Plan Review Details - Permit 18081075
Plan Review Stops For Permit 18081075
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-10-11 Cont ID  
Sent By jleahy Date 2018-10-11 Time 12:49 Rev Time 0.00
Received By jleahy Date 2018-10-11 Time 12:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-09-20 Cont ID  
Sent By jleahy Date 2018-09-20 Time 13:00 Rev Time 0.00
Received By jleahy Date 2018-09-20 Time 13:00 Sent To  
Notes
2018-09-20 13:01:35COMPLY WITH ZONING COMMENTS FAR AN ELECTRICAL PASS
 JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-06 Cont ID  
Sent By jleahy Date 2018-09-06 Time 14:37 Rev Time 0.00
Received By jleahy Date 2018-09-06 Time 14:37 Sent To  
Notes
2018-09-06 14:56:07FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 VALUE TOO LOW FOR PROPOSED WORK, SUBMIT SIGNED
 CONTRACT.
  
 WIND LOADS NEED TO BE SUBMITTED, AND SIGNED AND SEALED
 DRAWINGS FOR POLE WIH FIXURES.
  
 SHOW LIGHTING CONTROL FOR LIGHTS (PHOTCELL, TIME
 CLOCK?)
  
 EXTERIOR LIGHTING CONTROLS. LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY
 EITHER A COMBINATION OF A PHOTOSENSOR AND A TIME
 SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR.
 ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING
 PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER
 FOR A PERIOD OF AT LEAST 10 HOURS. FBC CE 405.2.4
  
 WALL PACKS TWO SHOWN NEED TO SUBMIT CUT SHEETS TYPE
 VSC-1 AND HOW THEY MOUNT
  
 VSF-1 NEED TO SHOW LOCATION OF ALL 12 ON PLANS DRAWINGS
 ONLY SHOW 2, PLUS SHOW HOW THEY MOUNT.
  
 WILL SUBMIT TO BUILDING WHEN ALL WIND LOADS AND CUT
 SHEETS ARE SUBMITTED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-11 Cont ID  
Sent By jleahy Date 2018-10-11 Time 12:50 Rev Time 0.00
Received By jleahy Date 2018-10-03 Time 10:11 Sent To  
Notes
2018-10-05 10:11:33RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-20 Cont ID  
Sent By jleahy Date 2018-09-20 Time 13:01 Rev Time 0.00
Received By jleahy Date 2018-09-12 Time 15:11 Sent To  
Notes
2018-09-13 15:11:30RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-06 Cont ID  
Sent By jleahy Date 2018-09-06 Time 16:46 Rev Time 0.00
Received By jleahy Date 2018-08-22 Time 12:35 Sent To  
Notes
2018-08-23 12:35:46ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 3 Status P Date 2018-10-10 Cont ID  
Sent By llouie Date 2018-10-10 Time   Rev Time 0.00
Received By llouie Date 2018-10-10 Time   Sent To E
Notes
2018-10-10 10:07:39PROVISO:
  
 1.) ANY EXISTING TREE IMPACTED BY THE INSTALLATION OF
 THE LIGHT FIXTURES SHALL BE REPLACED WITH A SIMILAR
 TREE SPECIE.

Review Stop Z ZONING
Rev No 2 Status F Date 2018-09-18 Cont ID  
Sent By llouie Date 2018-09-18 Time   Rev Time 0.00
Received By llouie Date 2018-09-18 Time   Sent To E
Notes
2018-09-18 12:05:41** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) ELEMENTS IN THE PHOTOMETRIC PLAN DOES NOT MATCH THE
 IMPROVEMENTS TO THE BELMART PLAZA SITE. PLEASE ADDRESS.
 [8/30 COMMENT NOT ADDRESSED]
  
 2.) LOCATION OF THE PROPOSED LIGHT FIXTURES SEEM TO
 CONFLICT WITH APPROVED AND INSTALLED LANDSCAPING ON THE
 PROPERTY. LANDSCAPING CANNOT BE REMOVED AND/OR
 RELOCATED WITHOUT THE APPROVAL OF THE CITY'S LANDSCAPE
 PLANNER BY A SEPARATE LANDSCAPE PERMIT. PLEASE ADDRESS.
 [8/30 COMMENT NOT ADDRESSED]
  
  
 NOTES:
  
 * REFERENCE: ISPR 14-01
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * ZONE: GC
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * SPOKE TO PAUL GANGLOFF OF RIVERSIDE ELECTRIC ON
 9/18/18 AND EXPLAINED WHY THE PERMIT HAD FAILED. LATEST
 APPROVED PLAN SENT TO MR. GANGLOFF TO FORWARD TO THE
 ELECTRICAL ENGINEER, AS SUBMITTED PLANS ARE OUTDATED
 AND DO NOT MATCH WHAT IS EXISTING ON PROPERTY.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-08-30 Cont ID  
Sent By llouie Date 2018-08-30 Time   Rev Time 0.00
Received By llouie Date 2018-08-28 Time 13:13 Sent To B
Notes
2018-08-30 11:39:13** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PROVIDE AN UPDATED, SIGNED AND SEALED SURVEY OF THE
 PROPERTY.
  
 2.) ELEMENTS IN THE PHOTOMETRIC PLAN DOES NOT MATCH THE
 IMPROVEMENTS TO THE BELMART PLAZA SITE. PLEASE ADDRESS.
  
 3.) LOCATION OF THE PROPOSED LIGHT FIXTURES SEEM TO
 CONFLICT WITH APPROVED AND INSTALLED LANDSCAPING ON THE
 PROPERTY. LANDSCAPING CANNOT BE REMOVED AND/OR
 RELOCATED WITHOUT THE APPROVAL OF THE CITY'S LANDSCAPE
 PLANNER BY A SEPERATE LANDSCAPE PERMIT. PLEASE ADDRESS.
  
  
 NOTES:
  
 * REFERENCE: ISPR 14-01
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * ZONE: GC
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  