Plan Review Details - Permit 18081507
Plan Review Stops For Permit 18081507
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-11-29 Cont ID  
Sent By dbattles Date 2018-11-29 Time 14:02 Rev Time 0.00
Received By dbattles Date 2018-11-29 Time 14:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-24 Cont ID  
Sent By dbattles Date 2018-10-24 Time 15:50 Rev Time 0.00
Received By dbattles Date 2018-10-24 Time 11:02 Sent To  
Notes
2018-10-24 15:55:06****CORRECTIONS****
 W.P.B. PERMIT: 18081507
 REVIEWED: OCTOBER 24, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
  
 1. [FBC AMENDED 109]VALUE OF PROJECT SEEMS LOW AT
 $22,500.00. PLEASE INCLUDE VALUE FOR ALL WORK BEING
 PERFOMED.
  
 2. [FBC EB301.1]WHICH METHOD IS BEING USED FOR
 COMPLIANCE? (PRESCRIPTIVE,WORK AREA OR PERFORMANCE)
  
 3. [FBC EB501]WHAT IS THE CLASSIFICATION OF NEW WORK?
 WHAT WAS THE OCCUPANCY OF THIS SPACE?
 WHAT ARE OCCUPANCIES OF ADJACENT SPACES?
  
 4. [FBC C503.2]CHANGE IN SPACE CONDITIONING
 HOW IS THERMAL ENVELOPE MAINTAINED IN BUSINESS AREA? IS
 THE DISPATCH AREA AND STORAGE AREA BEING COOLED?
  
 5. [FBC 1013.1 ]WHERE REQUIRED.
 EXITS AND EXIT ACCESS DOORS SHALL BE MARKED BY AN
 APPROVED EXIT SIGN READILY VISIBLE FROM ANY DIRECTION
 OF EGRESS TRAVEL. THE PATH OF EGRESS TRAVEL TO EXITS
 AND WITHIN EXITS SHALL BE MARKED BY READILY VISIBLE
 EXIT SIGNS TO CLEARLY INDICATE THE DIRECTION OF EGRESS
 TRAVEL IN CASES WHERE THE EXIT OR THE PATH OF EGRESS
 TRAVEL IS NOT IMMEDIATELY VISIBLE TO THE OCCUPANTS.
 INTERVENING MEANS OF EGRESS DOORS WITHIN EXITS SHALL BE
 MARKED BY EXIT SIGNS. EXIT SIGN PLACEMENT SHALL BE SUCH
 THAT NO POINT IN AN EXIT ACCESS CORRIDOR OR EXIT
 PASSAGEWAY IS MORE THAN 100 FEET (30 480 MM) OR THE
 LISTED VIEWING DISTANCE FOR THE SIGN, WHICHEVER IS
 LESS, FROM THE NEAREST VISIBLE EXIT SIGN.
 THE EXIT SIGN AT S.W. LOADING DOCK WOULD NOT BE VISIBLE
 WITH STORAGE CRATES. PROVIDE INTERMEDIATE SIGN VISABLE
 FROM AISLEWAY.
 ALSO, THE EXIT SIGN IN STORAGE THAT LEADS INTO
 ACCOUNTS, BUT THEN THERE IS NO EXIT SIGN IN ACCOUNTS.
  
 6. [FBC A403.2]SEPARATE FACILITIES
 LABEL THE EXISTING BATHROOMS FOR MEN AND WOMEN.
  
 7. [FBC A604.3]CLEARANCE
 SHOW ADA CLEARANCES AT BATHROOM FIXTURES.
  
 8. [FBC A206.1]GENERAL.
 ACCESSIBLE ROUTES SHALL BE PROVIDED IN ACCORDANCE WITH
 206 AND SHALL COMPLY WITH CHAPTER 4.
 SHOW ACCESSIBLE PATH FROM PARKING TO ACCESSIBLE ENTRY.
  
