Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-12-06 Cont ID  
Sent By jgomez Date 2018-12-06 Time 17:50 Rev Time 0.00
Received By jgomez Date 2018-12-06 Time 15:25 Sent To  
Notes
2018-11-29 17:11:58REVISION THIRD BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1-ENGINEERED PLANS SHOW THE METAL SCREENING ATTACHED TO
 THE A/C UNIT. TYPICALLY, A/C UNITS ARE NOT DESIGNED TO
 RESIST ADDITIONAL WIND LOADS. PROVIDE A/C MANUFACTURES
 SPECS SHOWING THAT THE UNIT IS DESIGNED FOR THIS
 ADDITIONAL LOAD OR PROVIDE COMPLETE ENGINEERING
 ANALYSIS SHOWING THAT THE EXISTING A/C UNIT WILL RESIST
 THE ADDITIONAL LOAD. SEC. 1609 FBC AND SEC. 107.2.1.2
 CITY AMENDMENTS.
  
 RESPONSE:
 SPINNAKER INDUSTRIES SLIDING LOUVERED PANEL
 ARCHITECTURAL SCREENING SPECIFICATION SUBMITTED
 SPECIFIES "THE SCREENING WILL BE SHIPPED "KOCKED-DOWN"
 AS AN ASSEMBLY KIT WHICH WILL MOUNT DIRECTLY TO THE
 MECHANICAL EQUIPMENT (NO ROOF-TOP PENETRATION WILL BE
 REQUIRED, OR ALLOWED)". NEED TO PROVIDE ENGINEERING
 ANALYSIS OR A/C MANUFACTUER SPECIFICATIONS SHOWNG THAT
 THE A/C WILL RESIST THE ADDTIONAL LOADS. OR ENGINEER OF
 RECORD PROVIDE COMPLETE DETAISLA ND SPECIFICATIONS FOR
 SCREENING TO BE ATTACHED TO THE A/C CURB NOT THE A/C
 UNIT. SEC. 1609 FBC AND SEC. 107.2.1.2 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 2- PROVIDE PLAN SHOWING THE LOCATION OF THE PROPOSED
 SCREENS. SEC. 1107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 SCOPE OF WORK SHOWN ON DRAWINGS FROM JACOBS SUBMITTED
 VIA E-MAI ON 11/27/18 IS NOT CLEAR. EQUIPMENT SHOWN ON
 FLOOR PLAN ON SHEET SK-1 AND SK-2 DOESN'T MATCH. NOT
 CLEAR IF INSTALLING SCREEN POSTS OR NOT. AND LOCATIOIN
 OF POST DON'T MATCH . CLARIFY IS USIING SPINNAKER
 INSUATRIES OR CITYSCAPES. COORDIANTE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 3- RE-SUBMIT COMPLETE COORDINATED PACKAGE FOR REVIEW.
 NOTE: MECHANICAL PLAN REVIEWER WILL NEED TO REVIEW
 PLANS FOR COMPLIANCE WITH ACCESS FOR SERVICE AND
 REPLACEMENT. PROVIDE THIS INFORAMTION FOR MECHANICAL
 REVIEW TO AVODI/CONFLICTS DELAYS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected].

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-10-01 Cont ID  
Sent By jgomez Date 2018-09-28 Time 15:33 Rev Time 0.00
Received By jgomez Date 2018-09-28 Time 18:55 Sent To Z
Notes
2018-09-26 13:15:22REVISION SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS.
  
 1-ENGINEERED PLANS SHOW THE METAL SCREENING ATTACHED TO
 THE A/C UNIT. TYPICALLY, A/C UNITS ARE NOT DESIGNED TO
 RESIST ADDITIONAL WIND LOADS. PROVIDE A/C MANUFACTURES
 SPECS SHOWING THAT THE UNIT IS DESIGNED FOR THIS
 ADDITIONAL LOAD OR PROVIDE COMPLETE ENGINEERING
 ANALYSIS SHOWING THAT THE EXISTING A/C UNIT WILL RESIST
 THE ADDITIONAL LOAD. SEC. 1609 FBC AND SEC. 107.2.1.2
 CITY AMENDMENTS.
  
