| Plan Review Stops For Permit 18080513 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2018-12-21 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-12-21 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-12-21 |
Time |
16:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-12-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-12-08 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-12-08 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2018-12-08 11:31:16 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 2ND REVIEW - ONLY MEP PAGES WERE SUBMITTED; NO | | | ARCHITECTURAL/LIFE SAFETY PLANS SUBMITTED | | | COMMENTS FROM PREVIOUS REVIEW, NOT ADDRESSED: | | | | | | 1. THE PERMIT APPLICATION DOES NOT INCLUDE A UNIT | | | NUMBER. PLANS ARE FOR SUITE #3. THE BUSINESS NAME ON | | | THE PLAN IS "ATHENA'S BUBBLE TEA". IT APPEARS THAT THIS | | | IS A NEW BUSINESS. (THIS INFORMATION WAS CHANGED IN OUR | | | SYSTEM, BUT THE APPLICATION NOT REVISED, PLEASE REVISE) | | | | | | REVISE THE PLAN TO INCLUDE A CODE SUMMARY; IS THIS A | | | CHANGE OF OCCUPANCY? WHAT WAS THE PREVIOUS | | | OCCPUPANCY/USE, WHAT IS PROPOSED NEW OCCUPANCY? | | | | | | A THOROUGH PLAN REVIEW CANNOT BE DONE AT THIS TIME DUE | | | TO INSUFFICIENT INFORMATION. | | | | | | 2. OTHER INFORMATION WHICH SHOULD BE INCLUDED: SELECT | | | METHOD OF COMPLIANCE PER FBC EB 301.1, OCCUPANT LOAD, | | | BUILDING TYPE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-09-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-09-15 |
Time |
17:27 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-09-15 |
Time |
17:27 |
Sent To |
|
|
| Notes |
| 2018-09-15 17:29:21 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. THE PERMIT APPLICATION DOES NOT INCLUDE A UNIT | | | NUMBER. PLANS ARE FOR SUITE #3. THE BUSINESS NAME ON | | | THE PLAN IS "ATHENA'S BUBBLE TEA". IT APPEARS THAT THIS | | | IS A NEW BUSINESS. | | | | | | REVISE THE PLAN TO INCLUDE A CODE SUMMARY; IS THIS A | | | CHANGE OF OCCUPANCY? WHAT WAS THE PREVIOUS | | | OCCPUPANCY/USE, WHAT IS PROPOSED NEW OCCUPANCY? | | | | | | A THOROUGH PLAN REVIEW CANNOT BE DONE AT THIS TIME DUE | | | TO INSUFFICIENT INFORMATION. | | | | | | 2. OTHER INFORMATION WHICH SHOULD BE INCLUDED: SELECT | | | METHOD OF COMPLIANCE PER FBC EB 301.1, OCCUPANT LOAD, | | | BUILDING TYPE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2018-12-21 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-12-21 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-12-21 |
Time |
16:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2018-11-30 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-11-30 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-11-30 |
Time |
13:23 |
Sent To |
|
|
| Notes |
| 2018-11-30 14:38:51 | PREVIOUS COMMENTS NOT ADDRESSED, SEE BELOW: | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. ENGINEER DID NOT STAMP ONE SET OF DRAWINGS ON | | | ELECTRICAL PAGES. ELECTRICAL PLAN IS REQUIRED TO BE | | | DESIGNED AND SIGNED/SEALED BY A DESIGN PROFESSIONAL OR | | | THE ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE | | | CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC 107.1 | | | | | | 2. VALUE IS LOW, VALUE TO INCLUDE ALL LABOR, EQUIPMENT, | | | MATERIALS, DESIGN FEES, ETC. RAISE VALUE. | | | | | | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING | | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WPB | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-08-30 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-08-30 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-08-30 |
