Plan Review Details - Permit 18080699
Plan Review Stops For Permit 18080699
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-09-17 Cont ID  
Sent By rmcdouga Date 2018-09-17 Time 16:32 Rev Time 0.00
Received By rmcdouga Date 2018-09-17 Time 16:32 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-27 Cont ID  
Sent By rmcdouga Date 2018-08-27 Time 08:09 Rev Time 0.00
Received By rmcdouga Date 2018-08-27 Time 07:57 Sent To I
Notes
2018-08-27 08:09:48PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ONE SET OF THE GENERATOR PAD ENGINEERED DRAWINGS IS
 REQUIRED TO HAVE THE ENGINEER'S ORIGINAL SEAL AND
 HANDWRITTEN SIGNATURE. 61G15-23.003 PROCEDURES FOR
 PHYSICALLY SIGNING AND SEALING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-09-14 Cont ID  
Sent By jpearson Date 2018-09-14 Time 10:19 Rev Time 0.00
Received By jpearson Date 2018-09-14 Time 10:19 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-21 Cont ID  
Sent By jpearson Date 2018-08-21 Time 08:46 Rev Time 0.00
Received By jpearson Date 2018-08-21 Time 08:46 Sent To  
Notes
2018-08-21 08:46:53CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS
 471, 481
 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC
 109.3
 3. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. SHOW WHICH LOADS, IF ANY, WILL BE AUTOMATICALLY
 MANAGED. CURRENT FORMAT PROVIDED IS CONFUSING AND
 DIFFICULT TO UNDERSTAND. SEE FBC RESIDENTAIL FOR PROPER
 FORMAT. NEC 220, 702.4(B)(2); FBC RE E3602.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-09-13 Cont ID  
Sent By lcrespo Date 2018-09-13 Time 16:08 Rev Time 0.00
Received By lcrespo Date 2018-09-13 Time 16:08 Sent To E
Notes
2018-09-13 16:23:5509/13/18 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-08-17 Cont ID  
Sent By lcrespo Date 2018-08-17 Time 06:56 Rev Time 0.00
Received By lcrespo Date 2018-08-17 Time 06:56 Sent To  
Notes
2018-08-17 06:56:1508/17/2018 1ST PLUMBING/GAS REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE ISOMETRIC SHOWS ONE GAS LINE FROM THE METER.
 THERE IS AN EXISTING SYSTEM FOR THE HOME PLEASE SHOW ON
 ISOMETRIC THE BTU LOAD OF THE EXISTING GAS SYSTEM, IT
 MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO
 ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF
 UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES 2017 FBC FUEL GAS SECS. 401.4,
 401.8, 402.1, 402.2, 402.3 OR 2017 FBC FUEL GAS RES.
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
 2. INDICATED THE NATURAL GAS METER IS A 2#, DOES THIS
 MEAN THERE IS A SEPARATE OR SECOND METER OF THE SYSTEM
 ON THE PLAN?, 2017 FBC FUEL GAS SEC. 402.2 OR 2017 FBC
 FUEL GAS RES. SEC. G2413.2.
 3. I HAVE PRINTED THE EXISTING SYSTEM AND PLACED IT IN
 YOU FILE AND I WILL EMAIL YOU SO YOU CAN REFER AND THEN
 YOU CAN MAKE NECESSARY CHANGES, PLEASE NOTE THAT IS FOR
 REFERENCE ONLY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-08-16 Cont ID  
Sent By destabro Date 2018-08-16 Time 15:19 Rev Time 0.00
Received By destabro Date 2018-08-16 Time 15:19 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-17 Cont ID  
Sent By rmcdouga Date 2018-09-17 Time 16:32 Rev Time 0.00
Received By rmcdouga Date 2018-09-06 Time 14:03 Sent To  
Notes
2018-09-07 14:03:35RESUB ROUTED TO LCRESPO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-27 Cont ID  
Sent By rmcdouga Date 2018-08-27 Time 08:10 Rev Time 0.00
Received By rmcdouga Date 2018-08-14 Time 13:14 Sent To  
Notes
2018-08-15 13:15:09ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2018-08-16 Cont ID  
Sent By destabro Date 2018-08-16 Time 15:19 Rev Time 0.00
Received By destabro Date 2018-08-16 Time 15:19 Sent To I
Notes
***NONE***