Plan Review Details - Permit 18080839
Plan Review Stops For Permit 18080839
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-09-19 Cont ID  
Sent By skennedy Date 2018-09-19 Time 08:55 Rev Time 0.00
Received By skennedy Date 2018-09-19 Time 08:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-31 Cont ID  
Sent By cthroop Date 2018-08-31 Time 09:59 Rev Time 0.00
Received By cthroop Date 2018-08-30 Time 11:49 Sent To  
Notes
2018-08-31 11:26:11BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PALM BEACH COUNTY IMPACT FEES MAY BE REQUIRED.
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 2. ROOFING PERMIT WILL BE REQUIRED.
  
 3. PROVIDE ENERGY CALC'S. CANNOT VERIFY R - VALUE OF
 CEILING AND WALL INSULATION NOTED ON PLANS.
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES. ENERGY
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 _ OR _
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 4. REFERENCE PLAN PAGE CS-3. EXPOSURE IS IDENTIFIED AS
 D. THE CORRECT EXPOSURE SHOULD BE B. PLEASE REVIEW YOUR
 DESIGN PRESSURES AND ENSURE THEY INCLUDE THIS ELEMENT.
 SURFACE ROUGHNESS B. URBAN AND SUBURBAN AREAS, WOODED
 AREAS OR OTHER TERRAIN WITH NUMEROUS CLOSELY SPACED
 OBSTRUCTIONS HAVING THE SIZE OF SINGLE-FAMILY DWELLINGS
 OR LARGER.
 SURFACE ROUGHNESS C. OPEN TERRAIN WITH SCATTERED
 OBSTRUCTIONS HAVING HEIGHTS GENERALLY LESS THAN 30 FEET
 (9144 MM). THIS CATEGORY INCLUDES FLAT OPEN COUNTRY AND
 GRASSLANDS. THIS SURFACE ROUGHNESS SHALL ALSO APPLY TO
 ANY BUILDING LOCATED WITHIN SURFACE ROUGHNESS B-TYPE
 TERRAIN WHERE THE BUILDING IS WITHIN 100 FEET (30.5 M)
 HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF SURFACE
 ROUGHNESS C- OR D-TYPE TERRAIN THAT EXTENDS MORE THAN
 600 FEET (182.9 M) AND WIDTH GREATER THAN 150 FEET
 (45.7 M) IN THE UPWIND DIRECTION.
 SURFACE ROUGHNESS D. FLAT, UNOBSTRUCTED AREAS AND WATER
 SURFACES. THIS CATEGORY INCLUDES SMOOTH MUD FLATS, SALT
 FLATS AND UNBROKEN ICE.
  
 5. REFERENCE PLAN PAGE A-7. PROPOSED 1/2 INCH PLYWOOD
 TO BE USED FOR UNDERLAYMENT AND IN CONTACT WITH
 CONCRETE SHALL BE PROTECTED OR PRESSURE TREATED.
 R317.1.2 GROUND CONTACT.
 ALL WOOD IN CONTACT WITH THE GROUND, EMBEDDED IN
 CONCRETE IN DIRECT CONTACT WITH THE GROUND OR EMBEDDED
 IN CONCRETE EXPOSED TO THE WEATHER THAT SUPPORTS
 PERMANENT STRUCTURES INTENDED FOR HUMAN OCCUPANCY SHALL
 BE APPROVED PRESSURE-PRESERVATIVE-TREATED WOOD SUITABLE
 FOR GROUND CONTACT USE,
  
 6. PRODUCT APPROVALS FOR WINDOWS AND DOORS ARE MISSING
 THE CERTIFICATION AGENCY CERTIFICATE.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR
 SUBMITTALS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-08-30 Cont ID  
Sent By jleahy Date 2018-08-30 Time 11:46 Rev Time 0.00
Received By jleahy Date 2018-08-30 Time 11:46 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-09-12 Cont ID  
Sent By fmittner Date 2018-09-12 Time 16:38 Rev Time 0.00
Received By fmittner Date 2018-09-12 Time 16:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-19 Cont ID  
Sent By skennedy Date 2018-09-19 Time 08:55 Rev Time 0.00
Received By skennedy Date 2018-09-19 Time 08:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-13 Cont ID  
Sent By skennedy Date 2018-09-13 Time 11:04 Rev Time 0.00
Received By skennedy Date 2018-08-16 Time 15:50 Sent To  
Notes
2018-08-17 15:50:35R23

