Plan Review Details - Permit 18081226
Plan Review Stops For Permit 18081226
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-02-07 Cont ID  
Sent By pvalenti Date 2019-02-07 Time 16:34 Rev Time 0.00
Received By pvalenti Date 2019-02-07 Time 16:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-12-08 Cont ID  
Sent By shill Date 2018-12-08 Time 12:44 Rev Time 0.00
Received By shill Date 2018-12-08 Time 12:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-22 Cont ID  
Sent By shill Date 2018-09-22 Time 16:33 Rev Time 0.00
Received By shill Date 2018-09-22 Time 16:33 Sent To  
Notes
2018-09-22 16:39:58****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. PROVIDE A SITE PLAN WHICH SHOWS LOCATION OF THIS
 UNIT. I WAS NOT ABLE TO FIND THE PREVIOUS PREMIT FOR
 THIS SPACE, SO COULD NOT DETERMINE WHETHER OR NOT THIS
 IS A CHANGE OF OCCUPANCY. THE MALL'S DIRECTORY ONLINE
 SHOWS "EZ RELAXATION" AT UNIT 213, BUT ANOTHER LINK ON
 THE MALL'S WEBSITE (HTTPS://WWW.PALMBEACHOUTLETS.COM/ST
 ORE/EZ-RELAXATION/2138935542/) SHOWS EZ RELAXATION AT
 UNIT E115.
  
 PROVIDE CONFIRM THAT THE PROPOSED NEW BUSINESS REPLACES
 EZ RELAXATION.
  
 IF IT DOES NOT, WHAT TENANT DOES THIS REPLACE? IF THIS
 IS A CHANGE OF OCCUPANCY, REVISE PLAN TO STATE THIS AND
 SHOW COMPLIANCE WITH FBC EB CHAPTER 10.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-11-09 Cont ID  
Sent By jpearson Date 2018-11-09 Time 17:52 Rev Time 0.00
Received By jpearson Date 2018-11-09 Time 17:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-02 Cont ID  
Sent By jpearson Date 2018-09-02 Time 11:00 Rev Time 0.00
Received By jpearson Date 2018-09-02 Time 11:00 Sent To  
Notes
2018-09-02 10:55:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE PALM BEACH OUTLETS MANAGEMENT STAMP IS REQUIRED
 ON THE PLANS OR A SEPARATE LETTER APPROVING THE PLANS
 NEEDS TO BE INCLUDED WITH THIS PERMIT SUBMITTAL PRIOR
 TO ELECTRIC APPROVAL. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-11-08 Cont ID  
Sent By scaldero Date 2018-11-08 Time 09:58 Rev Time 0.00
Received By scaldero Date 2018-11-08 Time 09:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-08-28 Cont ID  
Sent By scaldero Date 2018-08-28 Time 10:42 Rev Time 0.00
Received By scaldero Date 2018-08-28 Time 10:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-02-07 Cont ID  
Sent By pvalenti Date 2019-02-07 Time 16:34 Rev Time 0.00
Received By pvalenti Date 2019-01-31 Time 13:54 Sent To  
Notes
2019-02-01 13:54:59B20

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-20 Cont ID  
Sent By jesmith Date 2018-12-20 Time 10:40 Rev Time 0.00
Received By jesmith Date 2018-12-20 Time 10:40 Sent To  
Notes
2018-12-18 15:57:3412/18 TO JESMITH DESK; REMOVED FROM BOARD / S.HILL
2018-11-06 15:17:21B26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-22 Cont ID  
Sent By shill Date 2018-09-22 Time 16:49 Rev Time 0.00
Received By shill Date 2018-08-24 Time 13:54 Sent To  
Notes
2018-08-27 13:54:47B30

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-12-20 Cont ID  
Sent By ccole Date 2018-12-20 Time 17:11 Rev Time 0.00
Received By ccole Date 2018-11-20 Time 16:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-09-12 Cont ID  
Sent By ccole Date 2018-09-12 Time 11:28 Rev Time 0.00
Received By ccole Date 2018-09-11 Time 08:04 Sent To  
Notes
2018-09-12 12:04:211ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18081226
 9/12/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE
 MANICURE AND PEDICURE STATIONS, AND THE BEAUTY SALON
 AREA- SEE TABLE 403.3.1.1 FBC M. PLEASE NOTE THAT THE
 PLAN DOES NOT APPEAR TO SHOW EXHAUST VENTILATION IN THE
 BEAUTY SALON AREA.
  
