Plan Review Details - Permit 18080922
Plan Review Stops For Permit 18080922
Review Stop E ELECTRICAL
Rev No 5 Status P Date 2018-11-30 Cont ID  
Sent By fgiaquin Date 2018-11-30 Time 05:50 Rev Time 0.00
Received By fgiaquin Date 2018-11-30 Time 05:21 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2018-11-27 Cont ID  
Sent By fgiaquin Date 2018-11-27 Time 08:14 Rev Time 0.00
Received By fgiaquin Date 2018-11-27 Time 06:44 Sent To  
Notes
2018-11-27 06:55:58ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. 4TH ELECTRICAL PLAN REVIEW THAT HAS FAILED. PLAN
 REVIEW COMMENTS HAVE NOT BEEN ADDRESSED SEVERAL TIMES.
 PLEASE CONTACT ME TO SCHEDULE A MEETING. NO FURTHER
 PLAN REVIEWS WILL BE DONE UNTIL AFTER MEETING. MY EMAIL
 AND CELL PHONE NUMBER ARE BELOW.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-10-24 Cont ID  
Sent By fgiaquin Date 2018-10-24 Time 06:41 Rev Time 0.00
Received By fgiaquin Date 2018-10-24 Time 06:01 Sent To I
Notes
2018-10-24 06:39:23ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN PROVIDED IS NOT SIGNED AS PER LAST PLAN REVIEW
 COMMENTS.
 ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 2. BLEAKLEY ELECTRIC APPLIED FOR A ELEC-SUB PERMIT BUT
 HAS REFERENCED THE MASTER SET OF PLANS (PLANS SUBMITTED
 FOR THIS PERMIT). PROVIDE ELECTRICAL PLAN FOR REVIEW,
 SIGNED AND SEALED BY A LICENSED DESIGN PROFESSIONAL OR
 SIGNED BY THE ELECTRICAL CONTRACTOR QUALIFIER.
 INDICATE EXISTING CONDUIT SIZE, WIRE SIZE, AND OCP TO
 NEW PROPOSED FIRE PUMP FROM EXISITNG FIRE PUMP
 CONTROLLER. FS 471.003(2)(H); 471.025; WPB FBC 107.2.1,
 107.3.5
  
 3. INITIAL PERMIT APPLICATION SAID "INSTALLATION OF NEW
 FIRE PUMP AND CONTROLLER" NOW CONTRACTOR STATES ONLY
 THE FIRE PUMP IS TO BE REPLACED. PROVIDE SPECS FOR
 EXISTING FIRE PUMP CONTROLLER, PROVIDE UL/NRTL LISTING
 FOR EXISTING FIRE PUMP CONTROLLER AND PROVIDE
 DOCUMENTATION THAT SHOWS EXISTING FIRE PUMP CONTROLLER
 IS LISTED TO BE USED WITH NEW PROPOSED FIRE PUMP. NEC
 90.7, 110.2, 110.3B
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-09-25 Cont ID  
Sent By fgiaquin Date 2018-09-25 Time 06:34 Rev Time 0.00
Received By fgiaquin Date 2018-09-25 Time 05:28 Sent To I
Notes
2018-09-25 06:33:34ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. LICENSED ELECTRICAL CONTRACTOR REQUIRED FOR
 DISCONNECTION OF OLD AND INSTALLATION OF NEW FIRE PUMP
 AND CONTROLLER, AS PER LAST PLAN REVIEW COMMENTS.
 ELECTRICAL CONTRACTOR REQUIRED FBC 105.1, F.S. 489.505
  
 2. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 3. PLAN SHOWS 70PSI, 50HP PUMP BY PEERLESS BUT
 SUBMITTAL SAYS 100PSI, 60HP PUMP BY FAIRBANKS. PROVIDE
 ACCURATE PLAN AND SUBMITTALS FOR REVIEW. FBC 107.2.1
  
 4. NO UL OR OTHER NRTL LISTING PROVIDED FOR FIRE PUMP.
 NO SUBMITTALS PROVIDED FOR FIRE PUMP CONTROLLER.
 PROVIDE LISTINGS FOR BOTH NEC 110.3B, FBC 107.2.1
  
 5. VALUE LOW, RAISE VALUE OR VALUE WILL BE SET BY
 BUILDING OFFICAL. VALUE TO INCLUDE ALL MATERIALS AND
 LABOR.FIRE PUMP, CONTROLLER ETC.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-30 Cont ID  
Sent By fgiaquin Date 2018-08-30 Time 17:16 Rev Time 0.00
Received By fgiaquin Date 2018-08-30 Time 16:24 Sent To M
Notes
2018-08-30 17:16:29ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PERMIT AND ELECTRICAL CONTRACTOR
 REQUIRED. FBC 105.1, F.S. 489.505.
  
 2. VALUE EXTREMELY LOW. ESTIMATED VALUE OVER $125,000.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 3. ENGINEERED DRAWINGS REQUIRED VALUE OVER $125,000
  
 471.003?QUALIFICATIONS FOR PRACTICE; EXEMPTIONS.
  
 (H)?ANY ELECTRICAL, PLUMBING, AIR-CONDITIONING, OR
 MECHANICAL CONTRACTOR WHOSE PRACTICE INCLUDES THE
 DESIGN AND FABRICATION OF ELECTRICAL, PLUMBING,
 AIR-CONDITIONING, OR MECHANICAL SYSTEMS, RESPECTIVELY,
 WHICH SHE OR HE INSTALLS BY VIRTUE OF A LICENSE ISSUED
 UNDER CHAPTER 489, UNDER PART I OF CHAPTER 553, OR
 UNDER ANY SPECIAL ACT OR ORDINANCE WHEN WORKING ON ANY
 CONSTRUCTION PROJECT WHICH:
  
 1. REQUIRES AN ELECTRICAL OR PLUMBING OR
 AIR-CONDITIONING AND REFRIGERATION SYSTEM WITH A VALUE
 OF $125,000 OR LESS; AND
 2. REQUIRES AN AGGREGATE SERVICE CAPACITY OF 600
 AMPERES (240 VOLTS) OR LESS ON A RESIDENTIAL ELECTRICAL
 SYSTEM OR 800 AMPERES (240 VOLTS) OR LESS ON A
 COMMERCIAL OR INDUSTRIAL ELECTRICAL SYSTEM.
  
 4. SUBMITTALS REQUIRED FOR FIRE PUMP CONTROLLER/ATS FOR
 PRODUCT APPROVAL AND JOCKEY PUMP/JOCKEY PUMP CONTROLLER
 IF BEING REPLACED. PLAN UNCLEAR. FBC 107.2.1 NEC 110.3B
  
  
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2018-11-19 Cont ID  
Sent By pleduc Date 2018-11-19 Time   Rev Time 0.00
Received By pleduc Date 2018-11-19 Time 14:16 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-10-23 Cont ID  
Sent By pleduc Date 2018-10-23 Time   Rev Time 0.00
Received By pleduc Date 2018-10-23 Time 11:45 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-09-21 Cont ID  
Sent By pleduc Date 2018-09-21 Time   Rev Time 0.00
Received By pleduc Date 2018-09-20 Time 15:45 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-08-27 Cont ID  
Sent By J.Walker Date 2018-08-27 Time   Rev Time  
Received By   Date 2018-08-23 Time   Sent To E
Notes
2018-08-27 11:33:10WILL REQUIRE NFPA 25 TEST AND INSPECTIONS.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-11-30 Cont ID  
Sent By fgiaquin Date 2018-11-30 Time 05:50 Rev Time 0.00
Received By fgiaquin Date 2018-11-15 Time 16:12 Sent To  
Notes
2018-11-27 08:15:00PLAN ON FGIAQUINTO'S DESK AWAITING MEETING WITH
 CONTRACTOR.
2018-11-15 16:12:39RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-24 Cont ID  
Sent By fgiaquin Date 2018-10-24 Time 06:41 Rev Time 0.00
Received By fgiaquin Date 2018-10-18 Time 15:20 Sent To  
Notes
2018-10-19 15:20:36RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-25 Cont ID  
Sent By fgiaquin Date 2018-09-25 Time 06:34 Rev Time 0.00
Received By fgiaquin Date 2018-09-18 Time 13:30 Sent To  
Notes
2018-09-25 07:12:06PLAN ON SHILL'S DESK 9/25/18
2018-09-19 13:30:54RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-04 Cont ID  
Sent By hmoser Date 2018-09-04 Time 14:34 Rev Time 0.00
Received By hmoser Date 2018-08-17 Time 11:35 Sent To  
Notes
2018-08-20 11:35:33ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-09-04 Cont ID  
Sent By hmoser Date 2018-09-04 Time 14:02 Rev Time 0.00
Received By hmoser Date 2018-09-04 Time 14:01 Sent To I
Notes
***NONE***