Plan Review Details - Permit 18081220
Plan Review Stops For Permit 18081220
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-10-10 Cont ID  
Sent By rgathrig Date 2018-10-10 Time 15:49 Rev Time 0.00
Received By rgathrig Date 2018-10-10 Time 15:49 Sent To  
Notes
2018-10-10 15:50:39PERMIT IS ISSUED WITH THE PROVISO THAT SIGNED AND
 SEALED ENGINEERING WILL BE SUBMITTED PRIOR TO
 INSPECTION

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-09-24 Cont ID  
Sent By cthroop Date 2018-09-24 Time 08:50 Rev Time 0.00
Received By cthroop Date 2018-09-24 Time 08:06 Sent To I
Notes
2018-09-24 08:57:36BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. COMMENT # 4 FROM 1ST REVIEW HAS NOT BEEN ADDRESSED.
 SEE BELOW.
 4) SUBMIT TWO SETS OF THE MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION INSTRUCTIONS FOR THE ELEVATOR. PROVIDE
 DOCUMENTATION THE ELEVATOR COMPLIES WITH ASME A17.1/CSA
 B44. FBC 107.2.1 & FBC-R321.1.
  
 2. SECOND FLOOR PLAN INDICATES A PARAPIT WALL ABOVE
 ELEVATOR HOISTWAY. ROOF FRAMING PLAN APPROVED UNDER
 MPERMIT # 17110548 INDICATES A STANDINJG SEAM METAL
 ROOF IN THIS AREA. PROVIDE A PLAN AND DETAIL FOR THE
 RECONFIGURATION OF THIS ROOF LINE. IF A FLOOT ROOF WILL
 BE INSTALLED, PROVIDE PRODUCT APPROVALS FOR FLAT ROOF
 SYSTEM.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 3. SIGNATURE AND SEAL OF DESIGN PROFESSIONALS ARE
 COPIES. ORIGINAL SIGNATURE AND SEALS ARE REQUIRED.
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-28 Cont ID  
Sent By rmcdouga Date 2018-08-28 Time 17:52 Rev Time 0.00
Received By rmcdouga Date 2018-08-28 Time 17:52 Sent To E
Notes
2018-08-28 18:25:02PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS ON FILE FOR PERMIT #17070538 ARE FOR
 REMODELING A TWO STORY GARAGE/APARTMENT. THERE IS NO
 ELEVATOR SHOWN ON ANY OF THE PLANS THAT ARE FILE WITH
 THE BUILDING DEPARTMENT. IF YOU HAVE AN APPROVED SET OF
 PLANS WITH THE CITY BUILDING DEPARTMENT STAMPS, PLEASE
 BRING THEM IN SO THAT WE MAY MAKE A COPY FOR OUR
 RECORDS.
  
 2) SUBMIT TWO SETS OF FLOOR PLANS SHOWING THE
 DIMENSIONS AND LOCATION OF OF THE ELEVATOR HOISTWAY AND
 THE ELEVATOR EQUIPMENT ROOM. FBC 107.2.1
  
 3) PROVIDE FRAMING DETAILS OF THE ELEVATOR HOISTWAY AND
 ANY SPECIAL FRAMING/BLOCKING REQUIREMENTS. FBC 107.2.1
  
 4) SUBMIT TWO SETS OF THE MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION INSTRUCTIONS FOR THE ELEVATOR. PROVIDE
 DOCUMENTATION THE ELEVATOR COMPLIES WITH ASME A17.1/CSA
 B44. FBC 107.2.1 & FBC-R321.1
  
 3)

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2018-10-09 Cont ID  
Sent By jleahy Date 2018-10-09 Time 17:15 Rev Time 0.00
Received By jleahy Date 2018-10-09 Time 17:15 Sent To  
Notes
2018-10-09 17:16:41SEE JOHN PEARSON'S COMMENTS FROM LAST REVIEW,
 INFORMATION FOR THE ELEVATOR IS SHOWN ON THE MASTER
 PALN 17110548

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2018-09-20 Cont ID  
Sent By jpearson Date 2018-09-20 Time 14:03 Rev Time 0.00
Received By jpearson Date 2018-09-20 Time 14:03 Sent To B
Notes
2018-09-20 14:02:06ELEVATOR SHOWN ON PERMIT 17110548, WHICH IS ALREADY
 APPROVED FOR ELECTRICAL. NO FURTHER REVIEW NECESSARY.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-29 Cont ID  
Sent By jpearson Date 2018-08-29 Time 08:14 Rev Time 0.00
Received By jpearson Date 2018-08-29 Time 08:14 Sent To  
Notes
2018-08-29 08:14:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. PLANS FROM PERMIT
 17070538 DO NOT SHOW ANY WIRING OR LOAD INCLUDED FOR
 ELEVATOR. FS 471.003(2)(H); 471.025; WPB FBC 107.2.1,
 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-10 Cont ID  
Sent By cthroop Date 2018-10-10 Time 15:50 Rev Time  
Received By rgathrig Date 2018-09-18 Time 14:38 Sent To  
Notes
2018-09-19 14:38:24RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-28 Cont ID  
Sent By rmcdouga Date 2018-08-28 Time 17:52 Rev Time 0.00
Received By rmcdouga Date 2018-08-24 Time 16:23 Sent To  
Notes
2018-08-28 16:23:19GIVEN TO RMCDOUGAL