Time |
13:13 |
Sent To |
|
|
| Notes |
| 2018-08-30 15:01:22 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. ENGINEER DID NOT STAMP ONE SET OF DRAWINGS ON | | | ELECTRICAL PAGES. ELECTRICAL PLAN IS REQUIRED TO BE | | | DESIGNED AND SIGNED/SEALED BY A DESIGN PROFESSIONAL OR | | | THE ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE | | | CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC 107.1 | | | | | | 2. VALUE IS LOW, VALUE TO INCLUDE ALL LABOR, EQUIPMENT, | | | MATERIALS, DESIGN FEES, ETC. RAISE VALUE. | | | | | | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING | | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WPB | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-11-20 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-11-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-11-20 |
Time |
12:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-08-21 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-08-21 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-08-20 |
Time |
15:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-12-21 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-12-21 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-12-21 |
Time |
16:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-12-11 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2018-12-11 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2018-12-11 |
Time |
15:42 |
Sent To |
|
|
| Notes |
| 2018-12-08 11:31:43 | 12/8 REMOVED FROM BOARD, ROUTED TO JES DESK | | 2018-11-14 13:09:25 | B09 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-09-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-09-15 |
Time |
17:33 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-08-10 |
Time |
12:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2018-12-21 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-12-21 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-12-21 |
Time |
16:04 |
Sent To |
|
|
| Notes |
| 2018-12-21 16:04:36 | EXISTING MECHANICAL IS SUFFICIENT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2018-11-29 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-11-29 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-11-29 |
Time |
07:20 |
Sent To |
|
|
| Notes |
| 2018-11-29 10:26:45 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT #18080513 | | | 11/29/18 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) CORRECTED SHEET M1: THE PRINT IN THE NEW OUTDOOR AIR | | | AND ROOF TOP UNIT SCHEDULES IS TOO FAINT TO READ. | | | PLEASE EMBOLDEN THE PRINT SO THE CALCULATIONS AND DATA | | | IN THE SCHEDULES CAN BE REVIEWED- SECTION 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-09-04 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-09-04 |
Time |
12:08 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-09-04 |
Time |
12:08 |
Sent To |
|
|
| Notes |
| 2018-09-04 12:22:19 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #18080513 | | | 9/4/18 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE CODE COMPLIANCE DATA ON THE PLANS | | | INCLUDING THE OCCUPANCY CLASSIFICATION OF THE PROPOSED | | | NEW TENANT SPACE- FBC B, AND THE LEVEL OF ALTERATION | | | PER CHAPTER 5 FBC EX. THE NEW TEA SHOP APPEARS TO BE | | | EITHER A CHANGE OF OCCUPANCY OR A CHANGE OF USE. PLEASE | | | REFER TO SECTION 1009.1 AND PROVIDE MINIMUM VENTILATION | | | CALCULATIONS IN ACCORDANCE WITH TABLE 403.3.1.1 FBC M. | | | | | | 2) SHEET M-1: PLEASE REMOVE THE NOTE INDICATING "NO | | | MECHANICAL WORK TO BE DONE" BECAUSE IT APPEARS A NEW | | | EXHAUST FAN WILL BE INSTALLED IN THE TOILET ROOM. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2018-12-21 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-12-21 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2018-12-11 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2018-12-11 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2018-12-11 |
Time |
15:42 |
Sent To |
|
|
| Notes |
| 2018-12-11 15:42:21 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | 2ND REVIEW: DENIED | | | | | | 1. SECOND REQUEST; PROVIDE SCHEDULE OF OCCUPANCY TYPE | | | NOTING OCCUPANT LOAD PER FBC 1004 AND DETERMINE | | | COMPLIANCE WITH MINIMUM PLUMBING FACILITIES PER FPC | | | 403.1 AND TABLE 403.1. | | | 2. RE P-2; DETAIL-TYPICAL 3 COMPARTMENT SINK. SINK IS | | | USED FOR FOOD PREP. EACH COMPARTMENT SHALL DISCHARGE | | | INDEPENDENTLY TO FLOOR SINK THROUGH AN AIR GAP. FPC | | | 802.1.1. REVISE DETAIL TO COMPLY PER FBC WPB 107.2.1. | | | 3. RE: PLAN SHEET P-2; | | | 2ND REQUEST. HIGH TEMP KITCHEN WATER DETAIL SHOWING | | | COLD WATER CONNECTION TO HIGH TEMP EFFLUENT. IF THIS IS | | | A PHYSICAL CONDITION OF THE FACILITY THEN PROVIDE THE | | | FOLLOWING PER WPB FBC 107.2.1: | | | A. IDENTIFY THE HIGH TEMPERATURE EFFLUENT ON THE | | | SANITARY RISER DIAGRAM | | | B. PROVIDE EFFLUENT PIPING MATERIAL SPEC RATED FOR HIGH | | | TEMP AND COMPLIANT WITH FBC PL CHAPTER 7 | | | C. SHOW IT ON THE WATER DISTRIBUTION PLAN WITH A HIGH | | | HAZARD RPZ BACKFLOW PREVENTER AND INCLUDE IN DETAIL. | | | FPC 608.1. | | | IF NOT, THEN REMOVE DETAIL FROM PLAN. FBC WPB AMEND | | | 107.2.1 | | | 4. RE: P-1; AIR GAP FOR DISCHARGE FROM BACKFLOW | | | PREVENTER SHALL BE AT THE BACKFLOW PREVENTER WITH AN | | | APPROVED AIR GAP FITTING. THE AIR GAP AS NOTED ON THE | | | PLANS IS SUBJECT TO COMPROMISE AND COULD POSSIBLY BE | | | SUBMERGED. CHANGE NOTE ON FLOOR PLAN AND THE RISER | | | DIAGRAM TO REQUIRE AN AIR GAP FITTING AT THE BFP PER | | | WPB FBC 107.2.1. | | | 5. RE: PLAN SHEET P-1; TANKLESS WATER HEATER DETAIL | | | APPEARS TO HAVE NOTES WHICH ARE NOT LEGIBLE. PLEASE | | | CLARIFY PER WPB FBC 107.2.1. | | | 6. RE: PLAN SHEET P-2; GENERAL PLUMBING NOTES. THE BULK | | | OF THE COMMENTS IS NOT LEGIBLE. PLEASE CLARIFY PER WPB | | | FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-09-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-09-13 |
Time |
07:57 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2018-09-13 |
Time |
07:57 |
Sent To |
|
|
| Notes |
