| Plan Review Stops For Permit 18081315 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2019-02-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-02-05 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-02-05 |
Time |
13:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-12-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-12-08 |
Time |
12:11 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-12-08 |
Time |
12:11 |
Sent To |
|
|
| Notes |
| 2018-12-08 12:13:49 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. 2ND REVIEW, IT IS STILL NOT CLEAR WHAT CHANGED. SOME | | | PAGES HAVE NO REVISION CLOUDS OR DELTAS AND NO | | | NARRATIVE. OTHERS HAVE ILLEGIBLE DELTAS. | | | | | | FOR INSTANCE: A0.02 (AND OTHER PAGES) HAVE LIGHT | | | CLOUDS, ILLEGIBLE DELTA (REVISION INFORMATION). SINCE | | | THERE ARE NO DARK CLOUDS, IT APPEARS NO CHANGES WERE | | | DONE TO THESE PAGES. PLEASE EITHER REMOVE OR CLEARLY | | | INDICATE CHANGES WHICH NEED REVIEW. | | | | | | A NARRATIVE MAY BE HELPFUL. | | | | | | 3.WHEN RESUBMITTING, PLEASE INDICATE "0" FOR REVISED | | | SHEETS (NO ADDITIONAL FEES WILL BE APPLICABLE). IF YOU | | | SEND AN EMAIL AFTER RESUBMITTING, YOUR NEXT | | | **BUILDING** REVIEW WILL BE PRIORITIZED IF POSSIBLE. | | | | | | 4. IT APPEARS THAT ONE SET OF OLD SHEETS WAS REMOVED | | | (PLEASE LEAVE ALL DOCUMENTS IN THE BUILDING DIVISION). | | | THE THREE SETS OF MEPS ARE NOT THE SAME, CORRELATE, FBC | | | 107. | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-10-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-10-06 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-10-06 |
Time |
13:47 |
Sent To |
|
|
| Notes |
| 2018-10-06 14:06:01 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC 107, A0.02, A0.03, OTHER PAGES, TEXT INDICATING | | | THE REVISION NUMBER IS NOT LEGIBLE. THE RECORD SET | | | SHOWS ONE REVISION DATED 10/20/17. I WAS UNABLE TO | | | LOCATE REVISION 2 CHANGES, NOT CLEAR WHAT CHANGED. | | | | | | 2. THE PLANS ARE TOO LIGHT TO BE EASILY LEGIBLE AND | | | WILL NOT BE LEGIBLE AFTER SCANNING, FBC 107. PLEASE | | | REPRINT. | | | | | | 3.WHEN RESUBMITTING, PLEASE INDICATE "0" FOR REVISED | | | SHEETS (NO ADDITIONAL FEES WILL BE APPLICABLE). | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2019-01-30 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-01-30 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-01-30 |
Time |
07:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2018-11-06 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-11-06 |
Time |
12:21 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-11-06 |
Time |
12:21 |
Sent To |
|
|
| Notes |
| 2018-11-06 12:21:21 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. THIS WAS ORIGINALLY PASSED WITH 6 ELECRTICAL SHEETS | | | SHOWING REVISIONS. THIS SUBMISSION INCLUDED A FULL | | | ELECTRICAL SET THAT DID NOT SHOW REVISIONS, AND THERE | | | WAS ONLY ONE COPY. PROVIDE TWO COPIES OF SHEETS THAT | | | ARE REVISED AND INDICATE REVISIONS ON PLAN SHEETS. WPB | | | FBC 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-11-06 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-09-19 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-09-19 |
Time |
11:42 |
Sent To |
|
|
| Notes |
| 2018-11-06 12:12:21 | CHANGED STATUS TO FAIL AFTER SECOND REVIEW, SEE NOTES | | | FROM SECOND REVIEW. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2019-01-10 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-01-10 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2019-01-10 |
Time |
11:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-09-11 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-09-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-09-07 |
Time |
15:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-02-05 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-02-05 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-01-07 |
Time |
14:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-12-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-12-10 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-10-23 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2018-12-08 12:14:27 | 12/8 REMOVED FROM BOARD; ROUTED TO GJOHNSON DESK FOR | | | RESTAMP | | | | | | | | 2018-10-24 14:14:44 | C03 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-10-09 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-10-09 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-08-27 |
Time |
13:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2019-01-23 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-01-23 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-01-23 |
Time |
13:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2018-11-19 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-11-19 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-11-19 |
Time |
16:32 |
Sent To |
|
|
| Notes |
| 2018-11-19 17:10:07 | 1ST REVIEW FBC-2014 MECHANICAL | | | REVISION #18081315 | | | MASTER #17040807 | | | 11/19/18 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE- 2014 | | | FBC M- FLORIDA MECHANICAL CODE- 2014 | | | FBC EC- FLORIDA ENERGY CONSERVATION- 2014 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS- 2010 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS M2.1.1, M2.2.1, & M6.1: THE TOTAL AIRFLOW | | | CFMS SHOWN ON THE 1ST AND 2ND FLOOR DUCT LAYOUT PLANS | | | EXCEED THE CAPACITIES OF THE RTU'S 1 & 2, AND OF THE | | | MAIN SUPPLY TRUNKS FOR EACH SYSTEM. FOR EXAMPLE, THE | | | FIRST FLOOR PLAN (M2.1.1) SHOWS A TOTAL OF 26,600 CFMS | | | OF SUPPLY AIR FOR RTU-1 WHICH HAS A MAXIMUM CAPACITY OF | | | 10,118 CFMS. IN ADDITION THE 22X16 IS FAR UNDERSIZED TO | | | SUPPLY 19,400 CFMS OF AIR. PLEASE REVIEW AND CORRECT- | | | SECTION 603.1 FBC M | | | | | | 2) PROVIDE TWO COMPLETE SETS OF REVISED MECHANICAL | | | DRAWINGS FOR REVIEW- ONLY ONE SET WAS SUBMITTED- | | | SECTION 107.1 WPB. | | | | | | 3) PLEASE NOTE THAT COMMISSIONING OF THE MECHANICAL | | | SYSTEMS IS REQUIRED FOR FINAL APPROVAL AND CO OF THE | | | BUILDING- SECTION C408.2 FBC EC. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2018-09-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-09-21 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-09-21 |
Time |
08:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2019-01-28 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-01-28 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-01-28 |
Time |
08:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2018-12-10 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-12-10 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-12-10 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2018-12-10 14:32:03 | SEE BUILDING AND ELECTRIC NOTES. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2018-10-09 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-10-09 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-10-01 |
Time |
14:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2019-01-14 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2019-01-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2019-01-14 |
Time |
|
Sent To |
|
|
| Notes |
| 2019-01-14 15:30:39 | PROVISOS FROM 9/5/2018 REVIEW STILL APPLY. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-09-05 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2018-09-05 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
2018-08-31 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-09-05 12:54:21 | ZONING APPROVED WITH THE FOLLOWING PROVISOS: | | | | | | 1.) MINOR SITE PLA AMENDMENT REQUIRED TO MATCH APPROVED | | | PLAN SET PRIOR TO THE ISSUANCE OF FINAL CERTIFICATE OF | | | OCCUPANCY (C.O.). | | | | | | 2.) REPLAT OF THE PROPERTY REQUIRED PRIOR TO THE | | | ISSUANCE OF THE FINAL C.O. | | | | | | CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. |
|
|