 9.[FBC 1604.1] PROVIDE DETAIL OF NEW 3 HR ROLL UP DOORS
 COLUMS TO PICK UP LOAD FROM STEEL ANGLES.
 PROVIDE DETAIL OF FOOTING SUPPORT OF NEW 4X4 STEEL
 POSTS AT DISPATCH AREA.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-02-13 Cont ID  
Sent By jpearson Date 2019-02-13 Time 13:22 Rev Time 0.00
Received By jpearson Date 2019-02-13 Time 13:22 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-11-30 Cont ID  
Sent By jpearson Date 2018-11-30 Time 15:55 Rev Time 0.00
Received By jpearson Date 2018-11-30 Time 15:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-02 Cont ID  
Sent By jpearson Date 2018-10-02 Time 10:52 Rev Time 0.00
Received By jpearson Date 2018-10-02 Time 10:26 Sent To  
Notes
2018-10-02 10:37:15CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). NEC 215.5, 230, 408.30; WPB FBC 107.2.1
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4
 3. PROVIDE GFCI PROTECTION FOR VENDING MACHINES. THE
 GFCI DEVICE MUST BE READILY ACCESSIBLE. NEC 422.5,
 422.51
 4. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
 5. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-11-20 Cont ID  
Sent By pleduc Date 2018-11-20 Time   Rev Time 0.00
Received By pleduc Date 2018-11-20 Time 12:53 Sent To  
Notes
2018-11-20 13:08:21THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET LS 1 - AN EXIT SIGN IS INDICATED WITHIN A
 CLOUD IN THE ACCOUNTING ROMM LEADING INTO THE STORAGE
 AREA. THIS EXIT IS NOT REQUIRED, ADDITIONALLY, AN EXIT
 FROM AN AREA OF LOWER HAZARD CAN NTO EXIT INTO AN AREA
 OF HIGHER HAZARD.
  
 PLEAE OMIT THIS EXIT SIGN.
  
 7.5.1.6 EXIT ACCESS FROM ROOMS OR SPACES SHALL BE
 PERMITTED TO BE THROUGH ADJOINING OR INTERVENING ROOMS
 OR AREAS, PROVIDED THAT SUCH ROOMS OR AREAS ARE
 ACCESSORY TO THE AREA SERVED. FOYERS, LOBBIES, AND
 RECEPTION ROOMS CONSTRUCTED AS REQUIRED FOR CORRIDORS
 SHALL NOT BE CONSTRUED AS INTERVENING ROOMS. EXIT
 ACCESS SHALL BE ARRANGED SO THAT IT IS NOT NECESSARY TO
 PASS THROUGH ANY AREA IDENTIFIED UNDER PROTECTION FROM
 HAZARDS IN CHAPTERS 11 THROUGH 43.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-09-05 Cont ID  
Sent By pleduc Date 2018-09-05 Time   Rev Time 0.00
Received By pleduc Date 2018-09-05 Time 13:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2019-02-15 Time   Rev Time 0.00
Received By lmarchan Date 2019-02-07 Time 13:59 Sent To  
Notes
2019-02-08 14:00:00RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-01-15 Time   Rev Time 0.00
Received By skennedy Date 2019-01-09 Time 09:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-17 Cont ID  
Sent By gjohnson Date 2018-12-17 Time 11:01 Rev Time 0.00
Received By gjohnson Date 2018-11-13 Time 13:03 Sent To  
Notes
2018-11-14 13:03:17C11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-24 Cont ID  
Sent By dbattles Date 2018-10-24 Time 15:56 Rev Time 0.00
Received By dbattles Date 2018-08-30 Time 15:01 Sent To  
Notes
2018-08-31 15:02:06C10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-11-29 Cont ID  
Sent By dbattles Date 2018-11-29 Time 14:15 Rev Time 0.00
Received By dbattles Date 2018-11-29 Time 14:15 Sent To  
Notes
2018-11-29 14:16:57PLANS HAVE BEEN STAMPED BY PBC ON 10/26/18
 DB CALLED MR. SWOOPE ON 11/29/18 TO ASK IF THERE WAS AN
 MU #.
 HE STATED THAT THEY DID NOT PRODUCE ONE FOR THIS
 PROJECT AND ZERO FEES WERE DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-10-24 Cont ID  
Sent By dbattles Date 2018-10-24 Time 15:55 Rev Time 0.00
Received By dbattles Date 2018-10-24 Time 15:55 Sent To  
Notes
2018-10-24 15:56:25IMPACT FEE REVIEW BY PBC REQUIRED FOR CHANGE OF
 OCCUPANCY
  
