| Plan Review Stops For Permit 18080843 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-10-31 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-10-31 |
Time |
12:11 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-10-31 |
Time |
10:49 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-08-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-08-24 |
Time |
07:56 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-08-24 |
Time |
07:56 |
Sent To |
|
|
| Notes |
| 2018-08-24 08:00:10 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE 48" X | | | 72" RUSKIN MODEL ELF6375DXD LOUVER. FBC 107.3.4 - | | | PROVIDE TWO SETS OF PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001 PER | | | FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-10-19 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-10-19 |
Time |
09:14 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-10-19 |
Time |
09:14 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-08-29 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-08-29 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-08-28 |
Time |
17:23 |
Sent To |
|
|
| Notes |
| 2018-08-29 09:15:46 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | NEED TO SUBMIT CUT CHEETS FOR THE FIRE PUMP CONTROLLER. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-10-17 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2018-10-17 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2018-10-17 |
Time |
10:10 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-08-24 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2018-08-24 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2018-08-24 |
Time |
09:04 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2018-11-14 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-11-14 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-11-14 |
Time |
10:54 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2018-10-31 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-10-31 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-10-30 |
Time |
05:49 |
Sent To |
|
|
| Notes |
| 2018-10-30 11:44:56 | 1) SHT. M-1 - THE PLANS NOTE THE GAS SYSTEM PRESSURE IS | | | 11 INCHES WATER COLUMN WITH A PRESSURE DROP OF 6.0 IN. | | | WATER COLUMN BUT ON PAGE 5 IN THE REGULATOR | | | SPECIFICATIONS YOU HAVE HIGHLIGHTED A 14 INCH WATER | | | COLUMN CAPACITY TABLE WITH A 2 INCH WATER COLUMN DROP. | | | THIS IS AT THE TOP OF THE PAGE. CLARIFY. | | | 2) SUPPLY INFORMATION FOR THE SPACING OF THE EXHAUST | | | SUPPORTS. ALSO, THE SUPPORT DETAIL ON SHT. M-1 SHOWS A | | | PLASTIC ALL THREAD THROUGH THE CLEVIS HANGER. IS THIS | | | CORRECT? PLEASE ADVISE. | | | 3) THE GENERAC SPECS NOTE THE BTU LOAD OF THE GENERATOR | | | AS 2,340,000 BTU'S AND THE GAS PLAN SHOWS 2,800,000. | | | CLARIFY. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-10-25 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-09-05 |
Time |
11:45 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-09-04 |
Time |
11:45 |
Sent To |
|
|
| Notes |
| 2018-10-25 11:46:26 | 1) TWO DIFFERENT GAS PIPING RISERS HAVE BEEN SUBMITTTED | | | FOR THIS WORK. ONE IS FROM ROSADO PROPANE SERVICES AND | | | THE OTHER HAS BEEN DONE BY THE ENGINEER OF RECORD. | | | SUBMIT TWO COPIES OF THE CORRECT GAS DRAWING TO BE | | | SUBMITTED. FBC 107.2. | | | 2) INDICATE ON THE PLAN THE OPERATING PRESSURE OF THE | | | SYSTEM DOWNSTREAM OF THE REGULATOR FOR THE GENERATOR. | | | ROSADO PROPANE HAS SUBMITTED A SIZING TABLE FOR 5 PSI | | | AND SHT. M-1 SHOWS A PRESSURE OF LESS THAN 2 | | | PSI.CLARIFY. | | | 3) SHOW THE PSI OF THE SYSTEM DOWNSTREAM OF THE | | | EXISTING GAS METER AND SHOW THE LOCATION OF ANY | | | EXISTING GAS REGULATORS ON THE ROSADO PROPANE