Plan Review Details - Permit 18081181
| Plan Review Stops For Permit 18081181 |
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2018-09-25 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-09-25 |
Time |
03:55 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-09-25 |
Time |
03:08 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-08-29 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-08-29 |
Time |
13:55 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-08-29 |
Time |
13:48 |
Sent To |
I |
|
| Notes |
| 2018-08-29 13:55:02 | SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES USED | | | TO SIZE THE PE LINE TO THE NEW TANKLESS WATER HEATER OR | | | PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH | | | SIZING TABLE(S) FROM THE GAS CODE OR OTHER STANDARD | | | THAT WERE USED IN THE DESIGN OF THIS GAS SYSTEM. REFER | | | TO THE 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND | | | TABLES 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC. | | | G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3. A 3/4 OR | | | 1 INCH APPEARS TO BE UNDERSIZED FOR THE DISTANCE BASED | | | ON THE LONGEST RUN. | | | | | | . | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-09-25 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-09-25 |
Time |
03:55 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-09-20 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2018-09-21 11:37:07 | RESUB ROUTED TO TKLARGE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-08-29 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-08-29 |
Time |
13:55 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-08-23 |
Time |
12:33 |
Sent To |
|
|
| Notes |
| 2018-08-24 12:33:31 | PLUMB <5K |
|
|
|