| Plan Review Stops For Permit 18081402 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2019-02-14 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-02-14 |
Time |
10:16 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-02-13 |
Time |
18:20 |
Sent To |
|
|
| Notes |
| 2019-02-14 10:18:26 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- GAF SINGLE PLY PLY ROOFING SYSTEMS NOA 18-0523.05 | | | SUBMITTED. PROVIDE SIGNED AND SEALED RAS 117 | | | CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-01-17 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-01-17 |
Time |
18:30 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-01-17 |
Time |
11:37 |
Sent To |
|
|
| Notes |
| 2019-01-17 18:31:19 | NEW BUILDING (GROUP B) SECOND BUILDING REVIEW | | | CHECKLIST. | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | | | | PROVISO NOTE: | | | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO | | | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER | | | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID | | | CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR | | | TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME | | | OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT | | | ISSUANCE. | | | | | | | | | 1- OK. | | | | | | 2- TO BE DONE LATER BEFORE ISSUING PERMIT. | | | | | | 3- SOIL TEST REPORT SUBMITTED NEEDS SURVEYORS ORIGINAL | | | SEAL AND SIGNATURE OR DIGITAL SIGNATURE WHEN SUBMITTING | | | DOCUMENTS FOR PUBLIC RECORDS. CHAPTER 472 F.S. | | | | | | 4- OK. | | | | | | 5- ENERGY CALCULATIONS FORM SUBMITTED: | | | A) PLANS NEED TO SPECIFY THE INSULATION R VALUE OF | | | EXTERIOR WALLS. NOTE: ARCHITECT AND ENGINEER PREPARING | | | THE ENERGY CALCULATIONS TO COORDINATE INFORMATION TO | | | AVOID CONFLICTS/DELAYS. THIS APPLIES TO CEILING | | | INSULATION ALSO. SEC. C103.2 FBC-ENERGY CONSERVATION. | | | | | | RESPONSE: | | | PARTIALLY DONE. ARCHITECT PROVIDED INFORMATION ON SHEET | | | A.05 BUT INFORMATION SHOWN ON THE ENERGY CALCULATIONS | | | AND ARCHITECTURAL PLANS DON'T MATCH. ARCHITECT AND | | | ENGINEER TO COORDINATE TO AVOID MORE CONFLICTS/DELAYS. | | | | | | B)ARCHITECT OF RECORD TO CERTIFY (SIGNATURE AND LICENSE | | | NUMBER) ON ENERGY FORM AS REQUIRED BY SEC. C103.1.1.1.2 | | | FBC-ENERGY CONSERVATION. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT DONE. | | | | | | C) THE BUILDING OWNER OR LEGALLY AUTHORIZED AGENT NEEDS | | | TO CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE | | | ENERGY CODE AS REQUIRED BY SEC. C103.1.1.2 FBC-ENERGY | | | CONSERVATION PRIOR TO RECEIVING THE PERMIT TO BEGIN | | | CONSTRUCTION. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT DONE. | | | | | | D) ENGINEER OF RECORD PERFORMING THE ENERGY | | | CALCULATIONS TO COORDINATE WITH ARCHITECTURAL PLANS TO | | | AVOID CONFLICTS/DELAYS. INFORMATION FOR WALLS AND | | | CEILING INSULATION R VALUE DOESN'T MATCH. SEC. 107.2.1 | | | CITY AMENDMENTS. ALSO, CHECK THE PROPER BOXES IN THE | | | MANDATORY SECTION. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT DONE. | | | | | | 6- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR | | | INTERIOR WINDOWS SHOWN ON FLOOR PLANS. INCLUDE FRAMING | | | DETAILS AND GLAZING SPECIFICATIONS. SEC. 2406 FBC. | | | | | | RESPONSE: | | | RESPONSE LETTER STATES ""PLEASE SEE REVIEWED NOA". | | | CLARIFY IF INSTALLING SAME TYPE OF WINDOWS AS THE ONES | | | USED FOR THE EXTERIOR. PROVIDE CLEAR SPECIFICATIONS IN | | | THE WINDOW SHELLED ON SHEET A.13. | | | | | | 7- OK. | | | | | | 8- OK. | | | | | | 9- OK. | | | | | | 10- DUMPSTER STRUCTURAL PLANS SHOWN ON SHEET A.03 DON'T | | | MATCH STRUCTURAL PLANS SHOWN ON SHEET S.01. REVISE AS | | | REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | RESPONSE: | | | STILL DON'T MATCH. REVISE AS REQUIRED TO MATCH (SEE | | | DIMENSIONS AND STRUCTURAL SPECIFICATIONS) OR PROVIDE | | | ONLY ONE DETAIL TO AVOID CONFLICTS. | | | | | | 11- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | | 61G20-3.001 FOR: | | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | | SUBMITTAL) | | | | | | A)GAF SINGLE PLY PLY ROOFING SYSTEMS NOA 18-0523.05 | | | SUBMITTED. PROVIDE SIGNED AND SEALED RAS 117 | | | CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7. | | | SEC. 1609 FBC. | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-11-16 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-11-16 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-11-15 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2018-11-16 13:16:17 | NEW BUILDING (GROUP B) BUILDING REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | 1-ART IN PUBLIC SPACES. | | | PLEASE REVIEW ART IN PUBLIC PLACES. THE CITY OF WEST | | | PALM BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT | | | THAT APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT | | | FOR WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER | | | 6/29/14, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE | | | EQUAL TO OR GREATER THAN $750,000 WILL NEED TO COMPLY | | | WITH THIS ORDINANCE. | | | PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND | | | CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, | | | ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION | | | 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL | | | PROJECT CONSTRUCTION COST. | | | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE | | | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND | | | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO | | | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE | | | PROJECTS. | | | FOR CONTACT INFORMATION PLEASE CONTACT: | | | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR | | | 822-1515 E-MAIL: [email protected] | | | | | | 2- IMPACT FEES - DIGITAL SUBMITTALS | | | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | 3- PROVIDE COPY OF SOIL TEST REPORT SPECIFIED ON | | | FOUNDATION NOTES ON SHEET S.03. | | | SEC. 1803.1 FBC. | | | | | | 4- SITE PLAN ON SHEET A.02 SHOWS 10'X20' LOADING ZONE | | | IN THE MIDDLE OF THE PARKING LOT. THIS LOADING AREA IS | | | BLOCKING THE ACCESSIBLE PARKING SPACE. REVISE AS | | | REQUIRED. SEC. 206.1 FBC-ACCESSIBILITY. | | | | | | 5- ENERGY CALCULATIONS: | | | A) PLANS NEED TO SPECIFY THE INSULATION R VALUE OF | | | EXTERIOR WALLS. NOTE: ARCHITECT AND ENGINEER PREPARING | | | THE ENERGY CALCULATIONS TO COORDINATE INFORMATION TO | | | AVOID CONFLICTS/DELAYS. THIS APPLIES TO CEILING | | | INSULATION ALSO. SEC. C103.2 FBC-ENERGY CONSERVATION. | | | | | | B)ARCHITECT OF RECORD TO CERTIFY (SIGNATURE AND LICENSE | | | NUMBER) ON ENERGY FORM AS REQUIRED BY SEC. C103.1.1.1.2 | | | FBC-ENERGY CONSERVATION. | | | | | | C) THE BUILDING OWNER OR LEGALLY AUTHORIZED AGENT NEEDS | | | TO CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE | | | ENERGY CODE AS REQUIRED BY SEC. C103.1.1.2 FBC-ENERGY | | | CONSERVATION PRIOR TO RECEIVING THE PERMIT TO BEGIN | | | CONSTRUCTION. | | | | | | D) ENGINEER OF RECORD PERFORMING THE ENERGY | | | CALCULATIONS TO COORDINATE WITH ARCHITECTURAL PLANS TO | | | AVOID CONFLICTS/DELAYS. INFORMATION FOR WALLS AND | | | CEILING INSULATION R VALUE DOESN'T MATCH. SEC. 107.2.1 | | | CITY AMENDMENTS. ALSO, CHECK THE PROPER BOXES IN THE | | | MANDATORY SECTION. | | | | | | 6- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR | | | INTERIOR WINDOWS SHOWN ON FLOOR PLANS. INCLUDE FRAMING | | | DETAILS AND GLAZING SPECIFICATIONS. SEC. 2406 FBC. | | | | | | 7- SHEET A.08: PROVIDE COMPLETE DETAILS AND | | | SPECIFICATIONS FOR THE FASTENING OF THE METAL PARAPET | | | CAP AND (2)2X10P.T. WOOD BLOCKING. SEC. 1609.1 FBC. | | | | | | 8- LADDER TO ACCESS A/C EQUIPMENT ON THE UPPER ROOF | | | NEED TO EXTEND NOT LESS THAN 30INCHES. LADDERS NEED TO | | | BE CONSTRUCTED AS REQUIRED BY SEC. 306.5 | | | FBC-MECHANICAL. (SEE SEC. 1011.16 FBC). NOTE: | | | COORDINATE WITH MECHANICAL PLANS EXAMINER/INSPECTOR TO | | | AVOID CONFLICTS/ DELAYS. | | | | | | 9- CLARIFY IF TENANT SEPARATION WALL BETWEEN | | | MISCELLANEOUS SPACE 1 AND MISCELLANEOUS SPACE 2 IS | | | GOING TO BE A FIRE RATED WALL OR NOT. WALL TYPE 5 ON | | | SHEET A.06 DOESN'T PROVIDE SPECS FOR A FIRE RATED | | | ASSEMBLY BUT LIFE SAFETY PLAN ON SHEET A.14 SPECIFIES | | | THAT IT IS A FIRE RATED WALL. REVISE/CLARIFY AS | | | REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | 10- DUMPSTER STRUCTURAL PLANS SHOWN ON SHEET A.03 DON'T | | | MATCH STRUCTURAL PLANS SHOWN ON SHEET S.01. REVISE AS | | | REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | 11- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | | 61G20-3.001 FOR: | | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | | SUBMITTAL) | | | | | | A) ALL EXTERIOR DOORS AS SHOWN ON PLANS. | | | | | | B) ALL WINDOWS AS SHOWN ON PLANS. | | | | | | C)FLAT ROOF FOR METAL DECK AND CONCRETE DECK AS SHOWN | | | ON PLANS. . AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | | DESIGN PRESSURES OF SEC. 1609 FBC. NOTE: IF THE | | | SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR | | | ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117 | | | CALCULATIONS ARE REQUIRED. | | | | | | D) PRECAST LINTELS AS SHOWN ON PLANS. | | | | | | E) HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE | | | IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION | | | SCHEDULE. SEE CITY SAMPLE. | | | | | | 12- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2019-02-13 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-02-13 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-02-13 |
Time |
10:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-01-08 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-01-08 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-01-08 |
Time |
11:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-10-23 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-10-23 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-10-23 |
Time |
10:33 |
Sent To |
|
|
| Notes |
| 2018-10-23 15:01:04 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | | NEC 110.9, 110.10 | | | 2. PROVIDE SHOW WINDOW OUTLETS PER NEC 210.62. | | | 3. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, | | | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD | | | SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND | | | SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN | | | THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE | | | INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN | | | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC | | | 105.1, 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2019-01-18 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-01-18 |
Time |
08:58 |
Rev Time |
0.00 |
| Received By |
mgonzale |
Date |
2019-01-18 |
Time |
08:57 |
Sent To |
|
|
| Notes |
| 2019-01-18 08:58:29 | PLANS UNDER REVIEW AT ENGINEERING SERVICES DEPT. | | | | | | [email protected] | | | (561)818-1322 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2018-11-19 |
|
|
Cont ID |
|
| Sent By |
Mgonzale |
Date |
2018-11-19 |
Time |
|
Rev Time |
|
| Received By |
mgonzale |
Date |
2018-11-19 |
Time |
|
Sent To |
I |
|
| Notes |
| 2018-11-19 09:56:21 | PLANS UNDER REVIEW AT ENGINEERING SERVICES DEPT. | | | | | | [email protected] | | | (561)818-1322 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-12-20 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2018-12-20 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2018-12-20 |
Time |
09:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-09-25 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2018-09-25 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2018-09-21 |
Time |
14:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-02-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-02-20 |
Time |
11:59 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-01-25 |
Time |
14:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-01-18 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-01-18 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-12-18 |
Time |
12:54 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-11-26 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2018-11-26 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2018-09-19 |
Time |
09:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
P |
Date |
2019-03-06 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2019-03-06 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-02-13 |
Time |
14:00 |
Sent To |
|
|
| Notes |
| 2019-03-06 10:11:22 | RECEIPT 2019-0301-252 - $8756.13 PAID | | 2019-02-13 14:00:22 | 2/13/19 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2019-01-17 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-01-17 |
Time |
18:42 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-01-17 |
Time |
18:42 |
Sent To |
|
|
| Notes |
| 2018-12-21 08:54:50 | IMPACT FEES - DIGITAL SUBMITTALS | | | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2018-11-16 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-11-16 |
Time |
17:01 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-11-16 |
Time |
17:01 |
Sent To |
|
|
| Notes |
| 2018-11-16 17:01:20 | IMPACT FEES - DIGITAL SUBMITTALS | | | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2019-02-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-02-15 |
Time |
17:26 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-02-15 |
Time |
17:26 |
Sent To |
|
|
| Notes |
| 2019-02-15 17:27:45 | PROVISO: NEW SHEETS OK; IF THERE IS ANOTHER REVIEW | | | CYCLE, NEW SHEETS REQUIRE VERIFICATION | | | SHEET A.01 PROVIDED AS PAPER ORIGINAL | | | SOILS REPORT PROVIDED AS PAPER ORIGINAL | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2019-01-03 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2019-01-03 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2019-01-02 |
Time |
14:58 |
Sent To |
|
|
| Notes |
| 2019-01-03 10:18:36 | PASS PROVISO | | | 1) PROVIDE RETURN AIR IN STAFF ROOM # 7 | | | PER SECTION 601.6 BALANCED RETURN AIR. | | | 2017 FBC (M) | | | 2) REFER TO SECTION 601.6 BALANCED RETURN AIR | | | IN RECEPTION ROOM. 2017 FBC (M) | | | 3) REFER TO SECTION 606.2 WHERE REQUIRED | | | PROVIDE LITERATURE ON AIR HANDLER # 1 SHOWING | | | FAN SPEEDS. | | | HAVE INFORMATION ON SITE AT 1ST INSPECTION. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2018-11-01 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2018-11-01 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2018-10-31 |
Time |
11:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2019-02-19 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-02-19 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-02-19 |
Time |
16:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2019-01-17 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-01-17 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-01-17 |
Time |
09:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-11-13 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-11-13 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-11-13 |
Time |
09:51 |
Sent To |
|
|
| Notes |
| 2018-11-13 09:51:41 | 1ST REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. THE SINGLE OCCUPANT BATHROOM IN THE PRIVATE OFFICE | | | #2 IS REQUIRED TO COMPLY WITH SOME ACCESSIBILITY. | | | A) THE DOOR SHALL COMPLY WITH FBC ACC 603.2.3 EXCEPTION | | | #1. | | | B) THE EXCEPTIONS FOR THE SINGLE OCCUPANT BATHROOM ARE | | | THE FOLLOWING. | | | 1) THE HEIGHT OF THE TOILET FBC ACC 604.4 EXCEPTION #1 | | | 2) THE GRAB BAR DO NOT NEED TO BE INSTALLED BUT THE | | | REINFORCEMENT BACKING SHALL BE INSTALLED IN THE WALLS. | | | FBC ACC 604.5 EXCEPTION #1 | | | 3) THE LAVATORY FBC ACC 606.2 EXCEPTION #2 606.3 | | | EXCEPTION #1 | | | C) !!!!THESE ARE REQUIRED SHOW COMPLIANCE WITH THE | | | FOLLOWING!!!! | | | 1) THE TOILET SHALL COMPLY WITH FBC ACC 604.2 | | | LOCATION.THE WATER CLOSET SHALL BE POSITIONED WITH A | | | WALL OR PARTITION TO THE REAR AND TO ONE SIDE. THE | | | CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES (405 | | | MM) MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR | | | PARTITION, | | | 2) THE TOILET SHALL COMPLY WITH FBC ACC 604.3.1 SIZE. | | | CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES | | | MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND | | | 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR | | | WALL. | | | AND FBC ACC 604.3.2 OVERLAP. THE REQUIRED CLEARANCE | | | AROUND THE WATER CLOSET SHALL BE PERMITTED TO OVERLAP | | | THE WATER CLOSET, ASSOCIATED GRAB BARS, DISPENSERS, | | | SANITARY NAPKIN DISPOSAL UNITS, COAT HOOKS, SHELVES, | | | ACCESSIBLE ROUTES, CLEAR FLOOR SPACE AND CLEARANCES | | | REQUIRED AT OTHER FIXTURES, AND THE TURNING SPACE. NO | | | OTHER FIXTURES OR OBSTRUCTIONS SHALL BE LOCATED WITHIN | | | THE REQUIRED WATER CLOSET CLEARANCE. | | | | | | 2. ALL BATHROOMS SHALL COMPLY WITH FBC ACC 604.7 | | | DISPENSERS. TOILET PAPER DISPENSERS SHALL COMPLY WITH | | | 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES | | | MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE | | | CENTERLINE OF THE DISPENSER. | | | | | | 3. THE GRAB BARS IN THE COMMON BATHROOMS SHALL COMPLY | | | WITH FBC ACC 604.5.1 SIDE WALL. THE SIDE WALL GRAB BAR | | | SHALL BE 42 INCHES LONG MINIMUM, LOCATED 12 INCHES | | | MAXIMUM FROM THE REAR WALL AND EXTENDING 54 INCHES | | | MINIMUM FROM THE REAR WALL. | | | 604.5.2 REAR WALL. THE REAR WALL GRAB BAR SHALL BE 36 | | | INCHES LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF | | | THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 | | | INCHES MINIMUM ON THE OTHER SIDE. | | | | | | 4. THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE | | | GRIPPING SURFACE. PER FBC ACC 609.4 | | | | | | 5. THE BREAK ROOM SINK SHALL COMPLY WITH FBC ACC 606.2 | | | CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING WITH, | | | POSITIONED FOR A FORWARD APPROACH, AND KNEE AND TOE | | | CLEARANCE COMPLYING WITH SHALL BE PROVIDED. | | | 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED | | | WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER | | | SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR | | | GROUND | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2019-01-17 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-01-17 |
Time |
18:33 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-01-17 |
Time |
18:31 |
Sent To |
|
|
| Notes |
| 2019-01-17 18:33:47 | GAF SINGLE PLY PLY ROOFING SYSTEMS NOA 18-0523.05 | | | SUBMITTED. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-11-16 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-11-16 |
Time |
17:01 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-11-16 |
Time |
17:01 |
Sent To |
|
|
| Notes |
| 2018-11-16 17:02:26 | 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | | 61G20-3.001 FOR: | | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | | SUBMITTAL) | | | | | | A) FLAT ROOF FOR METAL DECK AND CONCRETE DECK AS SHOWN | | | ON PLANS. . AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | | DESIGN PRESSURES OF SEC. 1609 FBC. NOTE: IF THE | | | SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR | | | ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117 | | | CALCULATIONS ARE REQUIRED. | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2019-02-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-02-20 |
Time |
11:59 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-02-20 |
Time |
11:59 |
