Plan Review Details - Permit 18080621
Plan Review Stops For Permit 18080621
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-10-05 Cont ID  
Sent By pleduc Date 2018-10-05 Time   Rev Time 0.00
Received By pleduc Date 2018-10-05 Time 10:56 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-08-17 Cont ID  
Sent By pleduc Date 2018-08-17 Time   Rev Time 0.00
Received By pleduc Date 2018-08-15 Time 12:09 Sent To M
Notes
2018-08-16 16:57:53THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INCORRECT REFERENCE (2009) AND CODE
 SECTIONS INDICATED ON THE PLAN SHEET UNDER SYSTEM
 COMPLIANCE NOTES.
  
 PER THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE
 THE CORRECT 17 A CODE REFERENCE IS:
  
 NFPA 17A, STANDARD FOR WET CHEMICAL EXTINGUISHING
 SYSTEMS, 2013 EDITION.
  
  
 PLEASE REVIEW AND CORRECT THE EDITION AND THE CODE
 SECTIONS THAT ARE INSERTED.
  
  
  
 2) THERE IS NO INDICATIONS THAT THE SYSTEM IS TIED INTO
 THE BUILDINGS' FIRE ALARM SYSTEM.
  
 PER NFPA 17 A
  
 5.2.1.9 THE EXTINGUISHING SYSTEM SHALL BE CONNECTED TO
 THE
 FIRE ALARM SYSTEM, IF PROVIDED, IN ACCORDANCE WITH THE
 REQUIREMENTS
 OF NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE, SO
 THAT THE ACTUATION OF THE EXTINGUISHING SYSTEM WILL
 SOUND THE
 FIRE ALARM.
  
 ADDITIONALLY,
  
 PER NFPA 1
  
 13.7.1.2* BUILDING FIRE ALARM SYSTEMS. PROTECTED
 PREMISES FIRE
 ALARM SYSTEMS THAT SERVE THE GENERAL FIRE ALARM NEEDS
 OF A
 BUILDING OR BUILDINGS SHALL INCLUDE ONE OR MORE OF THE
 FOLLOWING
 SYSTEMS OR FUNCTIONS:
 (1) MANUAL FIRE ALARM SIGNAL INITIATION
 (2) AUTOMATIC FIRE ALARM AND SUPERVISORY SIGNAL
 INITIATION
 (3) MONITORING OF ABNORMAL CONDITIONS IN FIRE
 SUPPRESSION
 SYSTEMS
 (4) ACTIVATION OF FIRE SUPPRESSION SYSTEMS
  
 PER NFPA 101
  
 9.6.2 SIGNAL INITIATION.
 9.6.2.1 WHERE REQUIRED BY OTHER SECTIONS OF THIS CODE,
 ACTUATION
 OF THE FIRE ALARM SYSTEM SHALL OCCUR BY ANY OR ALL OF
 THE FOLLOWING
 MEANS OF INITIATION BUT SHALL NOT BE LIMITED TO SUCH
 MEANS:
 (1) MANUAL FIRE ALARM INITIATION
 (2) AUTOMATIC DETECTION
 (3) EXTINGUISHING SYSTEM OPERATION
  
 PER NFPA 96
  
 10.6.2 WHERE A FIRE ALARM SIGNALING SYSTEM IS SERVING
 THE OCCUPANCY
 WHERE THE EXTINGUISHING SYSTEM IS LOCATED, THE
 ACTIVATION
 OF THE AUTOMATIC FIRE-EXTINGUISHING SYSTEM SHALL
 ACTIVATE
 THE FIRE ALARM SIGNALING SYSTEM.
  
  
 PLEASE REVIEW AND CORRECT FOR FIRE ALARM ACTIVATION OR
 JUSTIFY WITH SPECIFIC CODE REFERENCES
  
  
  
  
 3) THERE IS NO CLEAR INDICATION OF THE LOCATION OF THE
 MANUAL ACTPULL STATION.
  
 5.2.1.10* A READILY ACCESSIBLE MEANS FOR MANUAL
 ACTUATION
 SHALL BE LOCATED IN A PATH OF EGRESS.
 5.2.1.10.1 WHEN MANUAL ACTUATION IS USED FOR
 COOKINGRELATED
 PROTECTION, THE MANUAL ACTUATION DEVICE SHALL BE
 INSTALLED
 NO MORE THAN 48 IN. (1200 MM) AND NO LESS THAN 42 IN.
 (1067 MM) ABOVE THE FLOOR.
 5.2.1.10.2 THE MANUAL ACTUATION DEVICE SHALL CLEARLY
 IDENTIFY
 THE HAZARD PROTECTED.
 5.2.1.11 AT LEAST ONE MANUAL ACTUATION DEVICE SHALL BE
 LOCATED IN
 ACCORDANCE WITH NFPA 96, STANDARD FOR VENTILATION
 CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS, OR AS
 DIRECTED BY THE
 AUTHORITY HAVING JURISDICTION, WITHIN THE LIMITATIONS
 OF THE MANUFACTURER?S
 DESIGN, INSTALLATION, AND MAINTENANCE MANUAL.
  
 10.5.1 A READILY ACCESSIBLE MEANS FOR MANUAL ACTIVATION
 SHALL
 BE LOCATED BETWEEN 1067 MM AND 1219 MM (42 IN. AND 48
 IN.)
 ABOVE THE FLOOR, BE ACCESSIBLE IN THE EVENT OF A FIRE,
 BE LOCATED
 IN A PATH OF EGRESS, AND CLEARLY IDENTIFY THE HAZARD
 PROTECTED.
 10.5.1.1 AT LEAST ONE MANUAL ACTUATION DEVICE SHALL BE
 LOCATED
 A MINIMUM OF 3 M (10 FT) AND A MAXIMUM OF 6 M (20 FT)
 FROM
 THE PROTECTED HOOD EXHAUST SYSTEM(S) WITHIN A PATH OF
 EGRESS
 OR AT AN ALTERNATIVE LOCATION ACCEPTABLE TO THE AHJ.
 10.5.1.2 MANUAL ACTIVATION USING A CABLE-OPERATED PULL
 STATION
 SHALL NOT REQUIRE MORE THAN 178 N (40 LB) OF FORCE,
 WITH A
 PULL MOVEMENT NOT TO EXCEED 356 MM (14 IN.) TO ACTIVATE
 THE
 AUTOMATIC FIRE-EXTINGUISHING EQUIPMENT.
  
  
 PLEASE REVIEW AND PROVIDE FOR THE ACURATE LOCATION.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-15 Cont ID  
Sent By cpuell Date 2018-10-15 Time 13:19 Rev Time 0.00
Received By cpuell Date 2018-10-01 Time 14:05 Sent To  
Notes
2018-10-02 14:05:40RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-21 Cont ID  
Sent By hmoser Date 2018-08-21 Time 13:44 Rev Time 0.00
Received By hmoser Date 2018-08-13 Time 15:53 Sent To  
Notes
2018-08-14 15:53:56ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-10-13 Cont ID  
Sent By cmontell Date 2018-10-13 Time 08:34 Rev Time 0.00
Received By cmontell Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-08-21 Cont ID  
Sent By hmoser Date 2018-08-21 Time 13:44 Rev Time 0.00
Received By hmoser Date 2018-08-21 Time 13:43 Sent To I
Notes
2018-08-21 13:44:15PLAN DENIED SEE FIRE COMMENTS. HM.