Plan Review Details - Permit 18080513
Plan Review Stops For Permit 18080513
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-12-21 Cont ID  
Sent By skennedy Date 2018-12-21 Time 16:30 Rev Time 0.00
Received By skennedy Date 2018-12-21 Time 16:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-12-08 Cont ID  
Sent By shill Date 2018-12-08 Time 11:29 Rev Time 0.00
Received By shill Date 2018-12-08 Time 11:29 Sent To  
Notes
2018-12-08 11:31:16****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND REVIEW - ONLY MEP PAGES WERE SUBMITTED; NO
 ARCHITECTURAL/LIFE SAFETY PLANS SUBMITTED
 COMMENTS FROM PREVIOUS REVIEW, NOT ADDRESSED:
  
 1. THE PERMIT APPLICATION DOES NOT INCLUDE A UNIT
 NUMBER. PLANS ARE FOR SUITE #3. THE BUSINESS NAME ON
 THE PLAN IS "ATHENA'S BUBBLE TEA". IT APPEARS THAT THIS
 IS A NEW BUSINESS. (THIS INFORMATION WAS CHANGED IN OUR
 SYSTEM, BUT THE APPLICATION NOT REVISED, PLEASE REVISE)
  
 REVISE THE PLAN TO INCLUDE A CODE SUMMARY; IS THIS A
 CHANGE OF OCCUPANCY? WHAT WAS THE PREVIOUS
 OCCPUPANCY/USE, WHAT IS PROPOSED NEW OCCUPANCY?
  
 A THOROUGH PLAN REVIEW CANNOT BE DONE AT THIS TIME DUE
 TO INSUFFICIENT INFORMATION.
  
 2. OTHER INFORMATION WHICH SHOULD BE INCLUDED: SELECT
 METHOD OF COMPLIANCE PER FBC EB 301.1, OCCUPANT LOAD,
 BUILDING TYPE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-15 Cont ID  
Sent By shill Date 2018-09-15 Time 17:27 Rev Time 0.00
Received By shill Date 2018-09-15 Time 17:27 Sent To  
Notes
2018-09-15 17:29:21****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. THE PERMIT APPLICATION DOES NOT INCLUDE A UNIT
 NUMBER. PLANS ARE FOR SUITE #3. THE BUSINESS NAME ON
 THE PLAN IS "ATHENA'S BUBBLE TEA". IT APPEARS THAT THIS
 IS A NEW BUSINESS.
  
 REVISE THE PLAN TO INCLUDE A CODE SUMMARY; IS THIS A
 CHANGE OF OCCUPANCY? WHAT WAS THE PREVIOUS
 OCCPUPANCY/USE, WHAT IS PROPOSED NEW OCCUPANCY?
  
 A THOROUGH PLAN REVIEW CANNOT BE DONE AT THIS TIME DUE
 TO INSUFFICIENT INFORMATION.
  
 2. OTHER INFORMATION WHICH SHOULD BE INCLUDED: SELECT
 METHOD OF COMPLIANCE PER FBC EB 301.1, OCCUPANT LOAD,
 BUILDING TYPE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-12-21 Cont ID  
Sent By skennedy Date 2018-12-21 Time 16:30 Rev Time 0.00
Received By skennedy Date 2018-12-21 Time 16:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-11-30 Cont ID  
Sent By jpearson Date 2018-11-30 Time 15:19 Rev Time 0.00
Received By jpearson Date 2018-11-30 Time 13:23 Sent To  
Notes
2018-11-30 14:38:51PREVIOUS COMMENTS NOT ADDRESSED, SEE BELOW:
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ENGINEER DID NOT STAMP ONE SET OF DRAWINGS ON
 ELECTRICAL PAGES. ELECTRICAL PLAN IS REQUIRED TO BE
 DESIGNED AND SIGNED/SEALED BY A DESIGN PROFESSIONAL OR
 THE ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE
 CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC 107.1
  
 2. VALUE IS LOW, VALUE TO INCLUDE ALL LABOR, EQUIPMENT,
 MATERIALS, DESIGN FEES, ETC. RAISE VALUE.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-30 Cont ID  
Sent By fgiaquin Date 2018-08-30 Time 15:01 Rev Time 0.00
Received By fgiaquin Date 2018-08-30 Time 13:13 Sent To  
Notes
2018-08-30 15:01:22ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ENGINEER DID NOT STAMP ONE SET OF DRAWINGS ON
 ELECTRICAL PAGES. ELECTRICAL PLAN IS REQUIRED TO BE
 DESIGNED AND SIGNED/SEALED BY A DESIGN PROFESSIONAL OR
 THE ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE
 CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC 107.1
  
