| Plan Review Stops For Permit 18081131 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-12-10 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-12-10 |
Time |
07:33 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-11-29 |
Time |
14:25 |
Sent To |
|
|
| Notes |
| 2018-12-10 07:38:07 | PROVISO: | | | REVIEW EXPIRED PERMITS WITH DEVELOPEMENT SERVICES AND | | | HAVE THEM REVOKED OR FINALED OUT (PRIOR TO FINALS ON | | | 18081131) | | | PCN 74434306000001030 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER I | | | [email protected] | | | 561-805-6718 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-10-23 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-10-23 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-10-22 |
Time |
09:19 |
Sent To |
|
|
| Notes |
| 2018-10-23 10:23:43 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 18081131 | | | REVIEWED: OCTOBER 23, 2018 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER I | | | [email protected] | | | 561-805-6718 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC ENERGY = FBC ENERGY CONSERVATION | | | | | | 1. SHEET LS1.0 AND LS2.0 SHOWS TWO DOORS THAT ACCESS | | | THE AREA OF WORK. WHY ARE THERE EXIT SIGNS THAT APPEAR | | | TO LEAD INTO THE AREA OF WORK WHEN EXITS ARE NOT IN | | | THAT DIRECTION? | | | | | | 2. THERE ARE OPEN PERMITS ON THIS PROPERTY THAT ARE | | | EXPIRED STATUS. PLEASE REVIEW THESE PERMITS AND CONTACT | | | US SO THAT THESE CAN BE CLOSED OUT OR PUT IN REVOKED | | | STATUS. | | | YOU CAN LOOK UP PAST PERMITS FROM WEBSITE LISTED BELOW. | | | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/ENTITY/LOGIN_MAI | | | N.ASPX | | | SEARCH BY PCN AND CLICK ACTIVITY TAB TO LIST ALL | | | PERMITS SHOWN IN SYSTEM. | | | WE ARE LOOKING TO CLEAR ANY PERMIT THAT SAYS EXPIRED. | | | | | | 3. PREVIOUS PERMIT 17080284 WAS SUBMITTED IN PAPER FORM | | | AND WE STILL HAVE THIS IN FILE. THIS CAN BE PUT IN | | | REVOKED STATUS, BUT WHAT DO YOU WANT TO DO WITH THE | | | PAPER. DO YOU WANT IT BACK, OR CAN WE DISCARD THE | | | PLANS? | | | | | | NOTE: | | | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW | | | OF MATERIALS REQUESTED. | | | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS | | | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | | NEED "VOID", RENDERING THEM NOT USABLE. | | | | | 2018-08-23 07:44:01 | **BUILDING PLANS EXAMINER TO EVALUATE REVOCATION OF | | | APPLICATION NUMBER 17080284 AS THIS APPLICATION IS FOR | | | WORK IN THE SAME AREA AND THE APPLICANT HAS INDICATED | | | THE WORK FOR 17080284 NEVER COMMENCED** |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2018-09-25 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-09-25 |
Time |
07:54 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-09-25 |
Time |
07:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-11-08 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2018-11-08 |
Time |
08:58 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2018-11-08 |
Time |
08:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-09-05 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2018-09-05 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2018-08-29 |
Time |
13:37 |
Sent To |
|
|
| Notes |
| 2018-09-05 14:49:21 | PERMIT # 18081131 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | 1) SHEET G1.0: UPDATE CODE REFERENCE LIST TO REFERENCE | | | NFPA 101 LIFE SAFETY CODE - 2015 EDITION. | | | | | | 2) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION | | | SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND | | | RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION | | | SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A | | | 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A | | | FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED | | | BY EMAIL ([email protected]) OR IN WRITING (FAX: | | | 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE | | | MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.? | | | | | | 3) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER | | | SYSTEM AND/OR FIRE ALARM SYSTEM. | | | | | | | | | SUE ELLEN CALDERON | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-12-10 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-11-07 |
Time |
15:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-10-23 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-10-23 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-08-22 |
Time |
09:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2018-10-23 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-10-23 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-10-23 |
Time |
10:20 |
Sent To |
|
|
| Notes |
| 2018-10-23 10:22:01 | NO CHANGE OF OCCUPANCY IN AREA OF WORK. | | | NO ADDITIONAL SPACE ADDED OR REMOVED. | | | | | | [FBC AMENDED 109]PLANS WILL BE REVIEWED BY THE PBC | | | IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON | | | NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR | | | WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE | | | WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY | | | UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO | | | YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE | | | R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU | | | ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE | | | UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2018-12-10 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-12-10 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-12-10 |
Time |
09:11 |
Sent To |
|
|
| Notes |
| 2018-12-10 09:43:39 | MECHANICAL PROVISO: | | | 12/10/18 | | | | | | A COMMISSIONING REPORT FOR THE NEW AC SYSTEM SHALL BE | | | SUBMITTED TO THE BUILDING DEPARTMENT AS A CONTINGENCY | | | FOR RECEIVING FINAL MECHANICAL INSPECTION APPROVAL AND | | | CO OF THE RENOVATED SPACES. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-09-28 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-09-28 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-09-28 |
Time |
10:32 |
Sent To |
|
|
| Notes |
| 2018-09-28 11:55:17 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #18081131 | | | 9/28/18 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS G1.0 & M2.1: ACCORDING TO THE CODE DATA | | | LISTED ON G1.0, THE VENTILATION SYSTEM FOR THE LAB HAS | | | BEEN DESIGNED IN COMPLAINCE WITH FLORIDA MECHANICAL | | | CODE SIXTH EDITION (2017). REFER TO TABLE 403.3.1.1 AND | | | PROVIDE AN EXHAUST SYSTEM FOR THE LAB BASED ON 1.0 CFMS | | | PER SQ. FT. AND OUTDOOR AIR AT A RATE BASED ON AN | | | OCCUPANT DENSITY OF 25 PERSONS PER 1000 SQ. FT. AT 10 | | | CFMS PER PERSON + 0.18 CFMS PER SQ. FT. REVISE THE | | | PLANS ACCORDINGLY AND PROVIDE VENTILATION CALCULATIONS. | | | ADVISORY: PLEASE SEE TABLE 7-1 DESIGN PARAMETERS ASHRAE | | | 170. AS INDICATED IN THE TABLE, LABORATORIES REQUIRE | | | NEGATIVE PRESSURE, AND DEPENDING ON THE TYPE OF | | | LABORATORY, ALSO REQUIRE ALL ROOM AIR TO BE EXHAUSTED | | | DIRECTLY TO THE OUTDOORS. | | | | | | 2) SHEET M2.1: THE PLAN INDICATES RECIRCULATION OF AIR | | | FROM THE LAB INTO ADJACENT SPACES WHICH IS LIMITED TO | | | 10 PERCENT OF THE AIR FROM THE LAB- SEE TABLE 403.3.1.1 | | | FOOTNOTE G AND PROVIDE AIR BALANCE CALCULATIONS. | | | | | | 3) M2.1, M2.2, & M6.1: RE AND SE ARE NOT SHOWN IN THE | | | AIR DEVICE SCHEDULE. | | | | | | 4) M2.3: SUBMIT A FL. PRODUCT APPROVAL AND A MIAMI-DADE | | | NOA FOR THE NEW LOUVER- RULE 9N-3 FAC. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
MEDGAS |
MEDICAL GAS |
| Rev No |
1 |
Status |
P |
Date |
2019-01-02 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-01-02 |
Time |
10:12 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-01-02 |
Time |
10:12 |
Sent To |
|
|
| Notes |
| 2019-01-02 10:17:03 | CONTRACTOR AND THE FIELD INSTALLER SHALL BE CERTIFIED | | | FOR MED GAS PER FAC 61G4-15.031 | | | | | | SEPARATE PERMIT REQUIRED FOR MED GAS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2019-01-02 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-01-02 |
Time |
10:11 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-01-02 |
Time |
10:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2018-12-10 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-12-10 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-12-10 |
Time |
09:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2018-09-24 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-09-24 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-09-24 |
Time |
11:08 |
Sent To |
|
|
| Notes |
| 2018-09-24 11:08:09 | SHEET S1.1 NOT DIGITALLY SIGNED, ALL OTHER SHEETS OK. | | | FS 471, 481; WPB FBC 107.1 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-08-31 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2018-08-31 |
Time |
14:54 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2018-08-31 |
Time |
14:54 |
Sent To |
|
|
| Notes |
| 2018-08-31 14:55:18 | NO EXTERIOR WORK SHOWN ON PLANS. |
|
|