  
Sent By shill Date 2019-02-27 Time 14:03 Rev Time 0.00
Received By shill Date 2019-02-27 Time 14:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-02-16 Cont ID  
Sent By jduprey Date 2019-02-16 Time 12:29 Rev Time 0.00
Received By shill Date 2019-02-16 Time 12:29 Sent To  
Notes
2019-02-16 12:33:11****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1.PROVISO: GENERATOR ATTACHMENT IS DELEGATED
 ENGINEERING PER SEOR. THIS IS REQUIRED TO BE SUBMITTED
 AS A REVISION, AND REVIEWED, PRIOR TO FIRST INSPECTION.
 DELEGATED ENGINEERING TO BE REVIEWED BY SEOR PRIOR TO
 SUBMITTAL TO THE CITY.
  
 2. FBC 1609.1, SHEET S002 1060 2.3 DECLARES EXPOSURE C;
 PLEASE PROVIDE JUSTIFICATION FOR C RATHER THAN D IN THE
 RESPONSE LETTER.
  
 3RD REVIEW; THIS WAS REVIEWED PRELIMINARILY VIA EMAIL.
 A REQUEST WAS MADE FOR ENGINEER TO EVALUATE THE
 CONDITION TO THE SOUTHEAST. ONLY THE NORTHEAST WAS
 ADDRESSED.
  
 THIS MAY BE SENT VIA EMAIL IN A DIGITALLY SIGNED
 LETTER.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-12-27 Cont ID  
Sent By shill Date 2018-12-27 Time 18:35 Rev Time 0.00
Received By shill Date 2018-12-27 Time 18:35 Sent To  
Notes
2018-12-27 18:36:05****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. PREVIOUS COMMENT LIST REQUESTED GENERATOR ATTACHMENT
 DETAILS. DETAIL 5 ON SHEET S201 REFERS TO SPACING PER
 MANUFACTURER SPECS. MANUFACTURER SPECS WERE NOT
 PROVIDED.
  
 PLEASE NOTE THAT IF THE MANUFACTURER SPECS ARE USED TO
 SHOW RESISTANCE TO WIND LOADS, THEY ARE TO BE PREPARED
 BY A FLORIDA PE AND BE SIGNED AND SEALED. THIS WOULD BE
 CONSIDERED DELEGATED ENGINEERING AND AS SUCH SHOULD BE
 REVIEWED BY SEOR PRIOR TO SUBMITTAL. THE DELEGATED
 ENGINEERING SHOULD INCLUDE THE SEOR'S WIND DESIGN
 CRITERIA SO COMPLIANCE IS CLEAR.
  
 2. FBC 1609.1, SHEET S002 1060 2.3 DECLARES EXPOSURE C;
 PLEASE PROVIDE JUSTIFICATION FOR C RATHER THAN D IN THE
 RESPONSE LETTER.
  
 3. SHEET S002 REFERS TO AN OUTDATED CODE, 1060 ITEM 1
 (FBC 2014). REVISE AND CHECK ALL.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-04 Cont ID  
Sent By cthroop Date 2018-10-04 Time 14:01 Rev Time 0.00
Received By cthroop Date 2018-10-04 Time 10:42 Sent To  
Notes
2018-10-04 14:03:39BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. NOA FOR STEEL DOOR TO BE REVIEWED BY DESIGNER OF
 RECORD.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE DOOR SUBMITTALS.
  
 2. ELECTRICAL SUB-PERMIT REQUIRED.
  
 3. PROVIDE THE MANUFACTURERS INSTALLATION INSTRUCTIONS
 THE PROPOSED GENERATORS. DETAIL OF GENERATOR TO
 FOUNDATION REQUIRED.
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-03-04 Cont ID  
Sent By jleahy Date 2019-03-04 Time 07:48 Rev Time 0.00
Received By jleahy Date 2019-03-04 Time 07:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-02-01 Cont ID  
Sent By jleahy Date 2019-02-01 Time 10:20 Rev Time 0.00
Received By jleahy Date 2019-02-01 Time 10:20 Sent To  
Notes
2019-02-01 11:58:36FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLEASE INDICATE THE TOTAL VALUE FOR THE WORK INVOLVED.
  