 2- PROVIDE PLAN SHOWING THE LOCATION OF THE PROPOSED
 SCREENS. SEC. 1107.2.1 CITY AMENDMENTS.
  
 3- ADDRESS SHOWN IN THE TITLE BLOCK DOESN'T MATCH
 ADDRESS OF BUILDING UNDER MASTER NUMBER 17100607. THE
 ADDRESS SHOWN ON APPROVED PLANS IS 851 VILLAGE BLVD
 #502. . REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-31 Cont ID  
Sent By jgomez Date 2018-08-31 Time 18:20 Rev Time 0.00
Received By jgomez Date 2018-08-31 Time 18:20 Sent To  
Notes
2018-08-31 18:24:15REVISION BUILDING REVIEW COMMENTS
 CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS.
  
 NOTE:
 REVISION FEES ARE NOT PAID. FUTURE REVIEWS WILL NOT BE
 DONE UNTIL FEES ARE PAID.
  
 1- PROPOSED WORK IS NOT CLEAR. DETAILS PROVIDED ARE
 ONLY FOR LOCATION OF TWO STEEL POSTS. THERE IS NO
 INFORMATION FOR THE SCREENING. SEE ZONING COMMENTS
 ALSO. SEC. 107.2.1 CITY AMENDMENTS.
  
 2- ADDRESS SHOWN IN THE TITLE BLOCK DOESN'T MATCH
 ADDRESS OF BUILDING. REVISE AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-12-06 Cont ID  
Sent By jgomez Date 2018-11-29 Time 17:50 Rev Time 0.00
Received By jgomez Date 2018-11-29 Time 17:08 Sent To  
Notes
2018-11-29 17:49:16JOHN MCFARLAND E-MAILED SPINNAKER INDUSTRIES SCREENING
 SYSTEMS INFORMATION. VIA E-MAIL.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-03 Cont ID  
Sent By cpuell Date 2018-10-03 Time 16:38 Rev Time 0.00
Received By cpuell Date 2018-09-18 Time 14:35 Sent To  
Notes
2018-09-19 14:36:10RESUB OF REVISION ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-31 Cont ID  
Sent By jgomez Date 2018-08-31 Time 18:24 Rev Time 0.00
Received By jgomez Date 2018-08-20 Time 16:33 Sent To I
Notes
2018-08-21 16:33:34REVISION ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status F Date 2018-10-03 Cont ID  
Sent By eschneid Date 2018-10-03 Time 14:25 Rev Time 0.25
Received By eschneid Date 2018-10-03 Time 14:25 Sent To PC
Notes
2018-10-03 14:27:55FAILED
  
 REVISED COMMENT: ZONING STAFF IS UNABLE TO VERIFY
 SCREENING IS BEING MET WITH THE INFORMATION PROVIDED ON
 THE PERMIT. INCLUDE A ROOF PLAN THAT CLEARLY SHOWS
 WHERE THE SPECIFIC SCREENING IS TO BE INSTALLED. THERE
 STRUCTURAL PLANS SHOW AN A/C UNIT COMPLETELY SURROUNDED
 BY SCREENING AND ONE SCREEN WALL. THESE NEED TO BE
 SHOWN IN RELATIONSHIP TO THE ROOF TOP EQUIPMENT THAT
 THEY ARE TO SCREEN.NOTE: THE E-MAILS THAT I HAD
 PREVIOUSLY RECEIVED ON THIS PROVIDED MORE INFORMATION
 AS TO LOCATION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-08-31 Cont ID  
Sent By eschneid Date 2018-08-31 Time 10:33 Rev Time 0.25
Received By eschneid Date 2018-08-31 Time 10:33 Sent To B
Notes
2018-08-31 10:36:48FAILED
  
 ZONING STAFF IS UNABLE TO VERIFY SCREENING IS BEING MET
 WITH THE INFORMATION PROVIDED ON THE PERMIT. THIS ONLY
 APPEARS TO BE FOR THE POST. PLEASE PROVIDE MORE
 INFORMATION. NOTE: THE E-MAILS THAT I HAD PREVIOUSLY
 RECIEVED ON THIS PROVIDED MORE INFORMATION AS TO
 LOCATION, SCREEN MATERIAL TYPE, ETC.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]