Sent To |
|
|
| Notes |
| 2019-02-15 11:01:02 | 2/14/19 HARD COPY ROUTED TO JGOMEZ FOR REVIEW. LEM |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2019-02-14 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-02-14 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-02-14 |
Time |
10:18 |
Sent To |
|
|
| Notes |
| 2019-02-14 10:18:55 | 1) NEED ARCHITECT'S DIGITAL SIGNATURE ON SHEET A.01 | | | TITLE SHEET. | | | | | | 2) SOIL TEST REPORT SUBMITTED NEEDS SURVEYORS ORIGINAL | | | SEAL AND SIGNATURE OR DIGITAL SIGNATURE WHEN SUBMITTING | | | DOCUMENTS FOR PUBLIC RECORDS. CHAPTER 472 F.S. | | 2019-02-13 12:34:00 | ELECTRICAL SHEETS OK. | | | | | 2019-02-13 11:14:06 | LANDSCAPING SIGNATURES NOT REQUIRED AS A SEPARATE | | | PERMIT WILL BE APPLICAD FOR. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2019-01-08 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-01-08 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-01-08 |
Time |
09:53 |
Sent To |
|
|
| Notes |
| 2019-01-08 09:53:31 | PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON | | | RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A | | | DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY | | | VERIFICATION. SHEETS A.01, L1.0, L1.1, L1.2, E.02, | | | E.03, E.04, M.01, AND P.02 NEED CORRECTION. PROVIDE | | | CORRECTION. WPB FBC 107.1; FS 471/481 |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2018-10-23 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-10-23 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-10-23 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2018-10-23 14:17:22 | PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON | | | RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A | | | DIGITAL SIGNATURE. SHEETS A.01, L1.0, L1.1, AND L1.2 | | | ARE MISSING THE REQUIRED SIGNATURES. PROVIDE | | | CORRECTION. WPB FBC 107.1; FS 471/481 |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
1 |
Status |
N |
Date |
2019-04-10 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-04-10 |
Time |
09:07 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-04-10 |
Time |
09:03 |
Sent To |
|
|
| Notes |
| 2019-04-10 09:10:05 | SUBMITTAL BUILDING REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | 1- RESIDENT INSPECTOR AGREEMENT SUBMITTED NEEDS TO BE | | | ORIGINAL. COPIES ARE NOT ALLOWED. PROVIDE THREE | | | ORIGINAL LETTERS. | | | NOTE: SPECIAL INSPECTOR IS NOT REQUIRED FOR THIS | | | BUILDING. THIS IS VOLUNTARILY REQUESTED BY THE | | | CONTRACTOR. | | | | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2019-02-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2019-02-11 |
Time |
14:28 |
Sent To |
|
|
| Notes |
| 2019-02-11 14:24:56 | **************************ZONING | | | REVIEW******************************* | | | | | | LANDSCAPE PLANS SHOULD BE SUBMITTED AS A SEPARATE | | | PERMIT TO BE REVIEWED BY THE CITY'S LANDSCAPE ENGINEER. | | | THERE WAS AN APPROVED LANDSCAPE PLAN THAT WAS WITH THE | | | SITE PLAN. PLACED A HOLD ON THE CO FOR FINAL LANDSCAPE | | | INSPECTION. | | | | | | | | | THANKS, | | | ALANA WOOTEN | | | ASSOCIATE PLANNER | | | PLANNING DIVISION | | | 561-822-1449 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2019-01-07 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2019-01-07 |
Time |
|
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2019-01-07 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2018-11-26 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
2018-11-26 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-11-26 15:53:36 | **********************ZONING REVIEW | | | FAILED************************** | | | | | | THERE WAS A CONDITION OF APPROVAL FOR THIS SITE PLAN, | | | THAT THE ENTIRE EXISTING SIDEWALK ON S. DIXIE HWY WILL | | | BE REPLACED WITH CONCRETE. | | | | | | | | | ALANA WOOTEN | | | ASSOCIATE PLANNER | | | PLANNING DIVISION | | | 561-822-1449 |
|
|