 PLEASE SUBMIT A CONTRACT SIGNED BY THE "CUSTOMER" NOT
 THE MANUFACTURER AND CONTRACTOR.
  
 $585,000 WOULD SEEM TO COVER THE GENERATORS AND
 ENCLOSURES BUT NOT THE REMAINDER OF THE WORK, SITE
 WORK, ELECTRICAL SWITCH GEAR, CONDUCTORS, ECT, ECT.
  
 109.3BUILDING PERMIT VALUATIONS.
 THE APPLICANT FOR A PERMIT SHALL PROVIDE AN ESTIMATED
 PERMIT VALUE AT TIME OF APPLICATION. PERMIT VALUATIONS
 SHALL INCLUDE TOTAL VALUE OF WORK, INCLUDING MATERIALS
 AND LABOR, FOR WHICH THE PERMIT IS BEING ISSUED, SUCH
 AS ELECTRICAL, GAS, MECHANICAL, PLUMBING EQUIPMENT AND
 PERMANENT SYSTEMS. IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE VALUATION IS UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE
 APPLICANT CAN SHOW DETAILED ESTIMATES TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FINAL BUILDING
 PERMIT VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-12-04 Cont ID  
Sent By jleahy Date 2018-12-04 Time 11:22 Rev Time 0.00
Received By jleahy Date 2018-12-04 Time 11:22 Sent To  
Notes
2018-12-04 11:26:42FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 VALUE FOR THE JOB STILL NEEDS TO RESOLVED, PLEASE
 SUBMIT SIGNED COPY OF THE CONTRACT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-27 Cont ID  
Sent By jleahy Date 2018-09-26 Time 11:37 Rev Time 0.00
Received By jleahy Date 2018-09-26 Time 11:37 Sent To  
Notes
2018-09-26 12:42:13FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PERMIT CAN NOT BE ISSUED TO A CGC WITHOUT AN ELECTRICAL
 SUB-PERMIT
  
 #1
 GSB HAS 1600A BREAKER
 ATS-2 HAS A 3000A BREAKER
  
 240.87 ARC ENERGY REDUCTION
 WHERE THE HIGHEST CONTINUOUS CURRENT TRIP SETTING FOR
 WHICH THE
 ACTUAL OVERCURRENT DEVICE INSTALLED IN A CIRCUIT
 BREAKER IS RATED
 OR CAN BE ADJUSTED IS 1200 A OR HIGHER, 240.87(A) AND
 (B) SHALL
 APPLY.
 (A) DOCUMENTATION. DOCUMENTATION SHALL BE AVAILABLE TO
 THOSE
 AUTHORIZED TO DESIGN, INSTA LL, OPERATE, OR INSPECT THE
 INSTALLATION
 AS TO THE LOCATION OF THE CIRCUIT BREAKER(S).
  
 #2
 VALUE TO LOW FOR PROPOSED WORK.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE
 CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET
 BY THE BUILDING OFFICIAL.
  
 #3
 SUBMIT CUT SHEETS ON PANEL GSB, ATS #1, #2, MAIN LSI,
 EMERGENCY MAIN. GENERATORS.
  
 #4
 800A MAIN LSI IS NOT GROUPED WITH ATS-1 MAIN
 200A EMERGENCY MAIN IS NOT GROUPED WITH ATS-2 MAIN.
  
 #5
 250.64 GROUNDING ELECTRODE CONDUCTOR INSTALLATION
 (A) ALUMINUM OR CO PPER-CLAD ALUMINUM CONDUCTORS.
 BARE ALUMINUM OR COPPER-CLAD ALUMINUM GROUNDING
 ELECTRODE
 CONDUCTORS SHALL NOT BE USED WHERE IN DIRECT CONTACT
 WITH MASONRY
 OR THE EARTH OR WHERE SUBJECT TO CORROSIVE CONDITIONS.
 WHERE
 USED OUTSIDE, ALUMINUM OR COPPER-CLAD ALUMINUM
 GROUNDING
 ELECTRODE CONDUCTORS SHALL NOT BE TERMINATED WITHIN 450
 MM
 (18 IN.) OF THE EARTH.
  