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-09-24 Cont ID  
Sent By skennedy Date 2018-09-24 Time 08:48 Rev Time 0.00
Received By skennedy Date 2018-09-19 Time 08:41 Sent To  
Notes
2018-09-19 08:42:08APPLICANT HAS ONE SET FOR IMPACT FEE REVIEW.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-08-31 Cont ID  
Sent By cthroop Date 2018-08-31 Time 08:12 Rev Time 0.00
Received By cthroop Date 2018-08-30 Time 14:18 Sent To  
Notes
2018-08-31 08:13:44BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-09-19 Cont ID  
Sent By skennedy Date 2018-09-19 Time 08:55 Rev Time 0.00
Received By skennedy Date 2018-09-19 Time 08:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-09-13 Cont ID  
Sent By skennedy Date 2018-09-13 Time 10:32 Rev Time 0.00
Received By skennedy Date 2018-09-13 Time 10:32 Sent To  
Notes
2018-09-13 10:46:351ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL
 1ST REVIEW FBC 2017 EXISTING BUILDING
  
 FAILED
  
 1. FBCR-M1602.3 BALANCED RETURN AIR REQUIRED .
  
 SHEET M1 THE RETURN AIR SYSTEM IS UNDERSIZED. M1602.3
 EXCEPTION 1. ALLOWS THE FOLLOWING: TRANSFER DUCTS MAY
 ACHIEVE THE REQUIREMENT BY INCREASING THE RETURN
 TRANSFER 11/2 TIMES THE CROSS SECTIONAL AREA (SQUARE
 INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR SPACE
 IT IS SERVING AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1-INCH UNDERCUT TO ACHIEVE PROPER RETURN
 AIR BALANCE.
  
 2. THIS STRUCTURE IS IDENTIFIED AS A CONTRIBUTING
 HISTORIC STRUCTURE ON THE CITY HISTORIC DISTRICT MAPS,
 ACCORDINGLY, COMPLIANCE WITH THE FBC ENERGY CODE IS NOT
 REQUIRED PER SECTION. R101.4.2.3. PLEASE NOTE THAT
 INACCURATE AND INCOMPLETE ENERGY FORMS WERE SUBMITTED
 FOR REVIEW. PLEASE ELECT TO REMOVE SUCH FORMS FROM THE
 SUBMITTAL AND IF SO PLEASE INDICATE THE APPLICABILITY
 OF THE EXEMPTION IN THE PROPERTY INFORMATION OR SCOPE
 OF WORK ON SHEET CS-2 OTHERWISE SUPPLY ACCURATE
 INFORMATION. IT IS FURTHER NOTED THAT THE WALL &
 CEILING SECTIONS SHOWN ON SHEET A-7 INDCATE INSULATION
 VALUES THAT APPEAR NOT POSSIBLE TO ACHIEVE GIVEN THE
 WALL ASSEMBLY TYPE. THE EQUIPMENT SIZING CALCULATION
 WHICH IS NOT REQUIRED LACKS AN ENERGY CALCULATION BASIS
 DETERMINING THE COOLING DEMAND EXPRESSED IN BTU'S AND
 LACKS THE MODEL AND ANY ACCURATE BASIS TO DETERMINE
 COOLING CAPACITY. YOU MAY ELCET TO REMOVE THE SIZING
 CALCULATION OR SUBMIT FULL ACCURATE INFORMATION.
  
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-08-23 Cont ID  
Sent By lcrespo Date 2018-08-23 Time 17:58 Rev Time 0.00
Received By lcrespo Date 2018-08-23 Time 17:58 Sent To  
Notes
2018-08-23 17:59:3808/23/18 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2018-08-31 Cont ID  
Sent By cthroop Date 2018-08-31 Time 11:26 Rev Time 0.00
Received By cthroop Date 2018-08-31 Time 11:26 Sent To  
Notes
2018-08-31 11:26:53ROOFING

Review Stop Z ZONING
Rev No 1 Status P Date 2018-09-12 Cont ID  
Sent By fmittner Date 2018-09-12 Time 16:38 Rev Time 0.00
Received By fmittner Date 2018-09-12 Time 16:38 Sent To  
Notes
***NONE***