 2) PROVIDE AIR BALANCE CALCULATIONS AND A SEQUENCE OF
 OPERATION FOR THE EXHAUST SYSTEMS- SECTION 501.4 FBC M.
 PLEASE NOTE THAT INSTALLATION OF AN ERV MAY BE REQUIRED
 PER SECTION C403.2.7 FBC EC.
  
 3) PROVIDE A DETAIL THAT INDICATES HOW THE FUMES AT THE
 PEDICURE CHAIRS ARE BEING CAPTURED AT THEIR SOURCES-
 TABLE 403.3.1.1 FOOTNOTE H FBC M
  
 4) M-1: THE PLAN APPEARS TO SHOW RECIRCULATION OF THE
 AIR FROM THE NAIL AND BEAUTY SALON IINTO THE RECEPTION
 AREA, THE MASSAGE AND WAX ROOMS, AND THE BACK OF HOUSE
 AREAS WHICH IS PROHIBITED PER TABLE 403.3.1.1 FOOTNOTE
 B FBC M.
  
 5) M-1: PROVIDE A DUCT SMOKE DETECTOR IN THE SUPPLY
 SIDE OF RTU-5- SECTION 606.2.1 FBC M.
  
 6) M-1: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE NEW
 AHU-1- SECTION 307 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-02-05 Cont ID  
Sent By jesmith Date 2019-02-05 Time 08:24 Rev Time 0.00
Received By jesmith Date 2019-02-05 Time 07:54 Sent To  
Notes
2019-02-05 08:24:22APPROVED
 PROVISO
 RE: WATER HEATER DETAIL; EXPANSION TANK TO BE LOCATED
 DOWNSTREAM OF ALL CHECK VALVES PER FBC PL 607.3. SEE
 RED LINE COMMENTS AT DETAIL PLAN PAGE P3.0
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-12-20 Cont ID  
Sent By jesmith Date 2018-12-20 Time 10:29 Rev Time 0.00
Received By jesmith Date 2018-12-18 Time 14:09 Sent To  
Notes
2018-12-18 14:25:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 2ND REVIEW: DENIED
 PLUMBING COMMENTS:
  
 1. RE: ATTACHED SPEC SHEET FOR PEDICURE CHAIRS BY
 OWNER; SPEC SHEET INDICATES THAT BACKFLOW PREVENTION IS
 BY OTHERS.
 A) SPECIFY BACKFLOW PREVENTION DEVICE FOR HOT AND COLD
 WATER SUPPLY LINES COMPLYING WITH THE REQUIREMENTS OF
 FBC PLUMBING 608.2 AND SHOW ON PLAN PER WPB FBC
 107.2.1.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 PHONE: 561-805-6715
 EMAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-09-18 Cont ID  
Sent By shill Date 2018-09-18 Time 14:15 Rev Time 0.00
Received By jesmith Date 2018-09-18 Time 14:11 Sent To  
Notes
2018-09-18 14:15:281ST REVIEW: FBC 2017 6TH EDITION
 PERMIT 18081226
 PLUMBING COMMENTS: DENIED
  