 #6
 WIRE AND CONDUIT SCHEDULE #9 SHOWS A 2/0 WHICH SHOULD
 BE 4/0
  
 #7
 PROVIDE FPL MAXIMUM DEMAND FOR THE SERVICE RECORDS FOR
 THE MAINS LOAD CALCULATION.
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-11-26 Cont ID  
Sent By scaldero Date 2018-11-26 Time 10:00 Rev Time 0.00
Received By scaldero Date 2018-11-26 Time 09:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-09-18 Cont ID  
Sent By scaldero Date 2018-09-18 Time 13:29 Rev Time 0.00
Received By scaldero Date 2018-09-18 Time 12:43 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2019-02-19 Cont ID  
Sent By gjohnson Date 2019-02-19 Time 09:24 Rev Time 0.00
Received By gjohnson Date 2019-02-19 Time 08:06 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-12-28 Cont ID  
Sent By gjohnson Date 2018-12-28 Time 12:18 Rev Time 0.00
Received By gjohnson Date 2018-12-28 Time 12:18 Sent To  
Notes
2018-12-28 12:30:372ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PREVIOUS GAS COMMENTS: NOT COMPLIED 2ND REQUEST.
  
 1. PROVIDE MANUFACTURE SPECIFICATION AND INSTALLATION
 GUIDES FOR GENERATOR, REGULATORS, SUCTION AND RETURN
 PUMPS, THE DUAL WALL PIPING WITH LEAK DETECTION,
 GEOFLEX PIPING, AND ANY NEW EQUIPMENT ON THE FUEL TANK
 SUCH AS THE ANTI SIPHON VALVE AND FOOT VALVE. PER WPB
 AMEND TO FBC 107.2.1
 IN THE RESPONSE LETTER IT STATED THAT MANUFACTURE SPEC
 WILL BE SUPPLIED IN SUBMITTAL PHASE THIS REVIEW IS
 CONSIDERED THE SUBMITTAL PHASE AND IT WILL BE REQUIRED
 TO SUBMIT THE DOCUMENTATION TO VERIFY CODE COMPLIANCE.
  
 2. COMPLIED
  
 3. ON THE NATURAL GAS RISER PLEASE SHOW THE FOLLOWING:
 A) COMPLIED
 B) COMPLIED
 C) COMPLIED
 D) SHOW DISTANCE AND SIZE OF PIPE FROM REGULATOR TO THE
 GENERATOR.
 E) COMPLIED
 PER WPB AMEND TO FBC 107.2.1
  
 4. COMPLIED
  
 5. COMPLIED
  
 NEW COMMENT:
  
 1. THE FIRST SECTION OF PIPE AFTER THE METER SHALL BE
 3" TO SUPPLY THE EXISTING LOAD AND THE NEW LOAD
 COMBINED. PER FBC FG TABLE 402.4(5)
  
 2. PLEASE PLACE NOTE ON PLAN. CITY OF WEST PALM BEACH
 GAS PIPING AFFIDAVIT OR MANOMETER TEST DOCUMENT
 REQUIRED AT JOBSITE FOR FINAL INSPECTION.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-10-03 Cont ID  
Sent By gjohnson Date 2018-10-03 Time 15:20 Rev Time 0.00
Received By gjohnson Date 2018-10-03 Time 10:29 Sent To  
Notes
2018-10-03 17:15:391ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE MANUFACTURE SPECIFICATION AND INSTALLATION
 GUIDES FOR GENERATOR, REGULATORS, SUCTION AND RETURN
 PUMPS, THE DUAL WALL PIPING WITH LEAK DETECTION,
 GEOFLEX PIPING, AND ANY NEW EQUIPMENT ON THE FUEL TANK
 SUCH AS THE ANTI SIPHON VALVE AND FOOT VALVE. PER WPB
 AMEND TO FBC 107.2.1
  
 2. PLEASE SHOW THE EXISTING BTU LOAD ON THE EXISTING
 PIPE. PER WPB AMEND TO FBC 107.2.1
  
 3. ON THE NATURAL GAS RISER PLEASE SHOW THE FOLLOWING:
 A) THE FURTHEST DISTANCE FROM THE METER TO THE LAST
 GENERATOR.
 B) SHOW THE BRANCHES FOR ALL 3 GENERATORS.
 C) INDICATE SYSTEM PRESSURE.
 D) SHOW DISTANCE AND SIZE OF PIPE FROM REGULATOR TO THE
 GENERATOR.
 E) INDICATE BTU LOAD ON EACH GENERATOR.
 PER WPB AMEND TO FBC 107.2.1
 4. PLEASE NOTE ON THE PLAN THE SIZING TABLE USED FROM
 FBC FG 402.4
  
