Plan Review Details - Permit 18081074
Plan Review Stops For Permit 18081074
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-11-14 Cont ID  
Sent By dbattles Date 2018-11-14 Time 11:08 Rev Time 0.00
Received By dbattles Date 2018-11-14 Time 11:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-27 Cont ID  
Sent By jwitmer Date 2018-09-27 Time 14:09 Rev Time 0.00
Received By dbattles Date 2018-09-27 Time 12:26 Sent To  
Notes
2018-09-27 14:10:48****CORRECTIONS****
 W.P.B. PERMIT: 18081074
 REVIEWED: SEPTEMBER 27, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
  
 [FBC 404.2.6]DOORS IN SERIES AND GATES IN SERIES.
 THE DISTANCE BETWEEN TWO HINGED OR PIVOTED DOORS IN
 SERIES AND GATES IN SERIES SHALL BE 48 INCHES (1220 MM)
 MINIMUM PLUS THE WIDTH OF DOORS OR GATES SWINGING INTO
 THE SPACE.
 ADJUST DOORS TO MEET ADA REQUIREMENTS AT VESTIBULE.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-10-24 Cont ID  
Sent By jleahy Date 2018-10-24 Time 09:02 Rev Time 0.00
Received By jleahy Date 2018-10-24 Time 09:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-13 Cont ID  
Sent By jleahy Date 2018-09-13 Time 09:42 Rev Time 0.00
Received By jleahy Date 2018-09-13 Time 09:41 Sent To  
Notes
2018-09-13 09:45:24FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ADDED VALUE FOR THE ADDITIONAL SYSTEMS , SPEAKERS,
 ANTENNA SYSTEMS, ADDITIONAL FIXTURES
  
 NO OUTLETS SHOWN ON ROOF FOR SERVICING (GFI)
  
 PROVIDE CUTSHEETS ON SPEAKERS, WIRING ANTENNA SYSTEM.
  
 SYMBOL WAP ???
  
 FAULT CURRENT CALCULATION FOR MAINS AND PANELS REQUIRED
 BEFORE ROUGH INSPECTIONS

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 2 Status P Date 2018-11-14 Cont ID  
Sent By jleahy Date 2018-11-14 Time 14:44 Rev Time 0.00
Received By jleahy Date 2018-11-14 Time 14:44 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status F Date 2018-09-13 Cont ID  
Sent By jleahy Date 2018-09-13 Time 09:46 Rev Time 0.00
Received By jleahy Date 2018-09-13 Time 09:46 Sent To  
Notes
2018-09-13 09:48:40FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 LOW VOLTAGE REVIEW ONLY FOR DATA ,TELEPHONE, SPEAKERS,
 AND ANTENNA SYSTEM
  
 NEED CUT SHEETS ON WIRING AND SPEAKER, AND ANTENNA
 SYSTEM.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-08-27 Cont ID  
Sent By scaldero Date 2018-08-27 Time 13:14 Rev Time 0.00
Received By scaldero Date 2018-08-27 Time 10:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-12-14 Time   Rev Time 0.00
Received By lmarchan Date 2018-12-03 Time 13:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-14 Cont ID  
Sent By jleahy Date 2018-11-14 Time 14:45 Rev Time 0.00
Received By jleahy Date 2018-10-12 Time 13:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-27 Cont ID  
Sent By dbattles Date 2018-09-27 Time 14:13 Rev Time 0.00
Received By dbattles Date 2018-08-23 Time 08:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-12-14 Cont ID  
Sent By ccole Date 2018-12-14 Time 15:33 Rev Time 0.00
Received By ccole Date 2018-12-14 Time 10:45 Sent To  
Notes
2018-12-14 15:39:54MECHANICAL PROVISO:
  
 COMMISSIONING REPORT FOR THE MECHANICAL, AND ELECTRICAL
 POWER AND LIGHTING SYSTEMS REQUIRED FOR C/O.
  
 SEE SHEETS M0.1 & M2.1 FOR THE GOLF CART GARAGE AND
 STORAGE AREA PROVISOS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-11-09 Cont ID  
Sent By ccole Date 2018-11-08 Time 10:08 Rev Time 0.00
Received By ccole Date 2018-11-08 Time 16:22 Sent To  
Notes
2018-11-14 10:13:012ND REVIEW FBC-2017 MECHANICAL
 REVISION #18081074
 MASTER #17110860
 11/8/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.2, M2.3, & M2,4: THE SUPPLY AND RETURN DUCT
 DROPS FROM RTU-1-8B APPEAR TO MISLABLED AS DROPS FROM
 AHU 1-8A.
  
 2) THE REQUESTED WIND LOAD ENGINEERING FOR INSTALLING
 THE RTU'S IS INCOMPLETE. THERE ARE NO DETAILS SHOWING
 HOW THE CURBS WILL BE ATTACHED TO THE ROOF STRUCTURE.
 CONCERNING THE RTU ATTACHMENT TO THE CURBS, THE
 SUBMITTALS FROM ENGINEERS BUEROSSE P.E. AND BERNARDO
 P.E SHALL BE SIGNED AND SEALED PER SECTION 61G15-23.002
 FAC. IT WOULD BE HELPFUL TO INDICATE WHICH ENGINEERING
 APPLIES TO WHICH RTU- SECTION 107.2.1 WPB.
  
 3) PLEASE PROVIDE MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE HYDROGEN SENSORS-
 SECTION 404.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-09-18 Cont ID  
Sent By ccole Date 2018-09-18 Time 16:07 Rev Time 0.00
Received By ccole Date 2018-09-18 Time 16:07 Sent To  
Notes
2018-09-18 17:20:001ST REVIEW FBC-2017 MECHANICAL
 REVISION #18081074
 MASTER #17110860
 9/18/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.2, M2.3, & M2,4: THE SUPPLY AND RETURN DUCT
 DROPS FROM RTU-1-8B APPEAR TO MISLABLED AS DROPS FROM
 AHU 1-8A.
  
 2) THE REQUESTED WIND LOAD ENGINEERING FOR INSTALLING
 THE RTU'S IS INCOMPLETE. THERE ARE NO DETAILS SHOWING
 HOW THE CURBS WILL BE ATTACHED TO THE ROOF STRUCTURE.
 CONCERNING THE RTU ATTACHMENT TO THE CURBS, THE
 SUBMITTALS FROM ENGINEERS BUEROSSE P.E. AND BERNARDO
 P.E SHALL BE SIGNED AND SEALED PER SECTION 61G15-23.002
 FAC. IT WOULD BE HELPFUL TO INDICATE WHICH ENGINEERING
 APPLIES TO WHICH RTU- SECTION 107.2.1 WPB.
  
 3) PLEASE PROVIDE MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE HYDROGEN SENSORS-
 SECTION 404.1 FBC M.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-09-25 Cont ID  
Sent By gjohnson Date 2018-09-25 Time 17:41 Rev Time 0.00
Received By gjohnson Date 2018-09-25 Time 17:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2018-11-14 Cont ID  
Sent By dbattles Date 2018-11-14 Time 11:15 Rev Time 0.00
Received By dbattles Date 2018-11-14 Time 11:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2018-08-25 Cont ID  
Sent By shill Date 2018-08-25 Time 08:53 Rev Time 0.00
Received By shill Date 2018-08-25 Time 08:53 Sent To  
Notes
2018-08-25 08:54:25A, F, MEP OK
 PROVISO: NEW PAGES UPLOADED FOR A 2ND REVIEW CYCLE
 REQUIRE SIGNATURE REVIEW
  