 2. VALUE IS LOW, VALUE TO INCLUDE ALL LABOR, EQUIPMENT,
 MATERIALS, DESIGN FEES, ETC. RAISE VALUE.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-11-20 Cont ID  
Sent By pleduc Date 2018-11-20 Time   Rev Time 0.00
Received By pleduc Date 2018-11-20 Time 12:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-08-21 Cont ID  
Sent By pleduc Date 2018-08-21 Time 16:28 Rev Time 0.00
Received By pleduc Date 2018-08-20 Time 15:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-12-21 Cont ID  
Sent By skennedy Date 2018-12-21 Time 16:30 Rev Time 0.00
Received By skennedy Date 2018-12-21 Time 16:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-11 Cont ID  
Sent By jesmith Date 2018-12-11 Time 15:42 Rev Time 0.00
Received By jesmith Date 2018-12-11 Time 15:42 Sent To  
Notes
2018-12-08 11:31:4312/8 REMOVED FROM BOARD, ROUTED TO JES DESK
2018-11-14 13:09:25B09

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-15 Cont ID  
Sent By shill Date 2018-09-15 Time 17:33 Rev Time 0.00
Received By shill Date 2018-08-10 Time 12:47 Sent To  
Notes
2018-08-14 12:47:13B11

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2018-12-21 Cont ID  
Sent By skennedy Date 2018-12-21 Time 16:04 Rev Time 0.00
Received By skennedy Date 2018-12-21 Time 16:04 Sent To  
Notes
2018-12-21 16:04:36EXISTING MECHANICAL IS SUFFICIENT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-11-29 Cont ID  
Sent By ccole Date 2018-11-29 Time 10:22 Rev Time 0.00
Received By ccole Date 2018-11-29 Time 07:20 Sent To  
Notes
2018-11-29 10:26:452ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18080513
 11/29/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) CORRECTED SHEET M1: THE PRINT IN THE NEW OUTDOOR AIR
 AND ROOF TOP UNIT SCHEDULES IS TOO FAINT TO READ.
 PLEASE EMBOLDEN THE PRINT SO THE CALCULATIONS AND DATA
 IN THE SCHEDULES CAN BE REVIEWED- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-09-04 Cont ID  
Sent By ccole Date 2018-09-04 Time 12:08 Rev Time 0.00
Received By ccole Date 2018-09-04 Time 12:08 Sent To  
Notes
2018-09-04 12:22:191ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18080513
 9/4/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE CODE COMPLIANCE DATA ON THE PLANS
 INCLUDING THE OCCUPANCY CLASSIFICATION OF THE PROPOSED
 NEW TENANT SPACE- FBC B, AND THE LEVEL OF ALTERATION
 PER CHAPTER 5 FBC EX. THE NEW TEA SHOP APPEARS TO BE
 EITHER A CHANGE OF OCCUPANCY OR A CHANGE OF USE. PLEASE
 REFER TO SECTION 1009.1 AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS IN ACCORDANCE WITH TABLE 403.3.1.1 FBC M.
  
 2) SHEET M-1: PLEASE REMOVE THE NOTE INDICATING "NO
 MECHANICAL WORK TO BE DONE" BECAUSE IT APPEARS A NEW
 EXHAUST FAN WILL BE INSTALLED IN THE TOILET ROOM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-12-21 Cont ID  
Sent By skennedy Date 2018-12-21 Time 16:30 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-12-11 Cont ID  
Sent By jesmith Date 2018-12-11 Time 15:42 Rev Time 0.00
Received By jesmith Date 2018-12-11 Time 15:42 Sent To  
Notes
2018-12-11 15:42:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 2ND REVIEW: DENIED
  