 [FBC AMENDED 109]PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2019-02-15 Cont ID  
Sent By ccole Date 2019-02-15 Time 12:48 Rev Time 0.00
Received By ccole Date 2019-02-15 Time 12:48 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-01-15 Cont ID  
Sent By ccole Date 2019-01-15 Time 16:30 Rev Time 0.00
Received By ccole Date 2019-01-15 Time 16:26 Sent To I
Notes
2019-01-15 16:31:463RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18081507
 11/28/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED
  
 1) THE PREVIOUS MECHANICAL PLANS SUBMITTEF BY STEVEN J.
 BRUH HAVE BEEN REMOVED. THE NEW M-1 PLAN SHEET BEARS
 THE TITLE BLOCK OF THE ARCHITECT, HOWEVER THE PLAN DOES
 NOT BEAR HIS SIGNATURE AND SEAL WHICH IS REQUIRED BY
 FL. STATUTE AND SECTION 61G15-16.003 FAC. IF KYSAR AC,
 WHOSE TITLE BLOCK ALSO APPEARS ON THE PLAN, IS THE NEW
 MECHANCIAL DESIGNER OF RECORD, HE CANNOT USE THE
 ARCHITECT'S PLAN WHICH HAS ARCHITECTURAL AND ELECTRICAL
 DETAILS AND NOTES THAT ARE BEYOND HIS SCOPE. KYSAR MUST
 PROVIDE A SEPARATE, CLEAR, LEGIBLE PLAN FOR REVIEW THAT
 ADDRESSES ALL PREVIOUS REVIEW COMMENTS CONCERNING THE
 MECHANICAL ALTERATIONS- SEE COMMENTS BELOW.
  
 A) REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3.1 FBC-17 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 B) PROVIDE A DUCT LAYOUT PLAN SHOWING THE REQUIRED
 ALTERATIONS TO THE EXISTING SYSTEMS TO ACCOMODATE THE
 NEW ROOMS AND SPACES WITH BALANCED AIR CONDITIONING-
 SECTION 603.1 FBC M.
  
 C) PROVIDE AN AIR DEVICE SCHEDULE.
  
 2) THE ARCHITECT OF RECORD STEVEN BRUH HAS ADDRESSED
 OTHER COMMENTS FROM THE 1ST REVIEW IN A RESPONSE
 NARRATIVE, HOWEVER HIS RESPONSES MUST BE APPLIED TO
 SIGNED AND SEALED PLANS THAT WILL BE APPROVED FOR
 INSPECTION, AND FOR PUBLIC RECORD- SEE COMMENTS BELOW
  
 A) EXHAUST VENTILATION CALCULATIONS FOR THE DISPATCH
 AND LOADING AREAS. PLEASE REVIEW SECTION 406 AND
 IDENTIFY IF THE AREAS IN QUESTION ARE TO BE CLASSIFIED
 AS PRIVATE OR PUBLIC GARAGES. IN EITHER CASE EXHAUST
 VENTILATION SYSTEMS SIZED AT A RATE OF 0.75 CFMS PER
 SF. WILL BE REQUIRED- TABLE 403.3.1.1 FBC M. (SEE SHEET
 A-1: THE PLANS SHOW OVERHEAD DOORS AT GRADE LEVEL IN
 THESE AREAS WHICH ALLOWS FOR VEHICLES TO DRIVE IN AND
 OUT, AND ALSO BE PARKED).
  
