Plan Review Details - Permit 18081189
Plan Review Stops For Permit 18081189
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-10-30 Cont ID  
Sent By skennedy Date 2018-10-30 Time 15:51 Rev Time 0.00
Received By skennedy Date 2018-10-30 Time 15:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-22 Cont ID  
Sent By shill Date 2018-09-22 Time 17:15 Rev Time 0.00
Received By shill Date 2018-09-22 Time 17:15 Sent To  
Notes
2018-09-22 17:19:11****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. PROVIDE A BASIC CODE SUMMARY: OCCUPANCY
 CLASSIFICATION, OCCUPANT LOAD, PREVIOUS OCCUPANCY,
 BUILDING TYPE, SPRINKLERED OR NON SPRINKLERED FBC 107.
  
 2. FBC A 202.3, 203.9, FIGURE 404.2.4.1(A), THE "NEW
 CABINETRY" OBSTRUCTS THE MANEUVERING CLEARANCE
 REQUIRED. NOTE THAT IN WORK AREAS THE OCCUPANT MUST BE
 ABLE TO APPROACH, ENTER AND EXIT THE WORK AREA.
  
 3. FBC A 202.4, AN ACCESSIBLE ROUTE TO THE ALTERED AREA
 IS REQUIRED. REVISE PLAN TO SHOW ACCESSIBLE PARKING,
 ACCESSIBLE ENTRANCE. PARKING WILL REQUIRE A SEPARATE
 PERMIT. PARKING RESTRIPE PERMIT IS TO BE SUBMITTED
 PRIOR TO ISSUANCE OF THIS PERMIT AND RESTRIPE IS TO BE
 COMPLETED PRIOR TO FINAL INSPECTION.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-10-30 Cont ID  
Sent By jleahy Date 2018-10-30 Time 11:06 Rev Time 0.00
Received By jleahy Date 2018-10-30 Time 11:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-10-17 Cont ID  
Sent By jpearson Date 2018-10-17 Time 11:25 Rev Time 0.00
Received By jpearson Date 2018-10-17 Time 11:01 Sent To  
Notes
2018-10-17 11:25:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN PROVIDED SHOWED AN ADDRESS FOR A PROJECT IN
 WELLINGTON. PROVIDE CORRECT PLAN WITH CORRECT ADDRESS.
 WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-17 Cont ID  
Sent By jpearson Date 2018-09-17 Time 12:24 Rev Time 0.00
Received By jpearson Date 2018-09-17 Time 12:05 Sent To  
Notes
2018-09-17 12:24:46CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. THIS PERSON MUST BE A LICENSED DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER.
 PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4
 4. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
 5. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "OLD
 SHEETS".
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-10-16 Cont ID  
Sent By pleduc Date 2018-10-16 Time   Rev Time 0.00
Received By pleduc Date 2018-10-16 Time 13:44 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-08-27 Cont ID  
Sent By pleduc Date 2018-08-27 Time   Rev Time 0.00
Received By pleduc Date 2018-08-27 Time 13:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-30 Cont ID  
Sent By skennedy Date 2018-10-30 Time 15:51 Rev Time 0.00
Received By skennedy Date 2018-10-11 Time 09:29 Sent To  
Notes
2018-10-16 09:31:19B16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-22 Cont ID  
Sent By shill Date 2018-09-22 Time 17:26 Rev Time 0.00
Received By shill Date 2018-08-23 Time 15:16 Sent To  
Notes
2018-08-24 15:16:17B29

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-09-22 Cont ID  
Sent By shill Date 2018-09-22 Time 17:26 Rev Time 0.00
Received By shill Date 2018-09-22 Time 17:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2018-10-25 Cont ID  
Sent By skennedy Date 2018-10-25 Time 15:36 Rev Time 0.00
Received By skennedy Date 2018-10-25 Time 15:36 Sent To  
Notes
2018-10-25 15:36:36SEE 18081337

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-10-24 Cont ID  
Sent By ccole Date 2018-10-24 Time 09:56 Rev Time 0.00
Received By ccole Date 2018-10-24 Time 09:53 Sent To  
Notes
2018-10-24 10:31:152ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18081189
 10/24/18
  
 CODES IN EFFECT:
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 THIS IS THE SECOND REVIEW OF THE PLANS AND THE COMMENTS
 FROM THE 1ST REVIEW (LISTED BELOW) STILL EXIST. IN
 ADDITION THERE ARE NEW OFFICES IN EACH TENANT SPACE
 THAT WILL REQUIRE VENTILATION AND ADEQUATE HEATING PER
 THE FBC M.
  
 PLEASE FORWARD THESE COMMENTS TO THE DESIGN
 PROFESSIONAL IN CHARGE AND URGE HIM/HER TO CONTACT ME
 AT THEIR EARLIEST CONVENIENCE TO DISCUSS THE ISSUES.
  
 1) REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3.1 FBC-17 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) SHEET 3: SHOW THE LOCATIONS OF THE AIR HANDLERS AND
 PROVIDE BASIC INFORMATION- MAKES AND MODELS, COOLING
 AND HEATING CAPACITIES.
  
 3) SHEET 3: INDICATE HOW THE RETURN AIR SYSTEM WILL
 FUNCTION. NO DETAILS ARE PROVIDED.
  
 2) SHEET 3: PROVIDE AN AIR DEVICE SCHEDULE AND A DETAIL
 SHOWING HOW THE NEW SOFFITS AND AC VENTS WILL BE
 CONSTRUCTED AND SUPPORTED.
  
