Plan Review Details - Permit 18080922
| Plan Review Stops For Permit 18080922 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2018-11-30 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-11-30 |
Time |
05:50 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-11-30 |
Time |
05:21 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2018-11-27 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-11-27 |
Time |
08:14 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-11-27 |
Time |
06:44 |
Sent To |
|
|
| Notes |
| 2018-11-27 06:55:58 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. 4TH ELECTRICAL PLAN REVIEW THAT HAS FAILED. PLAN | | | REVIEW COMMENTS HAVE NOT BEEN ADDRESSED SEVERAL TIMES. | | | PLEASE CONTACT ME TO SCHEDULE A MEETING. NO FURTHER | | | PLAN REVIEWS WILL BE DONE UNTIL AFTER MEETING. MY EMAIL | | | AND CELL PHONE NUMBER ARE BELOW. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2018-10-24 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-10-24 |
Time |
06:41 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-10-24 |
Time |
06:01 |
Sent To |
I |
|
| Notes |
| 2018-10-24 06:39:23 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PLAN PROVIDED IS NOT SIGNED AS PER LAST PLAN REVIEW | | | COMMENTS. | | | ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND | | | SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE | | | ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS | | | 471.003(2)(H); 471.025; WPB FBC 107.1 | | | | | | 2. BLEAKLEY ELECTRIC APPLIED FOR A ELEC-SUB PERMIT BUT | | | HAS REFERENCED THE MASTER SET OF PLANS (PLANS SUBMITTED | | | FOR THIS PERMIT). PROVIDE ELECTRICAL PLAN FOR REVIEW, | | | SIGNED AND SEALED BY A LICENSED DESIGN PROFESSIONAL OR | | | SIGNED BY THE ELECTRICAL CONTRACTOR QUALIFIER. | | | INDICATE EXISTING CONDUIT SIZE, WIRE SIZE, AND OCP TO | | | NEW PROPOSED FIRE PUMP FROM EXISITNG FIRE PUMP | | | CONTROLLER. FS 471.003(2)(H); 471.025; WPB FBC 107.2.1, | | | 107.3.5 | | | | | | 3. INITIAL PERMIT APPLICATION SAID "INSTALLATION OF NEW | | | FIRE PUMP AND CONTROLLER" NOW CONTRACTOR STATES ONLY | | | THE FIRE PUMP IS TO BE REPLACED. PROVIDE SPECS FOR | | | EXISTING FIRE PUMP CONTROLLER, PROVIDE UL/NRTL LISTING | | | FOR EXISTING FIRE PUMP CONTROLLER AND PROVIDE | | | DOCUMENTATION THAT SHOWS EXISTING FIRE PUMP CONTROLLER | | | IS LISTED TO BE USED WITH NEW PROPOSED FIRE PUMP. NEC | | | 90.7, 110.2, 110.3B | | | | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2018-09-25 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-09-25 |
Time |
06:34 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-09-25 |
Time |
05:28 |
Sent To |
I |
|
| Notes |
| 2018-09-25 06:33:34 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. LICENSED ELECTRICAL CONTRACTOR REQUIRED FOR | | | DISCONNECTION OF OLD AND INSTALLATION OF NEW FIRE PUMP | | | AND CONTROLLER, AS PER LAST PLAN REVIEW COMMENTS. | | | ELECTRICAL CONTRACTOR REQUIRED FBC 105.1, F.S. 489.505 | | | | | | 2. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND | | | SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE | | | ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H); | | | 471.025; WPB FBC 107.2.1, 107.3.5 | | | | | | 3. PLAN SHOWS 70PSI, 50HP PUMP BY PEERLESS BUT | | | SUBMITTAL SAYS 100PSI, 60HP PUMP BY FAIRBANKS. PROVIDE | | | ACCURATE PLAN AND SUBMITTALS FOR REVIEW. FBC 107.2.1 | | | | | | 4. NO UL OR OTHER NRTL LISTING PROVIDED FOR FIRE PUMP. | | | NO SUBMITTALS PROVIDED FOR FIRE PUMP CONTROLLER. | | | PROVIDE LISTINGS FOR BOTH NEC 110.3B, FBC 107.2.1 | | | | | | 5. VALUE LOW, RAISE VALUE OR VALUE WILL BE SET BY | | | BUILDING OFFICAL. VALUE TO INCLUDE ALL MATERIALS AND | | | LABOR.FIRE PUMP, CONTROLLER ETC. | | | | | | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING | | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WPB | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-08-30 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-08-30 |
Time |
17:16 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-08-30 |
Time |
16:24 |
Sent To |
M |
|
| Notes |
| 2018-08-30 17:16:29 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. ELECTRICAL PERMIT AND ELECTRICAL CONTRACTOR | | | REQUIRED. FBC 105.1, F.S. 489.505. | | | | | | 2. VALUE EXTREMELY LOW. ESTIMATED VALUE OVER $125,000. | | | | | | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING | | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | 3. ENGINEERED DRAWINGS REQUIRED VALUE OVER $125,000 | | | | | | 471.003?QUALIFICATIONS FOR PRACTICE; EXEMPTIONS. | | | | | | (H)?ANY ELECTRICAL, PLUMBING, AIR-CONDITIONING, OR | | | MECHANICAL CONTRACTOR WHOSE PRACTICE INCLUDES THE | | | DESIGN AND FABRICATION OF ELECTRICAL, PLUMBING, | | | AIR-CONDITIONING, OR MECHANICAL SYSTEMS, RESPECTIVELY, | | | WHICH SHE OR HE INSTALLS BY VIRTUE OF A LICENSE ISSUED | | | UNDER CHAPTER 489, UNDER PART I OF CHAPTER 553, OR | | | UNDER ANY SPECIAL ACT OR ORDINANCE WHEN WORKING ON ANY | | | CONSTRUCTION PROJECT WHICH: | | | | | | 1. REQUIRES AN ELECTRICAL OR PLUMBING OR | | | AIR-CONDITIONING AND REFRIGERATION SYSTEM WITH A VALUE | | | OF $125,000 OR LESS; AND | | | 2. REQUIRES AN AGGREGATE SERVICE CAPACITY OF 600 | | | AMPERES (240 VOLTS) OR LESS ON A RESIDENTIAL ELECTRICAL | | | SYSTEM OR 800 AMPERES (240 VOLTS) OR LESS ON A | | | COMMERCIAL OR INDUSTRIAL ELECTRICAL SYSTEM. | | | | | | 4. SUBMITTALS REQUIRED FOR FIRE PUMP CONTROLLER/ATS FOR | | | PRODUCT APPROVAL AND JOCKEY PUMP/JOCKEY PUMP CONTROLLER | | | IF BEING REPLACED. PLAN UNCLEAR. FBC 107.2.1 NEC 110.3B | | | | | | | | | | | | | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WPB | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2018-11-19 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-11-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-11-19 |
Time |
14:16 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2018-10-23 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-10-23 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-10-23 |
Time |
11:45 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-09-21 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-09-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-09-20 |
Time |
15:45 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-08-27 |
|
|
Cont ID |
|
| Sent By |
J.Walker |
Date |
2018-08-27 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
2018-08-23 |
Time |
|
Sent To |
E |
|
| Notes |
| 2018-08-27 11:33:10 | WILL REQUIRE NFPA 25 TEST AND INSPECTIONS. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2018-11-30 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-11-30 |
Time |
05:50 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-11-15 |
Time |
16:12 |
Sent To |
|
|
| Notes |
| 2018-11-27 08:15:00 | PLAN ON FGIAQUINTO'S DESK AWAITING MEETING WITH | | | CONTRACTOR. | | 2018-11-15 16:12:39 | RESUB ROUTED TO FIRE INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-10-24 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-10-24 |
Time |
06:41 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-10-18 |
Time |
15:20 |
Sent To |
|
|
| Notes |
| 2018-10-19 15:20:36 | RESUB ROUTED TO FIRE INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-09-25 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-09-25 |
Time |
06:34 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-09-18 |
Time |
13:30 |
Sent To |
|
|
| Notes |
| 2018-09-25 07:12:06 | PLAN ON SHILL'S DESK 9/25/18 | | 2018-09-19 13:30:54 | RESUB ROUTED TO FIRE INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-09-04 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2018-09-04 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2018-08-17 |
Time |
11:35 |
Sent To |
|
|
| Notes |
| 2018-08-20 11:35:33 | ROUTED TO FIRE INBOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2018-09-04 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2018-09-04 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2018-09-04 |
Time |
14:01 |
Sent To |
I |
|
| Notes |
|
|
|