 B) CLARIFY THE USE OF THE CHARGING STATION SHOWN IN THE
 WAREHOUSE OF SHEET EP-1. PLEASE NOTE THAT AN EXHAUST
 VENTILATION SYSTEM IS REQUIRED FOR BATTERY CHARGING
 AREAS PER SECTIONS 502.3- 502.5.3 FBC M. (THE ARCHITECT
 HAS INDICATED CELL PHONE CHARGING AND NOT BATTERY
 CHARGING FOR FORKLIFTS IN THIS AREA. THE ARCHITECT MUST
 INDICATE THAT ON THE PLAN, OTHERWISE PROVIDE THE
 REQUIRED EXHAUST VENTILATION IN THIS AREA).
  
 C) PROVIDE THE LEVEL OF ALTERATION FOR THE PROPOSED
 PROJECT- SEE CHAPTER 5 FBC EX AND DETERMINE IF THE
 PROJECT IS A LEVEL 1, 2, OR 3 ALTERATION OR A CHANGE OF
 OCCUPANCY.
  
 D) SHOW HOW THE WAREHOUSE IS BEING VENTILATED AND WHAT
 MATERIALS ARE BEING STORED THERE- SEE SECTIONS 401.2,
 402.1 AND TABLE 403.3.1.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-11-28 Cont ID  
Sent By ccole Date 2018-11-28 Time 14:40 Rev Time 0.00
Received By ccole Date 2018-11-28 Time 14:40 Sent To  
Notes
2018-11-28 16:05:362ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18081507
 11/28/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED
  
 SOME OF THE 1ST REVIEW COMMENTS LISTED BELOW HAVE NOT
 BEEN ADDRESSED COMPLETELY. PLEASE COMPLY
  
 1) REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3.1 FBC-17 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) PROVIDE A DUCT LAYOUT PLAN SHOWING THE REQUIRED
 ALTERATIONS TO THE EXISTING SYSTEMS TO ACCOMODATE THE
 NEW ROOMS AND SPACES WITH BALANCED AIR CONDITIONING-
 SECTION 603.1 FBC M. ( SEE SHEET EP-1: SUPPLY AND
 RETURN MISSING FROM SOME OF THE NEW ROOMS BEING
 CONSTRUCTED).
  
 3) EXHAUST VENTILATION CALCULATIONS FOR THE DISPATCH
 AND LOADING AREAS. PLEASE REVIEW SECTION 406 AND
 IDENTIFY IF THE AREAS IN QUESTION ARE TO BE CLASSIFIED
 AS PRIVATE OR PUBLIC GARAGES. IN EITHER CASE EXHAUST
 VENTILATION SYSTEMS SIZED AT A RATE OF 0.75 CFMS PER
 SF. WILL BE REQUIRED- TABLE 403.3.1.1 FBC M. (SEE SHEET
 A-1: THE PLANS SHOW OVERHEAD DOORS AT GRADE LEVEL IN
 THESE AREAS WHICH ALLOWS FOR VEHICLES TO DRIVE IN AND
 OUT, AND ALSO BE PARKED).
  