 5. EXPOSED PIPING SHALL BE LABELED AS NATURAL GAS OR
 DIESEL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-03-05 Cont ID  
Sent By shill Date 2019-03-05 Time 08:28 Rev Time 0.00
Received By shill Date 2019-03-04 Time 10:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-02-19 Cont ID  
Sent By gjohnson Date 2019-02-19 Time 09:24 Rev Time 0.00
Received By gjohnson Date 2019-01-17 Time 08:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-28 Cont ID  
Sent By gjohnson Date 2018-12-28 Time 12:30 Rev Time 0.00
Received By gjohnson Date 2018-11-20 Time 15:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-16 Cont ID  
Sent By lmarchan Date 2018-10-16 Time 15:40 Rev Time 0.00
Received By lmarchan Date 2018-09-17 Time 10:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2019-02-19 Cont ID  
Sent By gjohnson Date 2019-02-19 Time 08:06 Rev Time 0.00
Received By gjohnson Date 2019-02-19 Time 08:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2018-12-28 Cont ID  
Sent By gjohnson Date 2018-12-28 Time 12:16 Rev Time 0.00
Received By gjohnson Date 2018-12-28 Time 12:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2019-03-05 Cont ID  
Sent By shill Date 2019-03-05 Time 08:28 Rev Time 0.00
Received By shill Date 2019-03-05 Time 08:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2019-02-16 Cont ID  
Sent By shill Date 2019-02-16 Time 12:34 Rev Time 0.00
Received By shill Date 2019-02-16 Time 12:34 Sent To  
Notes
2019-02-16 12:34:42DIGITALLY SIGNATURES OK
 NEW SHEETS SUBMITTED NEXT REVIEW CYCLE REQUIRE REVIEW
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-12-27 Cont ID  
Sent By shill Date 2018-12-27 Time 18:59 Rev Time 0.00
Received By shill Date 2018-12-27 Time 18:59 Sent To  
Notes
2018-12-27 18:59:47SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 G001 IS NOT DIGITALLY SIGNED
 A121 IS NOT DIGITALLY SIGNED
 S, E, P SHEETS OK
 NEW SHEETS SUBMITTED NEXT REVIEW CYCLE REQUIRE
 VERIFICATION
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-10-04 Cont ID  
Sent By cthroop Date 2018-10-04 Time 14:03 Rev Time 0.00
Received By cthroop Date 2018-10-04 Time 10:42 Sent To  
Notes
2018-10-04 14:06:16BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THE SIGNATURE AND SEAL OF THE DESIGNER OF RECORD IS
 INVALID FOR THE FOLLOWING PLAN PAGES:
 A. G-001
 B. A-121
 C. CIVIL PAGES 1 AND 2
  
 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2019-03-01 Cont ID  
Sent By aaponte Date 2019-01-25 Time 09:06 Rev Time 0.00
Received By aaponte Date 2019-01-25 Time 09:06 Sent To  
Notes
2019-01-25 09:19:00PROVISO: PROPOSED GENERATOR WILL REMOVE FOUR EXISTING
 PARKING SPACES. PLEASE INCLUDE INFORMATION INDICATING
 WHERE THE PARKING SPACES ARE GOING TO BE RELOCATED, OR
 PROVIDE A PARKIGN CALCULATION TO DEMONSTRATE THE FOUR
 SPACES WERE NOT MINIMUM REQUIRED PARKING.CALCULATION
 SHALL BE PROVIDED AND SUBMITTED AS A REVISION FOR
 APPROVAL BEFORE FINAL CERTIFICATE OF COMPLETION.

Review Stop Z ZONING
Rev No 2 Status P Date 2018-12-18 Cont ID  
Sent By elevesqu Date 2018-12-18 Time 10:17 Rev Time 0.00
Received By elevesqu Date 2018-12-18 Time 10:17 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-10-16 Cont ID  
Sent By aaponte Date 2018-10-16 Time 15:21 Rev Time 0.00
Received By aaponte Date 2018-10-16 Time 15:21 Sent To  
Notes
***NONE***