Plan Review Details - Permit 18080708
Plan Review Stops For Permit 18080708
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-01 Cont ID  
Sent By dbattles Date 2018-10-01 Time 09:00 Rev Time 0.00
Received By dbattles Date 2018-09-28 Time 11:04 Sent To  
Notes
2018-10-01 09:01:15****CORRECTIONS****
 W.P.B. PERMIT: 18080708
 REVIEWED: SEPTEMBER 28, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC AMENDED R107.2.5]SHEET A1 DATA. THE USE TYPE
 WOULDN?T BE R-2, BUT IT SHOULD BE GROUP U PRIVATE
 GARAGE. ALSO, CHECK CONSTRUCTION TYPE III. WALLS WILL
 HAVE WOOD FURRING IN THEM, SO TYPE VB MAY BE
 APPROPRIATE. PLEASE USE FBC TABLE 601 TO CHOOSE
 CONSTUCTION TYPE AND INCLUDE A OR B IN THE TYPE BEING
 UTILIZED.
  
 2. [FBC R404.1.6] CONCRETE AND MASONRY FOUNDATION WALLS
 SHALL EXTEND ABOVE THE FINISHED GRADE ADJACENT TO THE
 FOUNDATION AT ALL POINTS A MINIMUM OF 4 INCHES (102 MM)
 WHERE MASONRY VENEER IS.
  
 3. [FBC R403.1.4]MINIMUM DEPTH.
 EXTERIOR FOOTINGS SHALL BE PLACED NOT LESS THAN 12
 INCHES (305 MM) BELOW THE UNDISTURBED GROUND SURFACE.
 WHERE APPLICABLE, THE DEPTH OF FOOTINGS SHALL ALSO
 CONFORM TO SECTIONS R403.1.4.1 THROUGH R403.1.4.2.
  
 4. [FBC R402.4]AIR LEAKAGE (MANDATORY).THE GARAGE DOOR
 WILL BE A BREAK IN THERMAL ENVELOPE. IS THIS DOOR GOING
 TO BE INSULATED? HOW DOES THE GARAGE DOOR MEET
 REQUIRMENTS FOR THERMAL ENVELOPE APPROACH?
  
 5. [FBC TABLE R402.1.2]WHAT IS THE SHGC OF THE GLASS IN
 THE ALUMINUM OUTSWING DOOR? IS THE GLASS INSULATED?
  
 6. [FBC AMENDED 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS TO
 THE BUILDING INSPECTOR PRIOR TO INSTALLATION.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-17 Cont ID  
Sent By jpearson Date 2018-09-17 Time 08:48 Rev Time 0.00
Received By jpearson Date 2018-09-17 Time 08:20 Sent To  
Notes
2018-09-17 08:47:58CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
 2. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. LOAD CALCULATION PROVIDED IS NOT
 PER CODE FOR RESIDENTIAL. NEC 215.2, 220, 408.30; FBC
 RE E3602.2
 3. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL B. NEC 225.31,
 225.32
 4. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 5. PLAN SHOWS A 3/0 FEEDER TO SUB-PANEL B FED FROM A 50
 AMP BREAKER IN PANEL A. I AM NOT AWARE OF A 50 AMP
 BREAKER THAT WILL ACCEPT 3/0 WIRE. PROVIDE
 CLARIFICATION AND/OR CORRECTION. NEC 110.3; FBC 107.2.1
 6. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "OLD
 SHEETS".
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-03 Cont ID  
Sent By hmoser Date 2018-10-03 Time 15:57 Rev Time 0.00
Received By hmoser Date 2018-08-14 Time 10:19 Sent To  
Notes
2018-08-16 10:19:25R34

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-10-01 Cont ID  
Sent By dbattles Date 2018-10-01 Time 09:01 Rev Time 0.00
Received By dbattles Date 2018-10-01 Time 09:01 Sent To  
Notes
2018-10-01 09:02:03[FBC AMENDED 109]PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-10-03 Cont ID  
Sent By hmoser Date 2018-10-03 Time 15:56 Rev Time 0.00
Received By hmoser Date 2018-10-03 Time 15:27 Sent To I
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2018-10-01 Cont ID  
Sent By dbattles Date 2018-10-01 Time 09:13 Rev Time 0.00
Received By dbattles Date 2018-10-01 Time 09:13 Sent To  
Notes
2018-10-01 09:14:51NOA AND ENGINEERING FOR FLAT ROOF PROVIDED.

Review Stop Z ZONING
Rev No 1 Status P Date 2018-08-28 Cont ID  
Sent By mcruz Date 2018-08-28 Time 16:58 Rev Time 0.00
Received By mcruz Date 2018-08-28 Time 16:57 Sent To  
Notes
2018-08-28 16:58:11ZONING PASSED WITH THE FOLLOWING PROVISO: GARAGE SHALL
 BE AT 6' FROM THE PRINCIPAL STRUCTURE.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]