Plan Review Details - Permit 18080669
Plan Review Stops For Permit 18080669
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-08-25 Cont ID  
Sent By rmcdouga Date 2018-08-25 Time 06:58 Rev Time 0.00
Received By rmcdouga Date 2018-08-25 Time 06:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-09-12 Cont ID  
Sent By jleahy Date 2018-09-12 Time 08:05 Rev Time 0.00
Received By jleahy Date 2018-09-12 Time 08:05 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-27 Cont ID  
Sent By jleahy Date 2018-08-27 Time 12:56 Rev Time 0.00
Received By jleahy Date 2018-08-27 Time 12:56 Sent To  
Notes
2018-08-27 12:57:25PROVIDE CUT SHEETS FOR EQUIPMENT, POOL PUMP, FILTER,
 LIGHT

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-08-30 Cont ID  
Sent By lcrespo Date 2018-08-30 Time 18:05 Rev Time 0.00
Received By lcrespo Date 2018-08-30 Time 18:05 Sent To  
Notes
2018-08-30 18:06:05GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE. AT
 THIS TIME. WPB AMENDMENTS TO FBC SEC. 107.2.1.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-13 Cont ID  
Sent By lmarchan Date 2018-09-13 Time 16:08 Rev Time 0.00
Received By lmarchan Date 2018-09-05 Time 13:49 Sent To  
Notes
2018-09-06 13:50:00RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-31 Cont ID  
Sent By cpuell Date 2018-08-31 Time 14:21 Rev Time 0.00
Received By cpuell Date 2018-08-14 Time 13:42 Sent To  
Notes
2018-08-15 13:42:46ROUTED TO ZONING INBOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-09-13 Cont ID  
Sent By lcrespo Date 2018-09-13 Time 15:51 Rev Time 0.00
Received By lcrespo Date 2018-09-13 Time 15:51 Sent To  
Notes
2018-09-13 15:52:3209/13/18 REVIEWED FOR CODE COMPLIANCE (PLUMBING/POOL)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-30 Cont ID  
Sent By lcrespo Date 2018-08-30 Time 17:58 Rev Time 0.00
Received By lcrespo Date 2018-08-30 Time 17:58 Sent To  
Notes
2018-08-30 17:59:5108/30/2018 1ST PLUMBING/POOL REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN
 DRAIN, GAS POOL HEATER AND THE PUMP. WPB AMENDMENTS TO
 FBC SEC. 107.2.1..
 2. SUBMIT SPECIFICATIONS FOR THE CARTRIDGE FILTER. WPB
 AMEND. TO FBC SEC. 107.2.1.
 3. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN
 DRAIN AND THE PUMP. WPB AMENDMENTS TO FBC SEC. 107.2.1.
 4. ALL GAS HEATERS SHALL HAVE A MINIMUM THERMAL
 EFFICIENCY OF 82 % FOR HEATERS MANUFACTURED ON OR AFTER
 APRIL 16, 2013, WHEN TESTED IN ACCORDANCE WITH ANSI Z
 21.56. POOL HEATERS FIRED BY NATURAL OR LP GAS SHALL
 NOT HAVE CONTINUOUSLY BURNING PILOT LIGHTS. 2017
 FBC-ENERGY - SEC. R403.10.4
 5. HEATED SWIMMING POOLS AND IN GROUND PERMANENTLY
 INSTALLED SPAS SHALL BE EQUIPPED WITH A VAPOR-RETARDANT
 COVER ON OR AT THE WATER SURFACE OR A LIQUID COVER OR
 OTHER MEANS PROVEN TO REDUCE HEAT LOSS. 2017 FBC-
 ENERGY- SEC. R 403.10.3.
 6. BACKFLOW PREVENTER REQUIRED PER THE CITY OF WEST
 PALM BEACH ORD #2853-95. A PERMIT REQUIRED BY A
 LICENSED CONTRACTOR AND MUST BE CERTIFIED BY UTILITIES
 PRIOR TO FINAL INSPECTION. A DUAL CHECK VALVE MAY BE
 USED IF NO POOL FILL IS INSTALLED AT THE METER AND
 INSTALLED BY UTILITIES WHICH DOES NOT REQUIRE A PERMIT
 SO PLEASE CONTACT CITY OF WPB UTILITIES AT 561-822-2240
 FOR FURTHER DIRECTIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop Z ZONING
Rev No 1 Status P Date 2018-08-22 Cont ID  
Sent By mcruz Date 2018-08-22 Time 15:02 Rev Time 0.00
Received By mcruz Date 2018-08-22 Time 15:00 Sent To  
Notes
***NONE***