Plan Review Details - Permit 18081500
Plan Review Stops For Permit 18081500
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-10-22 Cont ID  
Sent By pvalenti Date 2018-10-22 Time 11:01 Rev Time 0.00
Received By pvalenti Date 2018-10-22 Time 11:01 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-22 Cont ID  
Sent By shill Date 2018-09-22 Time 17:54 Rev Time 0.00
Received By shill Date 2018-09-22 Time 17:54 Sent To  
Notes
2018-09-22 17:56:16****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107, PLAN IS TOO SMALL; PLANS ARE TO BE
 ARCHITECTURAL QUALITY, DRAWN TO SCALE, MINIMUM 1/8"
 (1/4" PREFERABLE).
  
 2. FBC A FAIR HOUSING, REVISE PLAN TO SHOW COMPLIANCE
 WITH FAIR HOUSING REQUIREMENTS.
  
 3. FBC 107, THE PRINTED NAME AND SIGNATURE OF THE
 INDIVIDUAL TAKING RESPONSIBILITY FOR THE DESIGN IS
 REQUIRED TO BE ON THE PLANS.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-10-11 Cont ID  
Sent By jpearson Date 2018-10-11 Time 10:52 Rev Time 0.00
Received By jpearson Date 2018-10-11 Time 10:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-20 Cont ID  
Sent By jpearson Date 2018-09-20 Time 09:46 Rev Time 0.00
Received By jpearson Date 2018-09-20 Time 09:46 Sent To  
Notes
2018-09-20 09:46:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. THIS PERSON MUST BE A LICENSED DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER.
 PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-11-09 Cont ID  
Sent By lcrespo Date 2018-11-09 Time 15:17 Rev Time 0.00
Received By lcrespo Date 2018-10-31 Time 15:35 Sent To  
Notes
2018-11-01 15:35:34RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-24 Cont ID  
Sent By tklarge Date 2018-10-24 Time 12:16 Rev Time 0.00
Received By tklarge Date 2018-10-04 Time 13:45 Sent To  
Notes
2018-10-05 13:45:54B15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-24 Cont ID  
Sent By tklarge Date 2018-09-24 Time 06:18 Rev Time 0.00
Received By tklarge Date 2018-08-30 Time 14:32 Sent To  
Notes
2018-09-22 17:56:29TO TL DESK
  
2018-08-31 14:32:30B27

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-11-09 Cont ID  
Sent By lcrespo Date 2018-11-09 Time 15:17 Rev Time 0.00
Received By lcrespo Date 2018-11-09 Time 15:17 Sent To  
Notes
2018-11-09 15:18:4611/09/18 REVIEWED FOR CODE COMPLIANCE
 (PLUMBING/BACKFLOW)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-10-24 Cont ID  
Sent By tklarge Date 2018-10-24 Time 12:13 Rev Time 0.00
Received By tklarge Date 2018-10-24 Time 12:03 Sent To I
Notes
2018-10-24 12:15:31THE FOLLOWING COMMENTS FROM THE FIRST PLUMBING REVIEW
 HAVE NOT BEEN ADDRESSED.
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FHA = FAIR HOUSING ACT
  
  
 1. THIS BUILDING WAS CONSTRUCTED UNDER THE REQUIREMENTS
 OF THE FAIR HOUSING ACT. INDICATE ON THE PLANS WHICH
 DESIGN SPECIFICATION ( "A" OR 'B" OF THE ACT) WAS USED
 IN THE ORIGINAL DESIGN OF THIS UNIT.
  
 2. SHOW THE DEPTH OF THE NEW VANITY. THE VANITY SHALL
 BE A MAXIMUM OF 24 INCHES DEEP PER THE FAIR HOUSING
 ACT.
  
 3. ADDITIONAL REINFORCEMENT MAY BE REQUIRED IN THE
 WALLS AROUND THE TUB TO ALLOW FOR THE FUTURE
 INSTALLATION OF GRAB BARS PER THE FAIR HOUSING ACT.
 SHOW THE LOCATION OF THE REQUIRED REINFORCEMENTS AND
 THE MINIMUM WIDTH OF THE REINFORCEMENT AND THE MINIMUM
 AND MAXIMUM DISTANCES FROM THE FINISH FLOOR.
  
 4) SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE NEW TUB
 IN ACCORDANCE WITH THE FAIR HOUSING ACT.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-09-24 Cont ID  
Sent By tklarge Date 2018-09-24 Time 06:17 Rev Time 0.00
Received By tklarge Date 2018-09-24 Time 05:01 Sent To I
Notes
2018-09-24 06:17:47 
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FHA = FAIR HOUSING ACT
  
  
 1. FBC 107, PLAN IS TOO SMALL; PLANS ARE TO BE
 ARCHITECTURAL QUALITY, DRAWN TO SCALE, MINIMUM 1/8"
 (1/4" PREFERABLE).
  
 2. FBC 107, THE PRINTED NAME AND SIGNATURE OF THE
 INDIVIDUAL TAKING RESPONSIBILITY FOR THE DESIGN IS
 REQUIRED TO BE ON THE PLANS.
  
 3. THIS BUILDING WAS CONSTRUCTED UNDER THE REQUIREMENTS
 OF THE FAIR HOUSING ACT. INDICATE ON THE PLANS WHICH
 DESIGN SPECIFICATION ( "A" OR 'B" OF THE ACT) WAS USED
 IN THE ORIGINAL DESIGN OF THIS UNIT.
  
 4. SHOW THE DEPTH OF THE NEW VANITY. THE VANITY SHALL
 BE A MAXIMUM OF 24 INCHES DEEP PER THE FAIR HOUSING
 ACT.
  
 5. ADDITIONAL REINFORCEMENT MAY BE REQUIRED IN THE
 WALLS AROUND THE TUB TO ALLOW FOR THE FUTURE
 INSTALLATION OF GRAB BARS PER THE FAIR HOUSING ACT.
 SHOW THE LOCATION OF THE REQUIRED REINFORCEMENTS AND
 THE MINIMUM WIDTH OF THE REINFORCEMENT AND THE MINIMUM
 AND MAXIMUM DISTANCES FROM THE FINISH FLOOR.
  
 6) SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE NEW TUB
 IN ACCORDANCE WITH THE FAIR HOUSING ACT.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  