Plan Review Details - Permit 18081420
Plan Review Stops For Permit 18081420
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-09-24 Cont ID  
Sent By rmcdouga Date 2018-09-24 Time 16:39 Rev Time 0.00
Received By rmcdouga Date 2018-09-24 Time 16:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-17 Cont ID  
Sent By rmcdouga Date 2018-09-17 Time 18:01 Rev Time 0.00
Received By rmcdouga Date 2018-09-17 Time 17:39 Sent To I
Notes
2018-09-17 17:40:19PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION IS DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A FLOOR PLAN THAT SHOWS THE LOCATION, SIZE
 AND TYPE OF WINDOWS THAT ARE BEING ADDED TO THE SCOPE
 OF WORK. FBC 107.2.1
  
 2) THE WINDOW DOCUMENTS THAT WERE SUBMITTED FOR THE
 JELD-WEN SINGLE HUNG WINDOWS DO NOT HAVE THE FL# OR THE
 NOA# FOR THE PRODUCT. FAC 61G20-3
  
 3) IF ANY OF THESE ARE DOUBLE WINDOWS THAT ARE JOINED
 TOGETHER WITH A STRUCTURAL MULLION, THEN YOU WILL NEED
 TO SUBMIT PRODUCT APPROVALS FOR THEM. FAC 61G20-3
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-09-07 Cont ID  
Sent By fmittner Date 2018-09-07 Time 16:55 Rev Time 0.00
Received By fmittner Date 2018-09-07 Time 16:55 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-17 Cont ID  
Sent By rmcdouga Date 2018-09-17 Time 18:01 Rev Time 0.00
Received By rmcdouga Date 2018-08-29 Time 16:03 Sent To  
Notes
2018-08-30 16:03:53REVISION ROUTED TO HISTORIC INBOX