 1. SECOND REQUEST; PROVIDE SCHEDULE OF OCCUPANCY TYPE
 NOTING OCCUPANT LOAD PER FBC 1004 AND DETERMINE
 COMPLIANCE WITH MINIMUM PLUMBING FACILITIES PER FPC
 403.1 AND TABLE 403.1.
 2. RE P-2; DETAIL-TYPICAL 3 COMPARTMENT SINK. SINK IS
 USED FOR FOOD PREP. EACH COMPARTMENT SHALL DISCHARGE
 INDEPENDENTLY TO FLOOR SINK THROUGH AN AIR GAP. FPC
 802.1.1. REVISE DETAIL TO COMPLY PER FBC WPB 107.2.1.
 3. RE: PLAN SHEET P-2;
 2ND REQUEST. HIGH TEMP KITCHEN WATER DETAIL SHOWING
 COLD WATER CONNECTION TO HIGH TEMP EFFLUENT. IF THIS IS
 A PHYSICAL CONDITION OF THE FACILITY THEN PROVIDE THE
 FOLLOWING PER WPB FBC 107.2.1:
 A. IDENTIFY THE HIGH TEMPERATURE EFFLUENT ON THE
 SANITARY RISER DIAGRAM
 B. PROVIDE EFFLUENT PIPING MATERIAL SPEC RATED FOR HIGH
 TEMP AND COMPLIANT WITH FBC PL CHAPTER 7
 C. SHOW IT ON THE WATER DISTRIBUTION PLAN WITH A HIGH
 HAZARD RPZ BACKFLOW PREVENTER AND INCLUDE IN DETAIL.
 FPC 608.1.
 IF NOT, THEN REMOVE DETAIL FROM PLAN. FBC WPB AMEND
 107.2.1
 4. RE: P-1; AIR GAP FOR DISCHARGE FROM BACKFLOW
 PREVENTER SHALL BE AT THE BACKFLOW PREVENTER WITH AN
 APPROVED AIR GAP FITTING. THE AIR GAP AS NOTED ON THE
 PLANS IS SUBJECT TO COMPROMISE AND COULD POSSIBLY BE
 SUBMERGED. CHANGE NOTE ON FLOOR PLAN AND THE RISER
 DIAGRAM TO REQUIRE AN AIR GAP FITTING AT THE BFP PER
 WPB FBC 107.2.1.
 5. RE: PLAN SHEET P-1; TANKLESS WATER HEATER DETAIL
 APPEARS TO HAVE NOTES WHICH ARE NOT LEGIBLE. PLEASE
 CLARIFY PER WPB FBC 107.2.1.
 6. RE: PLAN SHEET P-2; GENERAL PLUMBING NOTES. THE BULK
 OF THE COMMENTS IS NOT LEGIBLE. PLEASE CLARIFY PER WPB
 FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-09-11 Cont ID  
Sent By shill Date 2018-09-13 Time 07:57 Rev Time 0.00
Received By jesmith Date 2018-09-13 Time 07:57 Sent To  
Notes
2018-09-12 07:04:59REVIEW COMPLETED BY JERALD SMITH 0017-P
2018-09-11 16:40:071ST REVIEW: FBC 2017 6TH EDITION
 PERMIT 180513
 PLUMBING COMMENTS:
  