 1. PROVIDE PROVIDE SMOKE/FIRE STOPPING DETAIL(S) FOR
 RATED GYPSUM ASSEMBLIES. IE. WATER SERVICE PENETRATION
 THROUGH CORRIDOR WALL. WPB AMEND TO FBC 107.2.1
 2. RE: WATER HEATERS
 A. AO SMITH ECRT-80 WATER HEATER IS DISCONTINUED.
 PROVIDE UPDATED WATER HEATER SCHEDULE. WPB AMEND TO FBC
 107.2.1
 B. PROVIDE SCHEDULE AND DETAIL FOR HOT WATER RECIRC
 PUMP; COORDINATE WITH ELECTRICAL. SHOW ALL VALVING,
 INCLUDING CHECK VALVES, AND INTERFACE WITH WATER
 HEATERS. A SINGLE DETAIL INCORPORATING PUMP AND HEATERS
 SHOULD BE PROVIDED. WPB AMEND TO FBC 107.2.1
 C. PROVIDE THERMAL EXPANSION CONTROL IN ACCORDANCE WITH
 FBC PLUMBING 607.3
 D. PROVIDE DRAIN PAN IN ACCORDANCE WITH FBC PLUMBING
 504.7
 3. RE: PLAN SHEET A1.0; SEE NOTE "PEDICURE CHAIRS PER
 OWNER. SEE ATTACHED SPEC SHEET." THERE ARE NO ATTACHED
 SPEC SHEETS. PROVIDE FOR CODE COMPLIANCE REVIEW,
 ESPECIALLY TO DETERMINE THAT THEY COMPLY WITH THE
 REQUIREMENTS OF FBC PLUMBING 608.2
 4. RE: PLAN SHEET A1.0; SEE NOTE "HAIR SINKS PER
 OWNER". PROVIDE SPEC SHEETS FOR CODE COMPLIANCE REVIEW,
 ESPECIALLY TO DETERMINE THAT THEY COMPLY WITH THE
 REQUIREMENTS OF FBC PLUMBING 608.2
 5. RE: WASHER/DRYER:
 A. PROVIDE NOTE "ACCESSIBLE SHUTOFF VALVES REQUIRED"
 PER FBC PLUMBING 606.3
 B. PROVIDE NOTE "PROVIDE WATER HAMMER ARRESTORS " PER
 FBC PLUMBING 604.9
 6. RE: PLAN SHEET A1.0; HC TOILET ROOMS. COMPLY WITH
 2017 FBC ACCESSIBILITY CODE
 A. DIMENSION TOILET ROOMS TO SHOW THE CLEAR SPACE
 AVAILABLE FOR WHEELCHAIR TURNING RADIUS.
 B. MISSING DIMENSION FROM BACKWALL TO SIDE HANDRAIL ON
 FLOOR PLAN.
 C. INSURE THAT TOILET PAPER DISPENSER LOCATION COMPLIES
 WITH FBC ACC 604.9.6
 D. LAVATORIES TO COMPLY WITH FBC ACC 604.8.1.6. NOTE
 DIMENSIONS ON PLAN
 7. RE: PLAN SHEET A1.0; DRINKING FOUNTAIN. COMPLY WITH
 2017 FBC ACCESSIBILITY CODE SECTION 602. DESIGNATE
 FIXTURE ON PLAN AS HC.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6715

Review Stop Z ZONING
Rev No 3 Status P Date 2019-02-05 Cont ID  
Sent By eschneid Date 2019-02-05 Time 15:59 Rev Time 0.25
Received By eschneid Date 2019-02-05 Time 15:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2018-12-14 Cont ID  
Sent By eschneid Date 2018-12-14 Time 16:37 Rev Time 0.25
Received By eschneid Date 2018-12-14 Time 10:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-08-31 Cont ID  
Sent By eschneid Date 2018-08-31 Time 15:20 Rev Time 0.25
Received By eschneid Date 2018-08-31 Time 15:20 Sent To  
Notes
2018-08-31 15:36:02FAILED
  
 1) THE PALM BEACH OUTLETS MANAGEMENT STAMP IS REQUIRED
 ON THE PLANS OR A SEPARATE LETTER APPROVING THE PLANS
 NEEDS TO BE INCLUDED WITH THIS PERMIT SUBMITTAL PRIOR
 TO ZONING APPROVAL.
  
 2) SHEET M-1 STATES THAT THERE WILL BE A NEW CONDENSING
 UNIT MOUNTED ON RAILS ON THE ROOF. PROVIDE SITE LINE
 DRAWINGS VERIFYING THAT THE NEW UNIT MEETS THE PALM
 BEACH OUTLETS ROOFTOP MECHANICAL EQUIPMENT SCREENING
 REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy