Plan Review Details - Permit 18080908
Plan Review Stops For Permit 18080908
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-12-21 Cont ID  
Sent By dbattles Date 2018-12-21 Time 09:01 Rev Time 0.00
Received By dbattles Date 2018-12-21 Time 09:01 Sent To  
Notes
2018-12-21 09:03:02PROVISO:
 FLOORING UNDERLAYMENT SUBMITTAL WILL BE NEEDED FOR 2ND
 FLOOR PRIOR TO FLOORING INSTALLATION.
 CONTACT ME VIA E-MAIL TO GET PRE-APPROVAL OF
 UNDERLAMENT PRIOR TO SUBMITTAL.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-24 Cont ID  
Sent By dbattles Date 2018-10-24 Time 10:54 Rev Time 0.00
Received By dbattles Date 2018-10-23 Time 07:51 Sent To  
Notes
2018-10-24 10:55:48****CORRECTIONS****
 W.P.B. PERMIT: 18080908
 REVIEWED: OCTOBER 24, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC 107.3.5]PROVIDE PROJECT DATA:
 LEVEL OF ALTERATION-THIS IS LEVEL 3 ALTERATION
 AREA OF EACH UNIT TYPE UNDER AIR.
 OCCUPANCY TYPE
 TYPE OF CONSTRUCTION
 EXISTING FIRE SEPARATION OF UNITS?
  
 2. UPLOAD NOA#17-1011.23 TO SUPPORTING DOCUMENTS FOLDER
 IN PROJECT DOX.
  
 3. REMOVE DOORS FROM THE WEST SIDE OF KEY PLAN SECOND
 FLOOR. THERE WOULD BE NO DOORS ON THAT SIDE OF BUILDING
 ON THAT LEVEL.
  
 4. 702.4 WINDOW OPENING CONTROL DEVICES.
 IN GROUP R-2 OR R-3 BUILDINGS CONTAINING DWELLING UNITS
 AND ONE- AND TWO-FAMILY DWELLINGS AND TOWNHOUSES
 REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL,
 WINDOW OPENING CONTROL DEVICES COMPLYING WITH ASTM
 F2090 SHALL BE INSTALLED WHERE AN EXISTING WINDOW IS
 REPLACED AND WHERE ALL OF THE FOLLOWING APPLY TO THE
 REPLACEMENT WINDOW:
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-01-04 Cont ID  
Sent By jpearson Date 2019-01-04 Time 09:24 Rev Time 0.00
Received By jpearson Date 2019-01-04 Time 09:24 Sent To  
Notes
2019-01-04 08:14:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING EXISTING BUILDING 2017 6TH
 EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
 (NOT PROVIDED)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-26 Cont ID  
Sent By jpearson Date 2018-09-26 Time 16:18 Rev Time 0.00
Received By jpearson Date 2018-09-26 Time 16:18 Sent To  
Notes
2018-09-26 16:17:58CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING EXISTING BUILDING 2017 6TH
 EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. LOAD CALCULATION FOR HOUSE PANEL SHOWS DEMAND
 FACTORS FROM NEC 220.82. THESSE DEMAND FACTORS ARE NOT
 PERMITTED ON FEDDERS WITH LESS THAN 100 AMPS CAPACITY.
 PROVIDE CORRECTION. NEC 220.82
 2. LOAD CALCULATION FOR PANEL B SHOWS ALL LOADS ADDED
 TOGETHER AND THEN DEMAND FACTORS APPLIED. THE AC SHOULD
 NOT BE INCLUDED IN THESE DEMAND FACTORS.THE LOAD FOR AC
 SHOULD BE AT 100% OF AC, OR 65% OF HEAT, WHICHEVER IS
 LARGER. PROVIDE CORRECTION. NEC 220.82
 3. LOAD CALCULATION FOR PANEL A SHOWS THE AC AT 65%.THE
 LOAD FOR AC SHOULD BE AT 100% OF AC, OR 65% OF HEAT,
 WHICHEVER IS LARGER. PROVIDE CORRECTION. NEC 220.82
 4. THIS APPEARS TO BE A LEVEL 2 ALTERATION, ALTHOUGH IT
 IS SHOWN AS A REPAIR ON THE PLAN. HOWEVER, ADDITIONAL
 AC EQUIPMENT IS BEING ADDED, SO IT WOULD APPEAR THAT IT
 SHOULD BE LEVEL 2. PROVIDE CLARIFICATION. FBC EX 504.1
 5. IF LEVEL 2 ALTERATION, PROVIDE UPGRADE OF ELECTRICAL
 IN WORK AREAS TO INCLUDE OUTLET SPACING, AFCI AND GFCI
 PROTECTION, AND MINIMUM LIGHTING REQUIREMENTS. FBC EX
 808.3; NEC 210.8, 210.12
 6. IF EXISTING ELECTRICAL MEETS THE REQUIREMENTS IN
 COMMENT 5, SHOW ON PLAN. WPB FBC 107.2.1
 7. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-12-17 Cont ID  
Sent By scaldero Date 2018-12-17 Time 09:35 Rev Time 0.00
Received By scaldero Date 2018-12-17 Time 09:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-08-28 Cont ID  
Sent By scaldero Date 2018-08-28 Time 13:46 Rev Time 0.00
Received By scaldero Date 2018-08-28 Time 12:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-15 Cont ID  
Sent By gjohnson Date 2019-01-15 Time 12:23 Rev Time 0.00
Received By gjohnson Date 2018-12-13 Time 08:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-24 Cont ID  
Sent By dbattles Date 2018-10-24 Time 10:57 Rev Time 0.00
Received By dbattles Date 2018-08-23 Time 10:27 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2018-10-24 Cont ID  
Sent By dbattles Date 2018-10-24 Time 10:57 Rev Time 0.00
Received By dbattles Date 2018-10-24 Time 10:56 Sent To  
Notes
2018-10-24 10:57:53NO CHANGE IN OCCUPANCY OR AREA.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-01-07 Cont ID  
Sent By ccole Date 2019-01-07 Time 15:39 Rev Time 0.00
Received By ccole Date 2019-01-07 Time 14:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-10-03 Cont ID  
Sent By ccole Date 2018-10-03 Time 17:10 Rev Time 0.00
Received By ccole Date 2018-09-28 Time 17:12 Sent To  
Notes
2018-10-03 17:34:441ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18080908
 10/3/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) DESIGN CRITERIA: PROVIDE A LIST OF CURRENT CODES AND
 STANDARDS USED IN THE DESIGN OF THE PROJECT. SHEET A101
 IS LISTING THE PROJECT AS REPAIR PER CHAPTER 6 OF THE
 FBC EX, HOWEVER THE INSTALLATION OF NEW CENTRAL AC
 SYSTEMS IN THE APARTMENTS IS DEEMED A LEVEL 2
 ALTERATION PER SECTION 504.1 FBC EX. ALSO, WINDOW
 REPLACEMENTS ARE DEEMED LEVEL 1 ALTERATIONS PER SECTION
 503.1 FBC EX. PLEASE UPDATE THE CODE DATA ACCORDINGLY.
  
 2) M201: INDICATE HOW ACCESS WILL BE PROVIDED TO THE
 NEW AIR HANDLERS IN THE NEW SOFFITS- SECTION 306.1 FBC
 M.
  
 3) M201: THE RETURN TRANSFERS IN BOTH A & B MODELS ARE
 UNDERSIZED- SEE SECTION 601.6 (2) FBC M AND ENLARGE THE
 GRILLS.
  
 4) M201: CLARIFY THE EXACT LOCATION OF THE NEW
 CONDENSERS AND PROVIDE INSTALLATION DETAILS- SECTION
 301.15 FBC M.
  
 5) M201: PROVIDE CONDENSATE DISPOSAL PLANS FOR THE AIR
 HANDLERS- SECION 307 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-01-15 Cont ID  
Sent By gjohnson Date 2019-01-15 Time 12:21 Rev Time 0.00
Received By gjohnson Date 2019-01-15 Time 12:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-10-09 Cont ID  
Sent By gjohnson Date 2018-10-09 Time 10:06 Rev Time 0.00
Received By gjohnson Date 2018-10-06 Time 07:10 Sent To  
Notes
2018-10-09 10:40:441ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE ENLARGED DETAIL FOR PLUMBING WORK IN THE
 KITCHENS WITH DIMENSIONS AND CLARIFY THAT THE SINK AND
 WATER HEATER IS BEING RELOCATED IN TYPE B UNITS IN
 ORDER TO CLARIFY SCOPE OF PLUMBING WORK. PER WPB AMEND
 TO FBC 107.2.1
  
 2. PROVIDE ENLARGED DETAIL FOR PLUMBING WORK IN THE
 BATHROOMS WITH THE DIMENSIONS SHOWING COMPLIANCE WITH
 FBC PL 405.3.1
  
 3. PLEASE CLARIFY WILL THE WATER HEATERS IN THE UNITS
 BE REPLACED WITH NEW PROVIDE NOTE ON PLAN. PER WPB
 AMEND TO FBC 107.2.1
  
 4. THE WATER HEATER DETAIL IS SHOWING A RECIRCULATION
 SYSTEM THE WATER ISOMETRIC FOR NEW LAUNDRY IS NOT
 SHOWING ONE PLEASE CLARIFY ALL PIPING SHALL COMPLY WITH
 FBCPL 504.6 PIPING FROM T+P VALVE SHALL DISCHARGE
 THROUGH AIR GAP IN THE SAME ROOM.
  
 5. THE SANITARY STACK FOR THE WASHING MACHINE STAND
 PIPE SHALL BE VENTED FBC PL 910.1
  
 6. THE SHUT OFF VALVES FOR THE STACKABLE WASHING
 MACHINE SHALL BE ACCESSIBLE WITHOUT MOVING THE
 APPLIANCE. PER FBC PL 606.3
  
 7. PROVIDE ENLARGED FLOOR PLAN. PER WPB AMEND TO FBC
 107.2.1.3 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8
 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER
 ACCEPTABLE MEDIUM. THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS
 RELATED TO RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE
 COMPATIBLE WITH THE ARCHIVE
 REQUIREMENTS OF FLORIDA STATUTES.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-12-21 Cont ID  
Sent By dbattles Date 2018-12-21 Time 09:05 Rev Time 0.00
Received By dbattles Date 2018-12-21 Time 09:05 Sent To  
Notes
2018-12-21 09:06:11ALL NEW DRAWINGS IN DRAWING FOLDER ARE NOT DIGITALLY
 SIGNED.
 PLEASE UPLOAD DIGITALLY SIGNED PDF'S.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-09-26 Cont ID  
Sent By jpearson Date 2018-09-26 Time 16:19 Rev Time 0.00
Received By jpearson Date 2018-09-26 Time 16:19 Sent To  
Notes
2018-09-26 16:19:14ALL SHEETS OK, NEED TO BE CHECKED AT RESUBMITAL FOR ANY
 NEW SHEETS. FS 471, 481; WPB FBC 107.1

Review Stop Z ZONING
Rev No 2 Status P Date 2018-12-31 Cont ID  
Sent By awooten Date 2018-12-31 Time   Rev Time 0.00
Received By awooten Date 2018-12-31 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-09-07 Cont ID  
Sent By awooten Date 2018-09-07 Time   Rev Time  
Received By awooten Date 2018-09-07 Time   Sent To  
Notes
2018-09-07 15:46:43*******************************************************
 ********ZONING REVIEW FAILED***************************
 *************************
  
 ARE YOU REPLACING THE EXISTING WINDOWS WITH THE SAME
 TYPE OF WINDOWS?
  
 FENCE REPAIR REQUIRES A SEPARATE PERMIT.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]