| 2018-09-12 07:04:59 | REVIEW COMPLETED BY JERALD SMITH 0017-P | | 2018-09-11 16:40:07 | 1ST REVIEW: FBC 2017 6TH EDITION | | | PERMIT 180513 | | | PLUMBING COMMENTS: | | | | | | 1. RE: PLAN SHEET P-1; DETAIL 1 AND DETAIL 2; WATER AND | | | SANITARY PLANS. FIXTURES AND EQUIPMENT ARE NOT LABELED. | | | FBC WPB AMEND 107.2.1 | | | 2. RE: PLAN SHEET P-1; FIXTURE SCHEDULE. NUMERIC TAGS | | | AND CONNECTION SIZES ARE BARELY DISCERNIBLE. INCREASE | | | LEGIBILITY. FBC WPB AMEND 107.2.1 | | | 3. RE: PLAN SHEET P-1; NOTES ARE BARELY DISCERNIBLE. | | | INCREASE LEGIBILITY. FBC WPB AMEND 107.2.1 | | | 4. RE: PLAN SHEET P-1; STANDARD PDI-G101 TABLE NOTES | | | ARE BARELY DISCERNIBLE. INCREASE LEGIBILITY. FBC WPB | | | AMEND 107.2.1 | | | 5. RE: PLAN SHEET P-1; GREASE PRODUCTION TABLE NOTES | | | ARE BARELY DISCERNIBLE. INCREASE LEGIBILITY. FBC WPB | | | AMEND 107.2.1 | | | 6. RE: PLAN SHEET P-1; DETAIL 3 NUMERIC TAG 05- 1" | | | WASTE NEEDS TO BE AN INDIRECT WASTE DISCHARGING THROUGH | | | AN AIR GAP TO A TRAPPED AND VENTED WASTE RECEPTOR. IE. | | | FLOOR SINK FPC 802.1 | | | 7. RE: PLAN SHEET P-1; DETAIL 3 NUMERIC TAG 08- 3 | | | COMPARTMENT SINK WASTE NEEDS TO BE AN INDIRECT WASTE | | | DISCHARGING THROUGH AN AIR GAP TO A TRAPPED AND VENTED | | | WASTE RECEPTOR. IE. FLOOR SINK FPC 802.1 AND IF USED IN | | | ACTUAL FOOD HANDLING THEN EACH COMPARTMENT SHALL | | | DISCHARGE INDEPENDENTLY TO SAID WASTE RECEPTACLE | | | THROUGH AN AIR GAP. FPC 802.1.1. PROVIDE DETAIL. FBC | | | WPB AMEND 107.2.1 | | | 8. RE: PLAN SHEET P-1; DETAIL 3 NUMERIC TAG 06- TRAPPED | | | AND VENTED HAND SINK TO DISCHARGE DOWNSTREAM OF GREASE | | | INTERCEPTOR. | | | 9. RE: PLAN SHEET P-1; DETAIL 3 NUMERIC TAG 19- PROVIDE | | | DETAIL AND MANUFACTURER'S INFO FOR SEWAGE PUMP. INCLUDE | | | VALVING AND SIZING OF DISCHARGE TO EXISTING SANITARY. | | | SHALL MEET REQUIREMENTS OF FPC 712. FBC WPB AMEND | | | 107.2.1 | | | 10. RE: PLAN SHEET P-1; DETAIL 3 NUMERIC TAG 19- | | | CONDENSER PUMP TO DISCHARGE THROUGH AN AIR GAP TO A | | | TRAPPED AND VENTED WASTE RECEPTOR. IE. FLOOR SINK FPC | | | 802.1. PROVIDE DETAIL AND MANUFACTURER'S INFO FOR | | | CONDENSER PUMP. FBC WPB AMEND 107.2.1 | | | 11. RE: PLAN SHEET P-2; HIGH TEMP KITCHEN WATER DETAIL | | | SHOWING COLD WATER CONNECTION TO HIGH TEMP EFFLUENT. IF | | | THIS IS A PHYSICAL CONDITION OF THE FACILITY THEN SHOW | | | IT ON THE WATER DISTRIBUTION PLAN WITH A HIGH HAZARD | | | RPZ BACKFLOW PREVENTOR AND INCLUDE IN DETAIL. FPC | | | 608.1. IF NOT, THEN REMOVE DETAIL FROM PLAN. FBC WPB | | | AMEND 107.2.1 | | | 12. TEMPERED WATER TO BE DELIVERED TO HAND SINK AND | | | LAVATORY IN ACCORDANCE WITH FPC 416.5 | | | 13. RE: PLAN SHEET P-1; DETAIL 3; WATER DISTRIBUTION | | | ISOMETRIC. TAG 07 NOT SHOWN ON ANY SCHEDULE. APPEARS TO | | | BE A TANKLESS WATER HEATER. PROVIDE SCHEDULE AND | | | DETAIL. FBC WPB AMEND 107.2.1 | | | 14. RE: PLAN SHEET P-1; DETAIL 2; SANITARY PLAN. REVISE | | | PLAN TO CLEARLY SHOW UG PIPING, SEWAGE PUMP DISCHARGE | | | AND ALL FLOOR SINKS. | | | 15. RE: PLAN SHEET P-2; DETAIL SHOWING AIR ADMITTANCE | | | VALVES. IF THIS IS A PHYSICAL CONDITION OF THE FACILITY | | | THEN SHOW IT ON THE SANITARY ISOMETRIC. IF NOT, THEN | | | REMOVE DETAIL FROM PLAN. FBC WPB AMEND 107.2.1 | | | 16. CONFIRM THAT WATER TEMPERATURE TO | | | UTILITY/UTENSIL/POT CLEANING FIXTURES MEET BOARD OF | | | HEALTH REQUIREMENTS WITHOUT PRESENTING A HAZARD TO | | | EMPLOYEES USING THESE ITEMS. | | | 17. PROVIDE SCHEDULE OF OCCUPANCY TYPE NOTING OCCUPANT | | | LOAD PER FBC 1004 AND DETERMINE COMPLIANCE WITH MINIMUM | | | PLUMBING FACILITIES PER FPC 403.1 AND TABLE 403.1. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6715 |
|
|