DRAWING | | | IF THAT IS THE DRAWING TO BE USED. FBC 107.2.1. | | | 4) THE GENERATOR SPECIFICATIONS AND THE DRAWING FROM | | | ROSADO PROPANE CALL OUT A 2 INCH GAS SUPPLY LINE TO THE | | | GENERATOR AND THE GAS RISER DRAWING ON SHT. M-1 SHOWS A | | | 1 1/2 INCH GAS SUPPLY LINE. CLARIFY. | | | 5) SHOW THE DISTANCE OF THE 2ND STAGE REGULATOR TO THE | | | GENERATOR ON THE GAS DRAWING TO BE USED. FBC 107.2.1. | | | 6) THE GAS INFO PAGE FROM ROSADO PROPANE NOTES PIPE | | | SIZING FOR NEW GAS LINE IS BASED ON TABLE 402.4 (7) FOR | | | A 5 PSI SYSTEM BUT ALSO REFERENCES THE SAME SIZING | | | TABLE FOR A LESS THAN 2 PSI SYSTEM. CLARIFY.THIS | | | INFORMATION CONFLICTS WITH THE INFORMATION PROVIDED BY | | | THE ENGINEER ON SHT. M-1. CLARIFY. | | | 7) THE GAS DRAWING FROM ROSADO PROPANE SHOWS A 10 PSI | | | GAS METER YET DRAWING M-1 SHOWS A LESS THAN 2 PSI | | | PRESSURE. CLARIFY. | | | 8) THE GAS PIPING FROM ROSADO PROPANE SHOWS GALVANIZED | | | PIPING TO BE RRUN UNDERGROUND.GALVANIZED PIPING SHALL | | | NOT BE USED UNDERGROUND PER FBC-FUEL GAS SEC.404.11, | | | 404.11.1. | | | 9) SUBMIT COMBUSTION CALCULATIONS FOR CCOMBUSTION AIR. | | | FBC-FUEL GAS SEC.304.1,304.6.2. | | | 10) SUBMIT MANUFACTURER'S SPECIFICATIONS AND | | | INSTALLATION DETAILS FOR THE NEW EXHAUST PIPE FROM THE | | | GENERATOR ( TYPE OF PIPE, TYPE OF SUPPOTS, SUPPORT | | | SPACING, ETC.). | | | 11) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | | MINIMUM REQUIRED CLEARANCES AROUND THE GENERATOR. FBC | | | 107.2.1. | | | 12) SUBMIT MANUFACTURER?S SPECIFICATIONS AND | | | INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS. | | | IDENTIFY ON THE SPECIFICATION SHEETS WHICH MODEL | | | REGULATOR IS BEING INSTALLED AND THE ORIFICE SIZE TO | | | ENSURE THE REGULATOR CAN ACCOMMODATE THE BTU LOAD | | | THROUGH THE REGULATOR.2017 FGC SEC.410.1, 2017 FBC-RES. | | | SEC. G2421.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-11-14 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-11-14 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-11-01 |
Time |
13:51 |
Sent To |
|
|
| Notes |
| 2018-11-02 13:52:05 | RESUB ROUTED TO TKLARGE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-10-31 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-10-31 |
Time |
12:13 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-10-01 |
Time |
15:05 |
Sent To |
|
|
| Notes |
| 2018-10-02 15:05:27 | RESUB ROUTED TO ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-09-05 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-09-05 |
Time |
07:29 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-08-16 |
Time |
12:59 |
Sent To |
|
|
| Notes |
| 2018-08-17 12:59:28 | ROUTED TO ZONING INBOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2018-08-29 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2018-08-29 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2018-08-29 |
Time |
13:23 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2018-11-14 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-11-14 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-11-14 |
Time |
10:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-09-05 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-09-05 |
Time |
07:28 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-09-04 |
Time |
05:48 |
Sent To |
I |
|
| Notes |
