| 2018-08-29 12:02:46 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE NRTL(NATIONALLY RECOGNIZED TESTING |
| | LABRATORY) FOR EXAMPLE UL,CSA,ETL CERTIFICATION AND |
| | LISTING FOR "WOOD POLE TO REMAIN FOR EXISING POWER |
| | SERVICE" 110.3B NEC |
| | |
| | 2. PROVIDE NRTL(NATIONALLY RECOGNIZED TESTING |
| | LABRATORY) FOR EXAMPLE UL,CSA,ETL CERTIFICATION AND |
| | LISTING FOR PROPOSED IRRIGATION PUMP ON PLAN. 110.3B |
| | NEC |
| | |
| | 3. PROVIDE NRTL(NATIONALLY RECOGNIZED TESTING |
| | LABRATORY) FOR EXAMPLE UL,CSA,ETL CERTIFICATION AND |
| | LISTING FOR ALL OTHER "EXISTING WOOD POLES TO REMAIN" |
| | WHAT IS MOUNTED ON WOODEN POLES? WHAT IS THE WIND LOAD |
| | RATED FOR OF WOODEN POLES? 110.3B NEC |
| | |
| | 4. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, FOR PUMP, ALL NEW LIGHTING, TRANSFORMERS, AND |
| | RECEPTACLES, THE WIRE AND BREAKER SIZE FOR THESE |
| | CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE |
| | TO COMPLY WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; |
| | WPB FBC 107.3.5; FBC RE E3706.2, E3902 |
| | |
| | 5. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS. NEC 220; |
| | |
| | 6. VALUE IS EXTREMELY LOW FOR AMOUNT OF WORK. RAISE |
| | VALUE TO REALISTIC PRICE OR VALUE OF WORK WILL BE SET |
| | BY BUILDING OFFICIAL. |
| | |
| | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WPB |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |