| Plan Review Stops For Permit 18081507 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-11-29 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-11-29 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-11-29 |
Time |
14:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-10-24 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-10-24 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-10-24 |
Time |
11:02 |
Sent To |
|
|
| Notes |
| 2018-10-24 15:55:06 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 18081507 | | | REVIEWED: OCTOBER 24, 2018 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER I | | | [email protected] | | | 561-805-6718 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC ENERGY = FBC ENERGY CONSERVATION | | | | | | 1. [FBC AMENDED 109]VALUE OF PROJECT SEEMS LOW AT | | | $22,500.00. PLEASE INCLUDE VALUE FOR ALL WORK BEING | | | PERFOMED. | | | | | | 2. [FBC EB301.1]WHICH METHOD IS BEING USED FOR | | | COMPLIANCE? (PRESCRIPTIVE,WORK AREA OR PERFORMANCE) | | | | | | 3. [FBC EB501]WHAT IS THE CLASSIFICATION OF NEW WORK? | | | WHAT WAS THE OCCUPANCY OF THIS SPACE? | | | WHAT ARE OCCUPANCIES OF ADJACENT SPACES? | | | | | | 4. [FBC C503.2]CHANGE IN SPACE CONDITIONING | | | HOW IS THERMAL ENVELOPE MAINTAINED IN BUSINESS AREA? IS | | | THE DISPATCH AREA AND STORAGE AREA BEING COOLED? | | | | | | 5. [FBC 1013.1 ]WHERE REQUIRED. | | | EXITS AND EXIT ACCESS DOORS SHALL BE MARKED BY AN | | | APPROVED EXIT SIGN READILY VISIBLE FROM ANY DIRECTION | | | OF EGRESS TRAVEL. THE PATH OF EGRESS TRAVEL TO EXITS | | | AND WITHIN EXITS SHALL BE MARKED BY READILY VISIBLE | | | EXIT SIGNS TO CLEARLY INDICATE THE DIRECTION OF EGRESS | | | TRAVEL IN CASES WHERE THE EXIT OR THE PATH OF EGRESS | | | TRAVEL IS NOT IMMEDIATELY VISIBLE TO THE OCCUPANTS. | | | INTERVENING MEANS OF EGRESS DOORS WITHIN EXITS SHALL BE | | | MARKED BY EXIT SIGNS. EXIT SIGN PLACEMENT SHALL BE SUCH | | | THAT NO POINT IN AN EXIT ACCESS CORRIDOR OR EXIT | | | PASSAGEWAY IS MORE THAN 100 FEET (30 480 MM) OR THE | | | LISTED VIEWING DISTANCE FOR THE SIGN, WHICHEVER IS | | | LESS, FROM THE NEAREST VISIBLE EXIT SIGN. | | | THE EXIT SIGN AT S.W. LOADING DOCK WOULD NOT BE VISIBLE | | | WITH STORAGE CRATES. PROVIDE INTERMEDIATE SIGN VISABLE | | | FROM AISLEWAY. | | | ALSO, THE EXIT SIGN IN STORAGE THAT LEADS INTO | | | ACCOUNTS, BUT THEN THERE IS NO EXIT SIGN IN ACCOUNTS. | | | | | | 6. [FBC A403.2]SEPARATE FACILITIES | | | LABEL THE EXISTING BATHROOMS FOR MEN AND WOMEN. | | | | | | 7. [FBC A604.3]CLEARANCE | | | SHOW ADA CLEARANCES AT BATHROOM FIXTURES. | | | | | | 8. [FBC A206.1]GENERAL. | | | ACCESSIBLE ROUTES SHALL BE PROVIDED IN ACCORDANCE WITH | | | 206 AND SHALL COMPLY WITH CHAPTER 4. | | | SHOW ACCESSIBLE PATH FROM PARKING TO ACCESSIBLE ENTRY. | | | | | | 9.[FBC 1604.1] PROVIDE DETAIL OF NEW 3 HR ROLL UP DOORS | | | COLUMS TO PICK UP LOAD FROM STEEL ANGLES. | | | PROVIDE DETAIL OF FOOTING SUPPORT OF NEW 4X4 STEEL | | | POSTS AT DISPATCH AREA. | | | | | | NOTE: | | | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW | | | OF MATERIALS REQUESTED. | | | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS | | | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | | NEED "VOID", RENDERING THEM NOT USABLE. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2019-02-13 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-02-13 |
Time |
13:22 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-02-13 |
Time |
13:22 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-11-30 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-11-30 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-11-30 |
Time |
15:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-10-02 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-10-02 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-10-02 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2018-10-02 10:37:15 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF | | | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, | | | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY | | | SUB-PANEL(S). NEC 215.5, 230, 408.30; WPB FBC 107.2.1 | | | 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | | WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, | | | 408.4 | | | 3. PROVIDE GFCI PROTECTION FOR VENDING MACHINES. THE | | | GFCI DEVICE MUST BE READILY ACCESSIBLE. NEC 422.5, | | | 422.51 | | | 4. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | | IS ADEQUATE. NEC 215.2, 220, 408.30 | | | 5. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-11-20 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-11-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-11-20 |
Time |
12:53 |
Sent To |
|
|
| Notes |
| 2018-11-20 13:08:21 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) SHEET LS 1 - AN EXIT SIGN IS INDICATED WITHIN A | | | CLOUD IN THE ACCOUNTING ROMM LEADING INTO THE STORAGE | | | AREA. THIS EXIT IS NOT REQUIRED, ADDITIONALLY, AN EXIT | | | FROM AN AREA OF LOWER HAZARD CAN NTO EXIT INTO AN AREA | | | OF HIGHER HAZARD. | | | | | | PLEAE OMIT THIS EXIT SIGN. | | | | | | 7.5.1.6 EXIT ACCESS FROM ROOMS OR SPACES SHALL BE | | | PERMITTED TO BE THROUGH ADJOINING OR INTERVENING ROOMS | | | OR AREAS, PROVIDED THAT SUCH ROOMS OR AREAS ARE | | | ACCESSORY TO THE AREA SERVED. FOYERS, LOBBIES, AND | | | RECEPTION ROOMS CONSTRUCTED AS REQUIRED FOR CORRIDORS | | | SHALL NOT BE CONSTRUED AS INTERVENING ROOMS. EXIT | | | ACCESS SHALL BE ARRANGED SO THAT IT IS NOT NECESSARY TO | | | PASS THROUGH ANY AREA IDENTIFIED UNDER PROTECTION FROM | | | HAZARDS IN CHAPTERS 11 THROUGH 43. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-09-05 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-09-05 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-09-05 |
Time |
13:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-02-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-02-07 |
Time |
13:59 |
Sent To |
|
|
| Notes |
| 2019-02-08 14:00:00 | RESUB ROUTED TO JPEARSON |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-01-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2019-01-09 |
Time |
09:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-12-17 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-12-17 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-11-13 |
Time |
13:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-10-24 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-10-24 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-08-30 |
Time |
15:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2018-11-29 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-11-29 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-11-29 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2018-11-29 14:16:57 | PLANS HAVE BEEN STAMPED BY PBC ON 10/26/18 | | | DB CALLED MR. SWOOPE ON 11/29/18 TO ASK IF THERE WAS AN | | | MU #. | | | HE STATED THAT THEY DID NOT PRODUCE ONE FOR THIS | | | PROJECT AND ZERO FEES WERE DUE. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2018-10-24 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-10-24 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-10-24 |
Time |
15:55 |
Sent To |
|
|
| Notes |
| 2018-10-24 15:56:25 | IMPACT FEE REVIEW BY PBC REQUIRED FOR CHANGE OF | | | OCCUPANCY | | | | | | [FBC AMENDED 109]PLANS REQUIRE REVIEW BY THE PBC IMPACT | | | FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY | | | CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR | | | REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE | | | RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE | | | OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO | | | V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN | | | AIRE.PDF |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2019-02-15 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-02-15 |
Time |
12:48 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-02-15 |
Time |
12:48 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2019-01-15 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-01-15 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-01-15 |