 1. RE: PLAN SHEET P-1; DETAIL 1 AND DETAIL 2; WATER AND
 SANITARY PLANS. FIXTURES AND EQUIPMENT ARE NOT LABELED.
 FBC WPB AMEND 107.2.1
 2. RE: PLAN SHEET P-1; FIXTURE SCHEDULE. NUMERIC TAGS
 AND CONNECTION SIZES ARE BARELY DISCERNIBLE. INCREASE
 LEGIBILITY. FBC WPB AMEND 107.2.1
 3. RE: PLAN SHEET P-1; NOTES ARE BARELY DISCERNIBLE.
 INCREASE LEGIBILITY. FBC WPB AMEND 107.2.1
 4. RE: PLAN SHEET P-1; STANDARD PDI-G101 TABLE NOTES
 ARE BARELY DISCERNIBLE. INCREASE LEGIBILITY. FBC WPB
 AMEND 107.2.1
 5. RE: PLAN SHEET P-1; GREASE PRODUCTION TABLE NOTES
 ARE BARELY DISCERNIBLE. INCREASE LEGIBILITY. FBC WPB
 AMEND 107.2.1
 6. RE: PLAN SHEET P-1; DETAIL 3 NUMERIC TAG 05- 1"
 WASTE NEEDS TO BE AN INDIRECT WASTE DISCHARGING THROUGH
 AN AIR GAP TO A TRAPPED AND VENTED WASTE RECEPTOR. IE.
 FLOOR SINK FPC 802.1
 7. RE: PLAN SHEET P-1; DETAIL 3 NUMERIC TAG 08- 3
 COMPARTMENT SINK WASTE NEEDS TO BE AN INDIRECT WASTE
 DISCHARGING THROUGH AN AIR GAP TO A TRAPPED AND VENTED
 WASTE RECEPTOR. IE. FLOOR SINK FPC 802.1 AND IF USED IN
 ACTUAL FOOD HANDLING THEN EACH COMPARTMENT SHALL
 DISCHARGE INDEPENDENTLY TO SAID WASTE RECEPTACLE
 THROUGH AN AIR GAP. FPC 802.1.1. PROVIDE DETAIL. FBC
 WPB AMEND 107.2.1
 8. RE: PLAN SHEET P-1; DETAIL 3 NUMERIC TAG 06- TRAPPED
 AND VENTED HAND SINK TO DISCHARGE DOWNSTREAM OF GREASE
 INTERCEPTOR.
 9. RE: PLAN SHEET P-1; DETAIL 3 NUMERIC TAG 19- PROVIDE
 DETAIL AND MANUFACTURER'S INFO FOR SEWAGE PUMP. INCLUDE
 VALVING AND SIZING OF DISCHARGE TO EXISTING SANITARY.
 SHALL MEET REQUIREMENTS OF FPC 712. FBC WPB AMEND
 107.2.1
 10. RE: PLAN SHEET P-1; DETAIL 3 NUMERIC TAG 19-
 CONDENSER PUMP TO DISCHARGE THROUGH AN AIR GAP TO A
 TRAPPED AND VENTED WASTE RECEPTOR. IE. FLOOR SINK FPC
 802.1. PROVIDE DETAIL AND MANUFACTURER'S INFO FOR
 CONDENSER PUMP. FBC WPB AMEND 107.2.1
 11. RE: PLAN SHEET P-2; HIGH TEMP KITCHEN WATER DETAIL
 SHOWING COLD WATER CONNECTION TO HIGH TEMP EFFLUENT. IF
 THIS IS A PHYSICAL CONDITION OF THE FACILITY THEN SHOW
 IT ON THE WATER DISTRIBUTION PLAN WITH A HIGH HAZARD
 RPZ BACKFLOW PREVENTOR AND INCLUDE IN DETAIL. FPC
 608.1. IF NOT, THEN REMOVE DETAIL FROM PLAN. FBC WPB
 AMEND 107.2.1
 12. TEMPERED WATER TO BE DELIVERED TO HAND SINK AND
 LAVATORY IN ACCORDANCE WITH FPC 416.5
 13. RE: PLAN SHEET P-1; DETAIL 3; WATER DISTRIBUTION
 ISOMETRIC. TAG 07 NOT SHOWN ON ANY SCHEDULE. APPEARS TO
 BE A TANKLESS WATER HEATER. PROVIDE SCHEDULE AND
 DETAIL. FBC WPB AMEND 107.2.1
 14. RE: PLAN SHEET P-1; DETAIL 2; SANITARY PLAN. REVISE
 PLAN TO CLEARLY SHOW UG PIPING, SEWAGE PUMP DISCHARGE
 AND ALL FLOOR SINKS.
 15. RE: PLAN SHEET P-2; DETAIL SHOWING AIR ADMITTANCE
 VALVES. IF THIS IS A PHYSICAL CONDITION OF THE FACILITY
 THEN SHOW IT ON THE SANITARY ISOMETRIC. IF NOT, THEN
 REMOVE DETAIL FROM PLAN. FBC WPB AMEND 107.2.1
 16. CONFIRM THAT WATER TEMPERATURE TO
 UTILITY/UTENSIL/POT CLEANING FIXTURES MEET BOARD OF
 HEALTH REQUIREMENTS WITHOUT PRESENTING A HAZARD TO
 EMPLOYEES USING THESE ITEMS.
 17. PROVIDE SCHEDULE OF OCCUPANCY TYPE NOTING OCCUPANT
 LOAD PER FBC 1004 AND DETERMINE COMPLIANCE WITH MINIMUM
 PLUMBING FACILITIES PER FPC 403.1 AND TABLE 403.1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6715