Plan Review Details - Permit 18081417
Plan Review Stops For Permit 18081417
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-11-05 Cont ID  
Sent By rmcdouga Date 2018-11-05 Time 08:31 Rev Time 0.00
Received By rmcdouga Date 2018-11-05 Time 07:47 Sent To I
Notes
2018-11-05 08:31:28PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) YOU ARE REQUIRED TO FILL OUT A RE-SUBMITTAL FORM TO
 BE SUBMITTED WITH THE CORRECTED PLANS AND/OR OTHER
 DOCUMENTS. THE PERMIT CLERK WILL RETRIEVE THE DENIED
 APPLICATION, PLANS AND OTHER DOCUMENTS FOR YOU. YOU ARE
 REQUIRED TO REMOVE THE OLD PLAN SHEETS THAT HAVE BEEN
 CORRECTED AND REPLACE THEM WITH THE NEW ONES. THE CLERK
 WILL PROVIDE YOU WITH A STAPLE REMOVER AND A STAPLER.
 ONE SET OF THE OLD PLAN SHEETS THAT HAVE BEEN REMOVED
 SHALL BE MARKED AS "VOIDED" AND RESUBMITTED ALONG WITH
 THE TWO (OR MORE) SETS THAT CONTAIN THE CORRECTED
 SHEETS. IF ALL OF THE PLAN SHEETS HAVE BEEN CORRECTED,
 THEN TWO (OR MORE) SETS OF THE NEW PLANS AND ANY OTHER
 DOCUMENTS SHALL BE SUBMITTED. TWO COMPLETE SETS OF
 PLANS AND OTHER CONSTRUCTION DOCUMENTS ARE REQUIRED TO
 BE SUBMITTED. FBC 107.1
  
 2) THERE IS A DIFFERENCE BETWEEN THE SIGNED AND SEALED
 ENGINEERING AND THE OTHER DRAWINGS. THE POOL SHAPE AND
 CROSS SECTIONS OF THE POOLS DO NOT MATCH. FBC107.2.1
  
 3) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 4) THE ADDRESS OF THE PROJECT IS REQUIRED ON THE
 DRAWINGS. FBC 107.2.1
  
 5) THERE ARE DRAWINGS THAT WERE SUBMITTED THAT ARE
 SIGNED AND SEALED BY TWO DIFFERENT FLORIDA LICENSED
 PROFESSIONAL ENGINEERS. ONE OF THESE ENGINEERS IS
 REQUIRED TO BE THE DESIGNER OF RECORD FOR THIS PROJECT.
 THE OTHER WOULD BE A DELEGATED ENGINEER. THE DESIGNER
 OF RECORD IS REQUIRED TO REVIEW AND APPROVE THE
 CONSTRUCTION DOCUMENTS FROM THE DELEGATED ENGINEER. FAC
 61G15-30.005
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-26 Cont ID  
Sent By rmcdouga Date 2018-09-26 Time 08:01 Rev Time 0.00
Received By rmcdouga Date 2018-09-26 Time 06:57 Sent To I
Notes
2018-09-26 07:37:33PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE SIGNED AND SEALED ENGINEERING TO SPECIFY THE
 REQUIRED LOCATIONS OF THE 30" X 30" CONCRETE DEADMAN
 ANCHORS. 107.2.1.2
  
 2) THERE IS A DIFFERENCE BETWEEN THE SIGNED AND SEALED
 ENGINEERING AND THE OTHER DRAWINGS. THE POOL SHAPE AND
 CROSS SECTIONS OF THE POOLS DO NOT MATCH. FBC107.2.1
  
 3) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 4) THE ADDRESS OF THE PROJECT IS REQUIRED ON THE
 DRAWINGS. FBC 107.2.1
  
 5) THE BLOCK DECO WALL DRAWINGS ARE MISSING
 INFORMATION. PROVIDE AN ELEVATION DRAWING OF THE WALL.
 SPECIFY THE SPACING OF THE VERTICAL REBAR AND THE
 SPACING OF THE CROSS BARS IN THE FOOTING. VERTICAL
 REINFORCING IS REQUIRED AT EACH END OF THE WALL. A BOND
 BEAM WITH HORIZONTAL REINFORCING IS REQUIRED AT THE TOP
 OF THE WALL. CLARIFY THE WIDTH AND THICKNESS OF THE
 FOOTER. A 12" WIDE FOOTER IS NOT ADEQUATE FOR THE 8"
 CONCRETE BLOCK WALL WITHOUT ENGINEERING. THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN IS
 REQUIRED ON ALL DRAWINGS. FBC 107.2.1
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-10-29 Cont ID  
Sent By jleahy Date 2018-10-29 Time 10:44 Rev Time 0.00
Received By jleahy Date 2018-10-29 Time 10:06 Sent To P
Notes
2018-10-29 10:45:04SEE PLAN COMMENTS FROM FIRST REVIEW JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-20 Cont ID  
Sent By jleahy Date 2018-09-20 Time 13:37 Rev Time 0.00
Received By jleahy Date 2018-09-20 Time 13:37 Sent To  
Notes
2018-09-20 13:39:00FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRIC SHOWN , NEED TO SIZE OF PUMP AND WIRE TO
 PUMP, GFCI PROTECTION, POOL LIGHT TRANSFORMER OR
 DRIVER.