| 2018-09-04 14:31:04 | 1) TWO DIFFERENT GAS PIPING RISERS HAVE BEEN SUBMITTTED | | | FOR THIS WORK. ONE IS FROM ROSADO PROPANE SERVICES AND | | | THE OTHER HAS BEEN DONE BY THE ENGINEER OF RECORD. | | | SUBMIT TWO COPIES OF THE CORRECT GAS DRAWING TO BE | | | SUBMITTED. FBC 107.2. | | | 2) INDICATE ON THE PLAN THE OPERATING PRESSURE OF THE | | | SYSTEM DOWNSTREAM OF THE REGULATOR FOR THE GENERATOR. | | | ROSADO PROPANE HAS SUBMITTED A SIZING TABLE FOR 5 PSI | | | AND SHT. M-1 SHOWS A PRESSURE OF LESS THAN 2 | | | PSI.CLARIFY. | | | 3) SHOW THE PSI OF THE SYSTEM DOWNSTREAM OF THE | | | EXISTING GAS METER AND SHOW THE LOCATION OF ANY | | | EXISTING GAS REGULATORS ON THE ROSADO PROPANE DRAWING | | | IF THAT IS THE DRAWING TO BE USED. FBC 107.2.1. | | | 4) THE GENERATOR SPECIFICATIONS AND THE DRAWING FROM | | | ROSADO PROPANE CALL OUT A 2 INCH GAS SUPPLY LINE TO THE | | | GENERATOR AND THE GAS RISER DRAWING ON SHT. M-1 SHOWS A | | | 1 1/2 INCH GAS SUPPLY LINE. CLARIFY. | | | 5) SHOW THE DISTANCE OF THE 2ND STAGE REGULATOR TO THE | | | GENERATOR ON THE GAS DRAWING TO BE USED. FBC 107.2.1. | | | 6) THE GAS INFO PAGE FROM ROSADO PROPANE NOTES PIPE | | | SIZING FOR NEW GAS LINE IS BASED ON TABLE 402.4 (7) FOR | | | A 5 PSI SYSTEM BUT ALSO REFERENCES THE SAME SIZING | | | TABLE FOR A LESS THAN 2 PSI SYSTEM. CLARIFY.THIS | | | INFORMATION CONFLICTS WITH THE INFORMATION PROVIDED BY | | | THE ENGINEER ON SHT. M-1. CLARIFY. | | | 7) THE GAS DRAWING FROM ROSADO PROPANE SHOWS A 10 PSI | | | GAS METER YET DRAWING M-1 SHOWS A LESS THAN 2 PSI | | | PRESSURE. CLARIFY. | | | 8) THE GAS PIPING FROM ROSADO PROPANE SHOWS GALVANIZED | | | PIPING TO BE RRUN UNDERGROUND.GALVANIZED PIPING SHALL | | | NOT BE USED UNDERGROUND PER FBC-FUEL GAS SEC.404.11, | | | 404.11.1. | | | 9) SUBMIT COMBUSTION CALCULATIONS FOR CCOMBUSTION AIR. | | | FBC-FUEL GAS SEC.304.1,304.6.2. | | | 10) SUBMIT MANUFACTURER'S SPECIFICATIONS AND | | | INSTALLATION DETAILS FOR THE NEW EXHAUST PIPE FROM THE | | | GENERATOR ( TYPE OF PIPE, TYPE OF SUPPOTS, SUPPORT | | | SPACING, ETC.). | | | 11) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | | MINIMUM REQUIRED CLEARANCES AROUND THE GENERATOR. FBC | | | 107.2.1. | | | 12) SUBMIT MANUFACTURER?S SPECIFICATIONS AND | | | INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS. | | | IDENTIFY ON THE SPECIFICATION SHEETS WHICH MODEL | | | REGULATOR IS BEING INSTALLED AND THE ORIFICE SIZE TO | | | ENSURE THE REGULATOR CAN ACCOMMODATE THE BTU LOAD | | | THROUGH THE REGULATOR.2017 FGC SEC.410.1, 2017 FBC-RES. | | | SEC. G2421.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2018-10-26 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2018-10-26 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2018-10-25 |
Time |
16:57 |
Sent To |
G |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2018-10-09 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2018-10-09 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2018-10-09 |
Time |
15:58 |
Sent To |
FIRE |
|
| Notes |
| 2018-10-09 16:07:05 | ZONING REVIEW FAILED, DUE TO THE FOLLOWING: | | | | | | 1) RESPOND TO COMMENTS IN WRITING. OTHER REVIEWERS WERE | | | ADDRESSED EXCEPT ZONING. | | | 2) PROVIDE A SURVEY/SITE PLAN SHOWING LOCATION OF | | | GENERATOR AND SETBACKS TO PROPERTY LINES. | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT | | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | MAGGIE CRUZ | | | ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: 561-822-1442 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2018-08-22 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2018-08-22 |
Time |
16:06 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2018-08-22 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2018-08-22 16:06:46 | ZONING REVIEW FAILED, DUE TO THE FOLLOWING: | | | | | | 1) PROVIDE A SURVEY SHOWING LOCATION OF GENERATOR AND | | | SETBACKS TO PROPERTY LINES. | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT | | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | MAGGIE CRUZ | | | ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: 561-822-1442 | | | E-MAIL: [email protected] |
|
|