Plan Review Details - Permit 18081451
Plan Review Stops For Permit 18081451
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-12-03 Cont ID  
Sent By pvalenti Date 2018-12-03 Time 07:12 Rev Time 0.00
Received By pvalenti Date 2018-12-03 Time 07:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-07 Cont ID  
Sent By shill Date 2018-09-07 Time 08:01 Rev Time 0.00
Received By shill Date 2018-09-07 Time 07:51 Sent To  
Notes
2018-09-07 08:01:51****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. THE PHASING PLAN IS NOT CLEAR. FBC B 3302.1, WILL
 PHASE 01 BE OPEN DURING PHASE 02 CONSTRUCTION? IF YES,
 HOW WILL EXIT LIGHTING BE AFFECTED? PROVIDE A NARRATIVE
 WHICH EXPLAINS THE PHASING.
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-11-20 Cont ID  
Sent By scaldero Date 2018-11-20 Time 09:32 Rev Time 0.00
Received By scaldero Date 2018-11-20 Time 09:32 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-09-05 Cont ID  
Sent By scaldero Date 2018-09-05 Time 11:03 Rev Time 0.00
Received By scaldero Date 2018-09-05 Time 10:26 Sent To  
Notes
2018-09-05 11:03:45PERMIT #18081451
 FIRE REVIEW COMMENTS
  
 FAILED COMMENTS:
  
 1) CLARIFICATION NEEDED ON WHAT IS TO BE ANTICIPATED AS
 PART OF THE PHASING PLANS. PLEASE PROVIDE A NARRATIVE
 EXPLANATION OF PHASING PLAN. PLEASE INCLUDE, AT A
 MINIMUM:
 A) WHAT, IF ANY, PART OF THE STORE WILL BE OPEN TO THE
 PUBLIC AND/OR STORE EMPLOYEES DURING EACH PHASE.
 B) HOW WILL CUSTOMERS AND STORE EMPLOYEES BE KEPT OUT
 OF CONSTRUCTION AREAS DURING PHASING WORK.
 C) ALL REQUIRED FIRE AND LIFE SAFETY SYSTEMS SHALL BE
 FULLY OPERATIONAL PRIOR TO OCCUPANCY.
 D) WHAT ARE THE ANTICIPATED PHASING DATES/ TIME FRAMES?
 E) PHASE 4 APPEARS TO APPLY TO THE MAIN POINT OF ENTRY
 AND EGRESS, WILL THIS ACCESS POINT BE OPEN TO THE
 PUBLIC DURING CONSTRUCTION OF PHASE 4? IF SO, HOW WILL
 CUSTOMERS BE PROTECTED FROM CONSTRUCTION WORK?
 F) THE RESTROOMS ARE LOCATED IN PHASE 3, WILL THEY BE
 ACCESSIBLE DURING CONSTRUCTION OF THIS PHASE? IF SO,
 WHAT KEEPS PATRONS/EMPLOYEES FROM ACCESSING THE
 CONSTRUCTION AREA?
  
 2) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-03 Cont ID  
Sent By pvalenti Date 2018-12-03 Time 07:13 Rev Time 0.00
Received By pvalenti Date 2018-11-15 Time 09:32 Sent To I
Notes
2018-11-16 09:32:55RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-07 Cont ID  
Sent By shill Date 2018-09-07 Time 08:01 Rev Time 0.00
Received By shill Date 2018-08-29 Time 10:48 Sent To  
Notes
2018-08-31 10:48:56ROUTED TO FIRE INBOX