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-09-17 Cont ID  
Sent By tklarge Date 2018-09-17 Time 12:46 Rev Time 0.00
Received By tklarge Date 2018-09-17 Time 12:46 Sent To  
Notes
2018-09-17 12:46:51THERE IS NO GAS HEATER ON THIS POOL. TKL.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-05 Cont ID  
Sent By rmcdouga Date 2018-11-05 Time 08:31 Rev Time 0.00
Received By rmcdouga Date 2018-10-16 Time 13:41 Sent To  
Notes
2018-10-17 13:41:26RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-26 Cont ID  
Sent By rmcdouga Date 2018-09-26 Time 08:01 Rev Time 0.00
Received By rmcdouga Date 2018-08-29 Time 14:16 Sent To  
Notes
2018-08-30 14:16:50ROUTED TO ZONING INBOX

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-11-01 Cont ID  
Sent By tklarge Date 2018-11-01 Time 11:44 Rev Time 0.00
Received By tklarge Date 2018-11-01 Time 06:01 Sent To  
Notes
2018-11-01 11:06:041) THERE ARE TWO DIFFERENT SIGNED AND SEALED POOL
 DRAWINGS IN THE SUBMITTAL PACKAGE. ONE IS BY CHARLES
 R.ADAMS AND ONE IS BY G.B. COLLINS ENGINEERING. REMOVE
 THE DRAWING THAT IS NOT APPLICABLE FROM THIS PACKAGE
 AND SUBMIT TWO COMPLETE SETS OF PLANS FOR SUBMITTAL.
 FBC SEC. 107.1.
 2) SPECIFICATIONS HAVE BEEN SUBMITTED FOR TWO DIFFERENT
 PUMPS AND FILTERS. REMOVE ALL OLD DOCUMENTS FROM THE
 SUBMITTAL PACKAGE AND SUBMIT TWO COMPLETE SETS OF
 DOCUMENTS FOR REVIEW. FBC SEC. 107.1.
 3) A SIMPLIFIED TOTAL DYNAMIC HEAD WORKSHEET SIGNED AND
 SEALED BY RICHARD TOMMELL HAS BEEN SUBMITTED. THE 2013
 EDITION OF ANSI/APSP/ICC-7 2013 DOES NOT ALLOW THIS
 METHOD TO BE USED FOR CALCULATION OF MAXIMUM SYSTEM
 FLOW RATE. REFER TO THE OPTIONS IN SEC. 4.4.9.1 OF THE
 AFOREMENTIONED CODE. THE RESPONSE LETTER FROM G.B.
 COLLINS ENGINEERING STATES THAT THE REASON FOR NOT
 ALLOWING THE SIMPLIFIED TDH METHOD IS UNCLEAR. PLEASE
 REFER TO THE AFOREMENTIONED STANDARD AND CODE SECTION.
 THE SIMPLIFIED TDH METHOD DEFINITION IS NO LONGER IN
 APSP-7 2013. SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS IN
 ACCORDANCE WITH APSP-7 2013. 2ND REQUEST.
 4) PLAN BY G.B. COLLINS - UNDER "GENERAL DESIGN
 REQUIREMENTS" NOTES REFERS TO ONE RETURN INLET PER 600
 SQ. FT. 2017 FBC-RES. SEC. R4501.21.5 REQUIRES ONE
 RETURN EVERY 300 SQ. FT. REVISE THE NOTE.
 5) SHOW THE COMPLETE SPA PIPING LAYOUT ON THE PLAN FROM
 G.B.COLLINS IF THAT IS THE PLAN TO BE SUBMITTED FOR
 PERMIT.FBC 107.2.1.
 6) SIZE ALL SECTIONS OF THE POOL AND SPA PIPING ON THE
 PLAN FROM G.B. COLLINS IF THAT IS THE PLAN TO BE
 SUBMITTED FOR PERMIT.FBC 107.2.1. FBC 107.2.1.
 7) SHOW ON THE PLAN FROM G.B. COLLINS IF THERE ARE ANY
 MAIN DRAINS ON THE POOL IF THAT IS THE PLAN TO BE
 SUBMITTED FOR PERMIT.FBC 107.2.1. FBC 107.2.1.
 8) THE POOL PLAN FROM G.B. COLLINS REFERS TO FLORIDA
 BUILDING CODE SEC.R4101. THIS SECTION IS FOR ELECTRICAL
 APPLIANCE INSTALLATION AND HAS NOTHING TO DO WITH THE
 POOL CODE. REVISE THE NOTE TO READ THE CORRECT SECTION
 OF THE FBC. FBC 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-09-17 Cont ID  