 4) CLARIFY THE USE OF THE CHARGING STATION SHOWN IN THE
 WAREHOUSE OF SHEET EP-1. PLEASE NOTE THAT AN EXHAUST
 VENTILATION SYSTEM IS REQUIRED FOR BATTERY CHARGING
 AREAS PER SECTIONS 502.3- 502.5.3 FBC M. (THE ARCHITECT
 HAS INDICATED CELL PHONE CHARGING AND NOT BATTERY
 CHARGING FOR FORKLIFTS IN THIS AREA. THE ARCHITECT MUST
 INDICATE THAT ON THE PLAN, OTHERWISE PROVIDE THE
 REQUIRED EXHAUST VENTILATION IN THIS AREA).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-10-10 Cont ID  
Sent By ccole Date 2018-10-10 Time 17:16 Rev Time 0.00
Received By ccole Date 2018-10-10 Time 17:16 Sent To  
Notes
2018-10-10 17:45:531ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18081507
 10/10/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NO MECHANICAL PLANS WERE SUBMITTED FOR THIS
 ALTERATION PROJECT EXCEPT A NOTE AND A DETAIL ON SHEET
 EP-1 ADDRESSING THE RELOCATION OF AN AHU AND HOW IT
 WILL BE SUPPORTED ABOVE THE CEILING. PLEASE PROVIDE THE
 FOLLOWING:
  
 A) PROVIDE THE LEVEL OF ALTERATION FOR THE PROPOSED
 PROJECT- SEE CHAPTER 5 FBC EX AMD DETERMINE IF THE
 PROJECT IS A LEVEL 1, 2, OR 3 ALTERATION OR A CHANGE OF
 OCCUPANCY.
  
 B) MINIMUM VENTILATION RATES FOR ALL ROOMS AND SPACES:
 REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3.1 FBC-17 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 C) EXHAUST VENTILATION CALCULATIONS FOR THE DISPATCH
 AND LOADING AREAS. PLEASE REVIEW SECTION 406 AND
 IDENTIFY IF THE AREAS IN QUESTION ARE TO BE CLASSIFIED
 AS PRIVATE OR PUBLIC GARAGES. IN EITHER CASE EXHAUST
 VENTILATION SYSTEMS SIZED AT A RATE OF 0.75 CFMS PER
 SF. WILL BE REQUIRED- TABLE 403.3.1.1 FBC M.
  
 D) PROVIDE A DUCT LAYOUT PLAN SHOWING THE REQUIRED
 ALTERATIONS TO THE EXISTING SYSTEMS TO ACCOMODATE THE
 NEW ROOMS AND SPACES WITH BALANCED AIR CONDITIONING-
 SECTION 603.1 FBC M.
  
 E) PROVIDE AN AIR DEVICE SCHEDULE.
  
 F) SHOW HOW THE WAREHOUSE IS BEING VENTILATED AND WHAT
 MATERIALS ARE BEING STORED THERE- SEE SECTIONS 401.2,
 402.1 AND TABLE 403.3.1.1.
  
 G) CLARIFY THE USE OF THE CHARGING STATION SHOWN IN THE
 WAREHOUSE OF SHEET EP-1. PLEASE NOTE THAT AN EXHAUST
 VENTILATION SYSTEM IS REQUIRED FOR BATTERY CHARGING
 AREAS PER SECTIONS 502.3- 502.5.3 FBC M.
  
  
 PLEASE NOTE THAT DUE TO THE LACK OF MECHANICAL PLANS
 THERE MAY BE ADDITIONAL COMMENTS WHEN COMPLETE PLANS
 AND CALCULATIONS ARE SUBMITTED.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-12-17 Cont ID  
Sent By gjohnson Date 2018-12-17 Time 11:00 Rev Time 0.00
Received By gjohnson Date 2018-12-17 Time 11:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-10-16 Cont ID  
Sent By gjohnson Date 2018-10-16 Time 07:11 Rev Time 0.00
Received By gjohnson Date 2018-10-15 Time 16:45 Sent To  
Notes
2018-10-16 07:19:441ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. A SERVICE SINK IS REQUIRED PLEAS SHOW LOCATION THE
 PLAN SHOW A UTILITY SINK BEING ELIMINATED IN COPIER
 ROOM #2 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
 AND FBC PL TABLE 403.1
  
 2. HOT WATER IS REQUIRED AT THE BREAKROOM SINK. PER FBC
 PL 607.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  