| Plan Review Stops For Permit 18081075 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2018-10-11 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-10-11 |
Time |
12:49 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-10-11 |
Time |
12:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2018-09-20 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-09-20 |
Time |
13:00 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-09-20 |
Time |
13:00 |
Sent To |
|
|
| Notes |
| 2018-09-20 13:01:35 | COMPLY WITH ZONING COMMENTS FAR AN ELECTRICAL PASS | | | JLEAHY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-09-06 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-09-06 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-09-06 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2018-09-06 14:56:07 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | VALUE TOO LOW FOR PROPOSED WORK, SUBMIT SIGNED | | | CONTRACT. | | | | | | WIND LOADS NEED TO BE SUBMITTED, AND SIGNED AND SEALED | | | DRAWINGS FOR POLE WIH FIXURES. | | | | | | SHOW LIGHTING CONTROL FOR LIGHTS (PHOTCELL, TIME | | | CLOCK?) | | | | | | EXTERIOR LIGHTING CONTROLS. LIGHTING NOT DESIGNATED FOR | | | DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY | | | EITHER A COMBINATION OF A PHOTOSENSOR AND A TIME | | | SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING | | | DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE | | | CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR | | | PHOTOSENSOR. | | | ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING | | | PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER | | | FOR A PERIOD OF AT LEAST 10 HOURS. FBC CE 405.2.4 | | | | | | WALL PACKS TWO SHOWN NEED TO SUBMIT CUT SHEETS TYPE | | | VSC-1 AND HOW THEY MOUNT | | | | | | VSF-1 NEED TO SHOW LOCATION OF ALL 12 ON PLANS DRAWINGS | | | ONLY SHOW 2, PLUS SHOW HOW THEY MOUNT. | | | | | | WILL SUBMIT TO BUILDING WHEN ALL WIND LOADS AND CUT | | | SHEETS ARE SUBMITTED. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-10-11 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-10-11 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-10-03 |
Time |
10:11 |
Sent To |
|
|
| Notes |
| 2018-10-05 10:11:33 | RESUB ROUTED TO ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-09-20 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-09-20 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-09-12 |
Time |
15:11 |
Sent To |
|
|
| Notes |
| 2018-09-13 15:11:30 | RESUB ROUTED TO ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-09-06 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-09-06 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-08-22 |
Time |
12:35 |
Sent To |
|
|
| Notes |
| 2018-08-23 12:35:46 | ROUTED TO ZONING INBOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2018-10-10 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2018-10-10 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2018-10-10 |
Time |
|
Sent To |
E |
|
| Notes |
| 2018-10-10 10:07:39 | PROVISO: | | | | | | 1.) ANY EXISTING TREE IMPACTED BY THE INSTALLATION OF | | | THE LIGHT FIXTURES SHALL BE REPLACED WITH A SIMILAR | | | TREE SPECIE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2018-09-18 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2018-09-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2018-09-18 |
Time |
|
Sent To |
E |
|
| Notes |
| 2018-09-18 12:05:41 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) ELEMENTS IN THE PHOTOMETRIC PLAN DOES NOT MATCH THE | | | IMPROVEMENTS TO THE BELMART PLAZA SITE. PLEASE ADDRESS. | | | [8/30 COMMENT NOT ADDRESSED] | | | | | | 2.) LOCATION OF THE PROPOSED LIGHT FIXTURES SEEM TO | | | CONFLICT WITH APPROVED AND INSTALLED LANDSCAPING ON THE | | | PROPERTY. LANDSCAPING CANNOT BE REMOVED AND/OR | | | RELOCATED WITHOUT THE APPROVAL OF THE CITY'S LANDSCAPE | | | PLANNER BY A SEPARATE LANDSCAPE PERMIT. PLEASE ADDRESS. | | | [8/30 COMMENT NOT ADDRESSED] | | | | | | | | | NOTES: | | | | | | * REFERENCE: ISPR 14-01 | | | | | | * REVISION MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * ZONE: GC | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * SPOKE TO PAUL GANGLOFF OF RIVERSIDE ELECTRIC ON | | | 9/18/18 AND EXPLAINED WHY THE PERMIT HAD FAILED. LATEST | | | APPROVED PLAN SENT TO MR. GANGLOFF TO FORWARD TO THE | | | ELECTRICAL ENGINEER, AS SUBMITTED PLANS ARE OUTDATED | | | AND DO NOT MATCH WHAT IS EXISTING ON PROPERTY. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2018-08-30 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2018-08-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2018-08-28 |
Time |
13:13 |
Sent To |
B |
|
| Notes |
| 2018-08-30 11:39:13 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) PROVIDE AN UPDATED, SIGNED AND SEALED SURVEY OF THE | | | PROPERTY. | | | | | | 2.) ELEMENTS IN THE PHOTOMETRIC PLAN DOES NOT MATCH THE | | | IMPROVEMENTS TO THE BELMART PLAZA SITE. PLEASE ADDRESS. | | | | | | 3.) LOCATION OF THE PROPOSED LIGHT FIXTURES SEEM TO | | | CONFLICT WITH APPROVED AND INSTALLED LANDSCAPING ON THE | | | PROPERTY. LANDSCAPING CANNOT BE REMOVED AND/OR | | | RELOCATED WITHOUT THE APPROVAL OF THE CITY'S LANDSCAPE | | | PLANNER BY A SEPERATE LANDSCAPE PERMIT. PLEASE ADDRESS. | | | | | | | | | NOTES: | | | | | | * REFERENCE: ISPR 14-01 | | | | | | * REVISION MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * ZONE: GC | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | |
|
|