Sent By tklarge Date 2018-09-17 Time 12:46 Rev Time 0.00
Received By tklarge Date 2018-09-17 Time 05:56 Sent To  
Notes
2018-09-17 11:06:561) THE SIMPLIFIED TOTAL DYNAMIC HEAD CALCULATION METHOD
 IS NO LONGER PERMITTED BY APSP 7- 2013. THEREFORE, THE
 SUBMITTTED TOTAL DYNAMIC HEAD CALCULATION SHEET IS
 UNACCEPTABLE. SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS
 FOR THE MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE
 PUMP FROM ITS PUMP CURVE IS NO LONGER ALLOWED TO BE
 USED IN DETERMINING MAXIMUM SYSTEM FLOW RATE PER
 ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013
 EDITION ADDRESSES FLOW RATE IN GALLONS PER MINUTE
 (GPM). IT REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES
 NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF THE SUCTION
 OUTLET FITTING ASSEMBLY (DRAIN COVER).THE TDH
 CALCULATIONS MUST INCLUDE ALL OF THE SYSTEM COMPONENTS
 INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES,
 HEATER, FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS
 EXCEPT THE PUMP.
 2) SUBMIT TWO LEGIBLE COPIES OF THE POOL PUMP CURVE.
 IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC
 TO THE PUMP BEING INSTALLED ON THIS POOL. THIS IS
 NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH
 CALCULATIONS
 3) INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS FOR
 THE PUMP BEING INSTALLED ON THIS SYSTEM. WPB AMEND. TO
 FBC SEC. 107.2.1.
 4) INDICATE ON THE POOL EQUIPMENT DOCUMENTS WHICH MODEL
 FILTER IS BEING INSTALLED. 2017 FBC SEC. 107.2.1.
 5) INDICATE ON THE POOL EQUIPMENT DOCUMENTS WHICH MODEL
 PUMP IS BEING INSTALLED. 2017 FBC SEC. 107.2.1.
 6) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE POOL MAIN DRAINS. 2017 FBC SEC.
 107.2.1.
 7) THE PRINTING ON THE SUBMITTTED SIGNED AND SEALED
 PLANS BY CHARLES ADAMS IS BARELY LEGIBLE. SUBMIT TWO
 LEGIBLE COPIES OF THE DOCUMENTS SIGNED AND SEALED BY
 CHARLES ADAMS FOR REVIEW. 2017 FBC SEC. 107.2.1, FL.
 ADMIN. CODE RULE 61G15-23.001.
 8) THE PIPE SIZES ARE MISSING FROM THE PIPING SCHEMATIC
 ON THE DDRAWINGS FROM MR. ADAMS, ENGINEER. 2017 FBC
 SEC. 107.2.1.
 9) SHT. 2 - NOTES - THE STANDARDS LISTED IN NOTE 13 OF
 PLANS FROM CHARLES ADAMS ARE OUTDATED. REVISE THE NOTE.
 THE FOLLOWING STANDARDS ARE IN EFFECT:
 ANSI/NSPI 3 - 2015
 ANSI/NSPI 5 - 2011
 ANSI/NSPI 7 - 2013
 10) INDICATE ON SHT. 2 OF THE PLANS FROM CHARLES
 EDWARDS WHICH MODEL OF THE POOL IS BEING INSTALLED.
 2017 FBC SEC. 107.2.1.
 11) SHT. 2, NOTE #19 OF PLANS BY CHARLES ADAMS STATES
 THAT THE PIPE SIZING AND HYDRAULIC VELOCITY WERE DONE
 BY THE CONTRACTOR. CLARIFY. THE ENGINEER OF RECORD IS
 RESPONSIBLE FOR THE DESIGN OF THE POOL. FL. ADMIN. CODE
 RULE 61G15-30.003.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-10-26 Cont ID  
Sent By mcruz Date 2018-10-26 Time 11:56 Rev Time 0.00
Received By mcruz Date 2018-10-26 Time 11:55 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-09-06 Cont ID  
Sent By mcruz Date 2018-09-06 Time 11:11 Rev Time 0.00
Received By mcruz Date 2018-09-06 Time 10:29 Sent To  
Notes
***NONE***