Plan Review Details - Permit 18080473
Plan Review Stops For Permit 18080473
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-09-26 Cont ID  
Sent By dbattles Date 2018-09-26 Time 09:14 Rev Time 0.00
Received By dbattles Date 2018-09-25 Time 14:15 Sent To  
Notes
2018-09-26 09:19:01W.P.B. PERMIT: 18080473
 REVIEWED: SEPTEMBER 26, 2018
  
 PROVISO:
 PROVIDE SURVEY TO SHOW THE ADDITIONS LOCATION TO
 PROPERTY LINES.
 SURVEY TO INCLUDE ANY EASEMENTS ON THE SUBJECT
 PROPERTY.
 HAVE SURVEY AVAILABLE AT SITE PRIOR TO FOUNDATION
 INSPECTION.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-09-14 Cont ID  
Sent By jpearson Date 2018-09-04 Time 09:59 Rev Time 0.00
Received By jpearson Date 2018-09-04 Time 09:58 Sent To  
Notes
2018-09-14 15:08:34CHANGED VALUE TO $213,000.00 PER CONTRACT PROVIDED.
 CHANGED STATUS TO PASSED.
  
  
  
2018-09-04 09:58:56CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-08-24 Cont ID  
Sent By fmittner Date 2018-08-24 Time 16:39 Rev Time 0.00
Received By fmittner Date 2018-08-24 Time 16:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-26 Cont ID  
Sent By skennedy Date 2018-09-26 Time 11:00 Rev Time 0.00
Received By skennedy Date 2018-08-09 Time 14:24 Sent To  
Notes
2018-08-10 14:24:23R25

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-10-04 Cont ID  
Sent By dharvey Date 2018-10-04 Time 15:46 Rev Time 0.00
Received By dharvey Date 2018-10-04 Time 15:46 Sent To  
Notes
2018-10-04 15:47:26RECEIPT PROVIDED. MU-2019-033752-0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-09-26 Cont ID  
Sent By dbattles Date 2018-09-26 Time 09:19 Rev Time 0.00
Received By dbattles Date 2018-09-26 Time 09:19 Sent To  
Notes
2018-09-26 09:20:11[FBC AMENDED 109]PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-09-26 Cont ID  
Sent By skennedy Date 2018-09-26 Time 11:00 Rev Time 0.00
Received By skennedy Date 2018-09-26 Time 11:00 Sent To  
Notes
2018-09-26 11:01:13OWNER OR AGENT SHOULD SIGN ENERGY FORMS WHEN
 RE-SUBMITTING.

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-10-04 Cont ID  
Sent By dharvey Date 2018-10-04 Time 15:48 Rev Time 0.00
Received By jesmith Date 2018-10-23 Time 07:44 Sent To  
Notes
2018-10-04 15:48:59NOTES FROM PLUMBING REVIEW ADDED AS A NOTE ON THE PLAN

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-09-18 Cont ID  
Sent By shill Date 2018-09-18 Time 09:08 Rev Time 0.00
Received By jesmith Date 2018-09-18 Time 09:06 Sent To  
Notes
2018-09-18 09:08:451ST REVIEW: FBC 2017 6TH EDITION
 PERMIT 18080473
 PLUMBING COMMENTS: DENIED
  
 1ST REVIEW: FBC 2017 6TH EDITION
 PERMIT 18080473
 PLUMBING COMMENTS: DENIED
  
 1. ARCHITECTURAL SHOWS NO WORK IN EXISTING 2 CAR
 GARAGE. ELECTRICAL PLAN SHOWS WATER HEATER IN EXISTING
 2 CAR GARAGE AND A NEW ELECTRICAL PANEL TO ACCOMMODATE
 THE RENOVATED RESIDENCE. WATER HEATER IS NOT SHOWN ON
 THE PLUMBING PLAN. IS THE WATER HEATER EXISTING?
 RELOCATED? NEW? PLEASE CLARIFY. SHOW WATER HEATER
 LOCATION, SIZE, AND TYPE ON THE PLUMBING PLAN; INDICATE
 NEW OR EXISTING (AND RELOCATED IF APPLICABLE) AND IF
 NEW OR RELOCATED, CONFIRM THAT THE REQUIREMENTS OF FBC
 RES CHAPTER 28 ARE COMPLIED WITH PER FBC WPB AMEND
 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6715
  
  
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2018-09-26 Cont ID  
Sent By dbattles Date 2018-09-26 Time 09:20 Rev Time 0.00
Received By dbattles Date 2018-09-26 Time 09:20 Sent To  
Notes
2018-09-26 09:30:13W.P.B. PERMIT: 18080473
 REVIEWED: SEPTEMBER 26, 2018
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
  
 FBC R = FBC RESIDENTIAL
  
 ROOFING SUBMITTAL NEEDS ADDITIONAL INFORMATION.
 [RAS 117]PROVIDE ENGINEERING FOR ENHANCED NAILING AS
 STATED IN PRODUCT APPROVAL UNDER GENERAL LIMITATIONS.
 CHOOSE WHICH SYSTEM IS BEING UTILIZED ON THE PRODUCT
 APPROVAL AND ONLY SUPPLY APPLICABLE SHEETS.
  
 THIS CAN BE RE-SUBMITTAL AS A 2ND REVIEW, OR IT CAN BE
 DEFERED AND SUBMITTED WITH THE ROOFING SUB PERMIT.
 CURRENTLY I PUT THE STATUS AS SUBMITTAL IN SUB PERMIT,
 BUT I WILL REVIEW AND CHANGE STATUS IF IT IS SUBMITTED
 AS 2ND REVIEW.
  
 THE TWO COPIES OF PRODUCT APPROVAL ARE WITH THE PERMIT,
 BUT THEY ARE NOT STAMPED AS APPROVED.
 THEY SHOULD GO BACK TO THE CONTRACTOR.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2018-08-24 Cont ID  
Sent By fmittner Date 2018-08-24 Time 16:39 Rev Time 0.00
Received By fmittner Date 2018-08-24 Time 16:39 Sent To  
Notes
***NONE***