Plan Review Details - Permit 18080552
Plan Review Stops For Permit 18080552
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-09-17 Cont ID  
Sent By rmcdouga Date 2018-09-17 Time 18:15 Rev Time 0.00
Received By rmcdouga Date 2018-09-17 Time 18:15 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-20 Cont ID  
Sent By rmcdouga Date 2018-08-20 Time 08:01 Rev Time 0.00
Received By rmcdouga Date 2018-08-20 Time 08:01 Sent To E
Notes
2018-08-20 09:19:32 
 PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF GENERATOR PAD DETAILS. SPECIFY
 HOW THE GENERATOR WILL BE ATTACHED TO THE PAD IN ORDER
 TO RESIST WINDLOADS. PROVIDE DETAILS SUCH AS PAD
 DIMENSIONS, REINFORCING, ANCHORING FASTENER TYPES,
 SIZES, EMBED DEPTH, NUMBER AND LOCATIONS. FBC-R 301.2.1
  
 2) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-09-14 Cont ID  
Sent By jleahy Date 2018-09-14 Time 11:10 Rev Time 0.00
Received By jleahy Date 2018-09-14 Time 11:10 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-23 Cont ID  
Sent By jleahy Date 2018-08-23 Time 09:11 Rev Time 0.00
Received By jleahy Date 2018-08-23 Time 09:11 Sent To I
Notes
2018-08-23 10:24:01FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 RISER DIAGRAM SHOWS TWO ATS???
  
 PLEASE SHOW CLEARANCES AROUND GENERATOR AT SIDE OF
 HOUSE, WHICH MEET THE MANUFACTURERS RECOMENDATIONS.
  
 PLANS NEED TO BE SIGNED.
  
 NEED PAD DETAILS.
  
 VALUE TO LOW FOR 22K GENERATOR. MUST INCLUDE LABOR
 ESTIMATES AND ALL MATERIALS. ($750 PER KW IS WHAT WE
 USUALLY SEE)

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-09-13 Cont ID  
Sent By lcrespo Date 2018-09-13 Time 07:29 Rev Time 0.00
Received By lcrespo Date 2018-09-13 Time 07:29 Sent To  
Notes
2018-09-13 07:30:2609/13/18 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-08-17 Cont ID  
Sent By lcrespo Date 2018-08-17 Time 16:29 Rev Time 0.00
Received By lcrespo Date 2018-08-17 Time 16:29 Sent To  
Notes
2018-08-17 16:30:2508/17/2018 1ST PLUMBING/GAS REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THERE IS AN EXISTING SYSTEM FOR THE HOME PLEASE SHOW
 ON ISOMETRIC THE BTU LOAD OF THE EXISTING GAS SYSTEM,
 IT MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM
 TO ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF
 UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES 2017 FBC FUEL GAS SECS. 401.4,
 401.8, 402.1, 402.2, 402.3 OR 2017 FBC FUEL GAS RES.
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. PLEASE LABEL TYPE OF GAS ON PLAN. (LP OR NATURAL).
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 4. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL GAS SEC.
 409.4, FBC FUEL GAS RES. SEC. G2420.4.
  
 5. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2017 FBC FUEL GAS RES. SEC.
 G2412.4, G2412.8, G2413.1, G2413.2, & G2413.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-17 Cont ID  
Sent By rmcdouga Date 2018-09-17 Time 18:15 Rev Time 0.00
Received By rmcdouga Date 2018-09-04 Time 13:27 Sent To  
Notes
2018-09-05 13:27:40RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-23 Cont ID  
Sent By jleahy Date 2018-08-23 Time 10:24 Rev Time 0.00
Received By jleahy Date 2018-08-10 Time 14:46 Sent To  
Notes
2018-08-13 14:46:47RESUB ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2018-09-11 Cont ID  
Sent By mcruz Date 2018-09-11 Time 09:16 Rev Time 0.00
Received By mcruz Date 2018-09-11 Time 09:13 Sent To P
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-08-16 Cont ID  
Sent By mcruz Date 2018-08-16 Time 16:55 Rev Time 0.00
Received By mcruz Date 2018-08-16 Time 16:48 Sent To  
Notes
2018-08-16 16:55:29ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) INDICATE SETBACK DIMENSION FROM GENERATOR TO
 PROPERTY LINE. THE PLAN SHOWS SETBACK TO FENCE. THE
 GENERATOR SHALL BE AT LEAST 3.5' FROM PROPERTY LINE.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]
  