Plan Review Details - Permit 18080699
| Plan Review Stops For Permit 18080699 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-09-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-09-17 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-09-17 |
Time |
16:32 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-08-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-08-27 |
Time |
08:09 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-08-27 |
Time |
07:57 |
Sent To |
I |
|
| Notes |
| 2018-08-27 08:09:48 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) ONE SET OF THE GENERATOR PAD ENGINEERED DRAWINGS IS | | | REQUIRED TO HAVE THE ENGINEER'S ORIGINAL SEAL AND | | | HANDWRITTEN SIGNATURE. 61G15-23.003 PROCEDURES FOR | | | PHYSICALLY SIGNING AND SEALING PLANS, SPECIFICATIONS, | | | REPORTS OR OTHER DOCUMENTS. | | | ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER | | | DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN | | | ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025, | | | F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY | | | SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE | | | PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. | | | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE | | | LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE | | | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR | | | COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE | | | USED. | | | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY | | | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY | | | OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE | | | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL | | | NOT RENDER THE SIGNATURE ILLEGIBLE. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-09-14 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-09-14 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-09-14 |
Time |
10:19 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-08-21 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-08-21 |
Time |
08:46 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-08-21 |
Time |
08:46 |
Sent To |
|
|
| Notes |
| 2018-08-21 08:46:53 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET | | | OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE | | | SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE | | | DESIGN. PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS | | | 471, 481 | | | 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC | | | 109.3 | | | 3. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL | | | LOADS. SHOW WHICH LOADS, IF ANY, WILL BE AUTOMATICALLY | | | MANAGED. CURRENT FORMAT PROVIDED IS CONFUSING AND | | | DIFFICULT TO UNDERSTAND. SEE FBC RESIDENTAIL FOR PROPER | | | FORMAT. NEC 220, 702.4(B)(2); FBC RE E3602.2 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD | | | SHEETS?. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2018-09-13 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-09-13 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-09-13 |
Time |
16:08 |
Sent To |
E |
|
| Notes |
| 2018-09-13 16:23:55 | 09/13/18 REVIEWED FOR CODE COMPLIANCE (GAS) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM | | | THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND | | | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF | | | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY | | | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-08-17 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-08-17 |
Time |
06:56 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-08-17 |
Time |
06:56 |
Sent To |
|
|
| Notes |
| 2018-08-17 06:56:15 | 08/17/2018 1ST PLUMBING/GAS REVIEW **DENIED** WITH | | | COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. THE ISOMETRIC SHOWS ONE GAS LINE FROM THE METER. | | | THERE IS AN EXISTING SYSTEM FOR THE HOME PLEASE SHOW ON | | | ISOMETRIC THE BTU LOAD OF THE EXISTING GAS SYSTEM, IT | | | MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO | | | ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF | | | UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO | | | ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING | | | RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING | | | APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE | | | SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE | | | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT | | | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF | | | THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN | | | A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO | | | 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE | | | EXISTING APPLIANCES 2017 FBC FUEL GAS SECS. 401.4, | | | 401.8, 402.1, 402.2, 402.3 OR 2017 FBC FUEL GAS RES. | | | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. | | | 2. INDICATED THE NATURAL GAS METER IS A 2#, DOES THIS | | | MEAN THERE IS A SEPARATE OR SECOND METER OF THE SYSTEM | | | ON THE PLAN?, 2017 FBC FUEL GAS SEC. 402.2 OR 2017 FBC | | | FUEL GAS RES. SEC. G2413.2. | | | 3. I HAVE PRINTED THE EXISTING SYSTEM AND PLACED IT IN | | | YOU FILE AND I WILL EMAIL YOU SO YOU CAN REFER AND THEN | | | YOU CAN MAKE NECESSARY CHANGES, PLEASE NOTE THAT IS FOR | | | REFERENCE ONLY. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6720 | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2018-08-16 |
|
|
Cont ID |
|
| Sent By |
destabro |
Date |
2018-08-16 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
destabro |
Date |
2018-08-16 |
Time |
15:19 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-09-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-09-17 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-09-06 |
Time |
14:03 |
Sent To |
|
|
| Notes |
| 2018-09-07 14:03:35 | RESUB ROUTED TO LCRESPO |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-08-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-08-27 |
Time |
08:10 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-08-14 |
Time |
13:14 |
Sent To |
|
|
| Notes |
| 2018-08-15 13:15:09 | ROUTED TO ZONING INBOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-08-16 |
|
|
Cont ID |
|
| Sent By |
destabro |
Date |
2018-08-16 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
destabro |
Date |
2018-08-16 |
Time |
15:19 |
Sent To |
I |
|
| Notes |
|
|
|