 3) SHEET 3: PROVIDE THE SUPPLY CFMS AT EACH SOFFIT VENT
 AND RETURN CFMS AT EACH GRILL OR VENT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-09-18 Cont ID  
Sent By ccole Date 2018-09-18 Time 07:24 Rev Time 0.00
Received By ccole Date 2018-09-18 Time 07:24 Sent To  
Notes
2018-09-18 07:36:101ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18081189
 9/18/18
  
 CODES IN EFFECT:
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3.1 FBC-17 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) SHEET 3: SHOW THE LOCATIONS OF THE AIR HANDLERS AND
 PROVIDE BASIC INFORMATION- MAKES AND MODELS, COOLING
 AND HEATING CAPACITIES.
  
 3) SHEET 3: INDICATE HOW THE RETURN AIR SYSTEM WILL
 FUNCTION. NO DETAILS ARE PROVIDED.
  
 2) SHEET 3: PROVIDE AN AIR DEVICE SCHEDULE AND A DETAIL
 SHOWING HOW THE NEW SOFFITS AND AC VENTS WILL BE
 CONSTRUCTED AND SUPPORTED.
  
 3) SHEET 3: PROVIDE THE SUPPLY CFMS AT EACH SOFFIT VENT
 AND RETURN CFMS AT EACH GRILL OR VENT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
 HTTPS://WWW.SURVEYMONKEY.COM/R/WESTPALMBEACHCONSTRUCTIO
 NSERVICES
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-10-30 Cont ID  
Sent By jesmith Date 2018-10-30 Time 13:35 Rev Time 0.00
Received By jesmith Date 2018-10-30 Time 13:34 Sent To  
Notes
2018-10-30 13:34:432ND REVIEW:
 PLUMBING COMMENTS: APPROVED
 PROVISO
  
 1. SEE RED LINE OF WATER CLOSET LOCATION PLACED
 DIAGONALLY FROM THE DOOR.
 2. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL.
  
  
  
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-09-19 Cont ID  
Sent By shill Date 2018-09-19 Time 15:20 Rev Time 0.00
Received By jesmith Date 2018-09-19 Time 15:19 Sent To  
Notes
2018-09-19 14:59:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW:
 PERMIT 18081189
 PLUMBING COMMENTS: DENIED
  
 1. SKETCHES PROVIDED BY HARRY BARBER PLUMBING, INC. DO
 NOT REFLECT PLAN LAYOUT. IS ONE OF THE EXISTING TOILET
 ROOMS TO BE RECONFIGURED. PLEASE CLARIFY AND IF SO,
 PLEASE NOTE ON PLANS SHOWING EXISTING, THEN PROPOSED.
 2. THE PROJECT TITLE BLOCK ON PLAN PAGES 4 AND 5 ARE
 NOT THE SAME AS PAGES 1,2 AND 3. PLEASE CLARIFY.
 3. PROVIDE DESIGN OCCUPANT LOAD CALCULATIONS SO THAT
 MINIMUM FIXTURE REQUIREMENTS MAY BE DETERMINED. FBC
 SECTION 1004
 3. PROVIDE ON PLUMBING PLAN IN ACCORDANCE WITH WPB FBC
 107.3.5.1.3, THE FOLLOWING:
 A. MINIMUM PLUMBING FACILITIES PER FBC PL 403.1 AND
 TABLE 403.1. (SEE NOTE 3)
  *PER FBC PL TABLE 403.1; MERCANTILE, FURNISH ONE (1)
 DRINKING FOUNTAIN WHICH COMPLIES WITH FBC ACC 602,
 211.2 NOTE EXCEPTION IN FBC PL 410.
  *PER FBC PL TABLE 403.1; MERCANTILE, FURNISH ONE (1)
 SERVICE SINK.
 B. WATER SUPPLY PIPING PLAN LAYOUT AND RISER DIAGRAM
 NOTING THE WORK TO BE DONE INTEGRATE WITH THE EXISTING.
 CLOUD NEW WORK.
 C. SANITARY PLAN LAYOUT AND RISER DIAGRAM NOTING THE
 WORK TO BE DONE INTEGRATE WITH THE EXISTING. CLOUD NEW
 WORK.
 D. PROVIDE SCHEDULE FOR INSTA HOT WATER HEATER. IF NOT
 TANKLESS THEN PROVIDE FOR T&P RELIEF, DRAIN PAN AND PAN
 PER FBC PL SECTION 504. INSURE THAT IT WILL MEET THE
 HOT WATER DEMAND OF FIXTURES SERVICED.
 E. PER FBC PL 416.5, PROVIDE TEMPERED WATER FROM
 LAVATORIES AND GROUP WASH FIXTURES LOCATED IN PUBLIC
 TOILET FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.
 4. PER WPB FBC, PLAN (EACH SHEET OF BOTH COPIES) IS
 REQUIRED TO BEAR THE NAME AND BE SIGNED AND SEALED BY
 THE PERSON RESPONSIBLE FOR THE DESIGN. THIS PERSON MUST
 BE A LICENSED DESIGN PROFESSIONAL OR THE PLUMBING
 CONTRACTOR QUALIFIER. PROVIDE CORRECTION. WPB FBC
 107.1, 107.2; FS 471, 481
 5. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. CONTINGENT UPON REVIEW BY BUILDING, CONSTRUCTION
 VALUE IS YET TO BE DETERMINED. WPB FBC 109 UPON
 DETERMINATION OF SAID VALUE, ACCESSIBILITY FOR UP TO
 20% OF SAID VALUE SHALL BE APPLIED UPGRADE THE
 ACCESSIBILITY REQUIREMENTS AS NOTED IN FAC 202.4.1.
 6. PLANS SHALL PROVIDE INFORMATION INCLUDING DIMENSIONS
 AND DETAILS SHOWING COMPLIANCE INCLUDING SHOWING AND
 IDENTIFYING ACCESSIBLE BATHS PER WPB FBC 107.3.5.1(10)
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6715
  