Time |
16:26 |
Sent To |
I |
|
| Notes |
| 2019-01-15 16:31:46 | 3RD REVIEW FBC-2017 MECHANICAL | | | PERMIT #18081507 | | | 11/28/18 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED | | | | | | 1) THE PREVIOUS MECHANICAL PLANS SUBMITTEF BY STEVEN J. | | | BRUH HAVE BEEN REMOVED. THE NEW M-1 PLAN SHEET BEARS | | | THE TITLE BLOCK OF THE ARCHITECT, HOWEVER THE PLAN DOES | | | NOT BEAR HIS SIGNATURE AND SEAL WHICH IS REQUIRED BY | | | FL. STATUTE AND SECTION 61G15-16.003 FAC. IF KYSAR AC, | | | WHOSE TITLE BLOCK ALSO APPEARS ON THE PLAN, IS THE NEW | | | MECHANCIAL DESIGNER OF RECORD, HE CANNOT USE THE | | | ARCHITECT'S PLAN WHICH HAS ARCHITECTURAL AND ELECTRICAL | | | DETAILS AND NOTES THAT ARE BEYOND HIS SCOPE. KYSAR MUST | | | PROVIDE A SEPARATE, CLEAR, LEGIBLE PLAN FOR REVIEW THAT | | | ADDRESSES ALL PREVIOUS REVIEW COMMENTS CONCERNING THE | | | MECHANICAL ALTERATIONS- SEE COMMENTS BELOW. | | | | | | A) REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 403.3.1 FBC-17 MECHANICAL. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED CFMS OF OUTDOOR AIR. | | | | | | B) PROVIDE A DUCT LAYOUT PLAN SHOWING THE REQUIRED | | | ALTERATIONS TO THE EXISTING SYSTEMS TO ACCOMODATE THE | | | NEW ROOMS AND SPACES WITH BALANCED AIR CONDITIONING- | | | SECTION 603.1 FBC M. | | | | | | C) PROVIDE AN AIR DEVICE SCHEDULE. | | | | | | 2) THE ARCHITECT OF RECORD STEVEN BRUH HAS ADDRESSED | | | OTHER COMMENTS FROM THE 1ST REVIEW IN A RESPONSE | | | NARRATIVE, HOWEVER HIS RESPONSES MUST BE APPLIED TO | | | SIGNED AND SEALED PLANS THAT WILL BE APPROVED FOR | | | INSPECTION, AND FOR PUBLIC RECORD- SEE COMMENTS BELOW | | | | | | A) EXHAUST VENTILATION CALCULATIONS FOR THE DISPATCH | | | AND LOADING AREAS. PLEASE REVIEW SECTION 406 AND | | | IDENTIFY IF THE AREAS IN QUESTION ARE TO BE CLASSIFIED | | | AS PRIVATE OR PUBLIC GARAGES. IN EITHER CASE EXHAUST | | | VENTILATION SYSTEMS SIZED AT A RATE OF 0.75 CFMS PER | | | SF. WILL BE REQUIRED- TABLE 403.3.1.1 FBC M. (SEE SHEET | | | A-1: THE PLANS SHOW OVERHEAD DOORS AT GRADE LEVEL IN | | | THESE AREAS WHICH ALLOWS FOR VEHICLES TO DRIVE IN AND | | | OUT, AND ALSO BE PARKED). | | | | | | B) CLARIFY THE USE OF THE CHARGING STATION SHOWN IN THE | | | WAREHOUSE OF SHEET EP-1. PLEASE NOTE THAT AN EXHAUST | | | VENTILATION SYSTEM IS REQUIRED FOR BATTERY CHARGING | | | AREAS PER SECTIONS 502.3- 502.5.3 FBC M. (THE ARCHITECT | | | HAS INDICATED CELL PHONE CHARGING AND NOT BATTERY | | | CHARGING FOR FORKLIFTS IN THIS AREA. THE ARCHITECT MUST | | | INDICATE THAT ON THE PLAN, OTHERWISE PROVIDE THE | | | REQUIRED EXHAUST VENTILATION IN THIS AREA). | | | | | | C) PROVIDE THE LEVEL OF ALTERATION FOR THE PROPOSED | | | PROJECT- SEE CHAPTER 5 FBC EX AND DETERMINE IF THE | | | PROJECT IS A LEVEL 1, 2, OR 3 ALTERATION OR A CHANGE OF | | | OCCUPANCY. | | | | | | D) SHOW HOW THE WAREHOUSE IS BEING VENTILATED AND WHAT | | | MATERIALS ARE BEING STORED THERE- SEE SECTIONS 401.2, | | | 402.1 AND TABLE 403.3.1.1. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2018-11-28 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-11-28 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-11-28 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2018-11-28 16:05:36 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT #18081507 | | | 11/28/18 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED | | | | | | SOME OF THE 1ST REVIEW COMMENTS LISTED BELOW HAVE NOT | | | BEEN ADDRESSED COMPLETELY. PLEASE COMPLY | | | | | | 1) REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 403.3.1 FBC-17 MECHANICAL. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED CFMS OF OUTDOOR AIR. | | | | | | 2) PROVIDE A DUCT LAYOUT PLAN SHOWING THE REQUIRED | | | ALTERATIONS TO THE EXISTING SYSTEMS TO ACCOMODATE THE | | | NEW ROOMS AND SPACES WITH BALANCED AIR CONDITIONING- | | | SECTION 603.1 FBC M. ( SEE SHEET EP-1: SUPPLY AND | | | RETURN MISSING FROM SOME OF THE NEW ROOMS BEING | | | CONSTRUCTED). | | | | | | 3) EXHAUST VENTILATION CALCULATIONS FOR THE DISPATCH | | | AND LOADING AREAS. PLEASE REVIEW SECTION 406 AND | | | IDENTIFY IF THE AREAS IN QUESTION ARE TO BE CLASSIFIED | | | AS PRIVATE OR PUBLIC GARAGES. IN EITHER CASE EXHAUST | | | VENTILATION SYSTEMS SIZED AT A RATE OF 0.75 CFMS PER | | | SF. WILL BE REQUIRED- TABLE 403.3.1.1 FBC M. (SEE SHEET | | | A-1: THE PLANS SHOW OVERHEAD DOORS AT GRADE LEVEL IN | | | THESE AREAS WHICH ALLOWS FOR VEHICLES TO DRIVE IN AND | | | OUT, AND ALSO BE PARKED). | | | | | | 4) CLARIFY THE USE OF THE CHARGING STATION SHOWN IN THE | | | WAREHOUSE OF SHEET EP-1. PLEASE NOTE THAT AN EXHAUST | | | VENTILATION SYSTEM IS REQUIRED FOR BATTERY CHARGING | | | AREAS PER SECTIONS 502.3- 502.5.3 FBC M. (THE ARCHITECT | | | HAS INDICATED CELL PHONE CHARGING AND NOT BATTERY | | | CHARGING FOR FORKLIFTS IN THIS AREA. THE ARCHITECT MUST | | | INDICATE THAT ON THE PLAN, OTHERWISE PROVIDE THE | | | REQUIRED EXHAUST VENTILATION IN THIS AREA). | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-10-10 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-10-10 |
Time |
17:16 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-10-10 |
Time |
17:16 |
Sent To |
|
|
| Notes |
| 2018-10-10 17:45:53 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #18081507 | | | 10/10/18 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) NO MECHANICAL PLANS WERE SUBMITTED FOR THIS | | | ALTERATION PROJECT EXCEPT A NOTE AND A DETAIL ON SHEET | | | EP-1 ADDRESSING THE RELOCATION OF AN AHU AND HOW IT | | | WILL BE SUPPORTED ABOVE THE CEILING. PLEASE PROVIDE THE | | | FOLLOWING: | | | | | | A) PROVIDE THE LEVEL OF ALTERATION FOR THE PROPOSED | | | PROJECT- SEE CHAPTER 5 FBC EX AMD DETERMINE IF THE | | | PROJECT IS A LEVEL 1, 2, OR 3 ALTERATION OR A CHANGE OF | | | OCCUPANCY. | | | | | | B) MINIMUM VENTILATION RATES FOR ALL ROOMS AND SPACES: | | | REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 403.3.1 FBC-17 MECHANICAL. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED CFMS OF OUTDOOR AIR. | | | | | | C) EXHAUST VENTILATION CALCULATIONS FOR THE DISPATCH | | | AND LOADING AREAS. PLEASE REVIEW SECTION 406 AND | | | IDENTIFY IF THE AREAS IN QUESTION ARE TO BE CLASSIFIED | | | AS PRIVATE OR PUBLIC GARAGES. IN EITHER CASE EXHAUST | | | VENTILATION SYSTEMS SIZED AT A RATE OF 0.75 CFMS PER | | | SF. WILL BE REQUIRED- TABLE 403.3.1.1 FBC M. | | | | | | D) PROVIDE A DUCT LAYOUT PLAN SHOWING THE REQUIRED | | | ALTERATIONS TO THE EXISTING SYSTEMS TO ACCOMODATE THE | | | NEW ROOMS AND SPACES WITH BALANCED AIR CONDITIONING- | | | SECTION 603.1 FBC M. | | | | | | E) PROVIDE AN AIR DEVICE SCHEDULE. | | | | | | F) SHOW HOW THE WAREHOUSE IS BEING VENTILATED AND WHAT | | | MATERIALS ARE BEING STORED THERE- SEE SECTIONS 401.2, | | | 402.1 AND TABLE 403.3.1.1. | | | | | | G) CLARIFY THE USE OF THE CHARGING STATION SHOWN IN THE | | | WAREHOUSE OF SHEET EP-1. PLEASE NOTE THAT AN EXHAUST | | | VENTILATION SYSTEM IS REQUIRED FOR BATTERY CHARGING | | | AREAS PER SECTIONS 502.3- 502.5.3 FBC M. | | | | | | | | | PLEASE NOTE THAT DUE TO THE LACK OF MECHANICAL PLANS | | | THERE MAY BE ADDITIONAL COMMENTS WHEN COMPLETE PLANS | | | AND CALCULATIONS ARE SUBMITTED. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2018-12-17 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-12-17 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-12-17 |
Time |
11:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-10-16 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-10-16 |
Time |
07:11 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-10-15 |
Time |
16:45 |
Sent To |
|
|
| Notes |
| 2018-10-16 07:19:44 | 1ST REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. A SERVICE SINK IS REQUIRED PLEAS SHOW LOCATION THE | | | PLAN SHOW A UTILITY SINK BEING ELIMINATED IN COPIER | | | ROOM #2 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | AND FBC PL TABLE 403.1 | | | | | | 2. HOT WATER IS REQUIRED AT THE BREAKROOM SINK. PER FBC | | | PL 607.1 | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|